| 2013-08-15 15:22:45 | BUILDING PLAN REVIEW |
| | PERMIT: 13071119 |
| | ADD: 1617 N FLAGLER DR # 602 |
| | CONT: ED'S ISLAND TIME SERVICES, INC |
| | TEL: (561)541-0004 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: AUGUST 15, 2010 |
| | ACTION: PROVISO |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) ID-02 PLANS INDICATE THE USE OF TRIM, NOT SPECIFIED |
| | IF WOOD OR FOAM. |
| | 2010 FBC-B 806.3 FOAM PLASTIC. |
| | FOAM PLASTIC USED AS TRIM IN ANY OCCUPANCY SHALL COMPLY |
| | WITH SECTION 2604.2. |
| | 2604.2 INTERIOR TRIM. |
| | FOAM PLASTIC USED AS INTERIOR TRIM SHALL COMPLY WITH |
| | SECTIONS 2604.2.1 THROUGH 2604.2.4. |
| | [F] 2604.2.1 DENSITY. |
| | THE MINIMUM DENSITY OF THE INTERIOR TRIM SHALL BE 20 |
| | PCF (320 KG/M3). |
| | [F] 2604.2.2 THICKNESS. |
| | THE MAXIMUM THICKNESS OF THE INTERIOR TRIM SHALL BE 1/2 |
| | INCH (12.7 MM) AND THE MAXIMUM WIDTH SHALL BE 8 INCHES |
| | (204 MM). |
| | [F] 2604.2.3 AREA LIMITATION. |
| | THE INTERIOR TRIM SHALL NOT CONSTITUTE MORE THAN 10 |
| | PERCENT OF THE SPECIFIC WALL OR CEILING AREAS TO WHICH |
| | IT IS ATTACHED. |
| | [F] 2604.2.4 FLAME SPREAD. |
| | THE FLAME SPREAD INDEX SHALL NOT EXCEED 75 WHERE TESTED |
| | IN ACCORDANCE WITH ASTM E 84 OR UL 723. THE |
| | SMOKE-DEVELOPED INDEX SHALL NOT BE LIMITED. |
| | EXCEPTION: WHEN THE INTERIOR TRIM MATERIAL HAS BEEN |
| | TESTED AS AN INTERIOR FINISH IN ACCORDANCE WITH NFPA |
| | 286 AND COMPLIES WITH THE ACCEPTANCE CRITERIA IN |
| | SECTION 803.1.2.1, IT SHALL NOT BE REQUIRED TO BE |
| | TESTED FOR FLAME SPREAD INDEX IN ACCORDANCE WITH ASTM E |
| | 84 OR UL 723. |
| | |
| | 2) A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | 2B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING |
| | FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF |
| | NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 100. |
| | |
| | 2C) FBC-B 2010 603.2 EXCEPTION 2 WOOD FLOORS |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FBC-B 2010 |
| | JAMES A. WITMER CBO |