Plan Review Details - Permit 13071103
Plan Review Stops For Permit 13071103
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2013-11-16 Cont ID  
Sent By jwitmer Date 2013-11-16 Time 07:47 Rev Time 0.00
Received By jwitmer Date 2013-11-16 Time 07:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-10-02 Cont ID  
Sent By jwitmer Date 2013-10-02 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2013-10-02 Time 07:45 Sent To  
Notes
2013-10-02 07:46:38PB OUTLET MALLS:
 BUILDING PROVISO:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-02 Cont ID  
Sent By jwitmer Date 2013-08-02 Time 07:36 Rev Time 0.00
Received By jwitmer Date 2013-08-02 Time 06:31 Sent To  
Notes
2013-08-02 07:36:45BUILDING PLAN REVIEW
 PERMIT: 13071103
 ADD: 1751 PALM BEACH LAKES # E117
 CONT: TBD TO BE DETERMINED
 TEL: (407)469-5599 GARY BARSON
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: AUGUST 02/ 2013
 ACTION:DENIED
  
 1) PLANS ARE NOT STAMPED REVIEWED BY THE PALM BEACH
 OUTLET MALL OF THEIR REVIEW AND APPROVAL.
  
 2) SHEET A4.2 DETAIL # 2 THE ENLARGED ACCESSIBLE
 DRESSING ROOM.
 2010 FBC-ACCESSIBILITY 803.4 BENCHES.
 803.4 BENCHES.
 A BENCH COMPLYING WITH 903 SHALL BE PROVIDED WITHIN THE
 ROOM.
  
 903.4 BACK SUPPORT.
 THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE
 AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 INCHES
 (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A POINT 2
 INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE TO A
 POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM)
 MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED
 HORIZONTALLY.
  
 ADVISORY 903.4 BACK SUPPORT.
 TO ASSIST IN TRANSFERRING TO THE BENCH, CONSIDER
 PROVIDING GRAB BARS ON A WALL ADJACENT TO THE BENCH,
 BUT NOT ON THE SEAT BACK. IF PROVIDED, GRAB BARS CANNOT
 OBSTRUCT TRANSFER TO THE BENCH.
  
 903.6 STRUCTURAL STRENGTH.
 ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS
 USED WHEN A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS
 (1112 N) IS APPLIED AT ANY POINT ON THE SEAT, FASTENER,
 MOUNTING DEVICE, OR SUPPORTING STRUCTURE.
  
 3) PB OUTLET MALLS:
 BUILDING PROVISO:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-11-18 Cont ID  
Sent By skennedy Date 2013-11-18 Time 11:09 Rev Time 0.00
Received By skennedy Date 2013-11-18 Time 11:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-10-18 Cont ID  
Sent By dharvey Date 2013-10-18 Time 14:39 Rev Time 0.00
Received By skennedy Date 2013-10-18 Time 14:34 Sent To  
Notes
2013-10-18 14:39:25REVIEW COMMENTS OF 8/15/13 BY DOUG HARVEY DO NOT APPEAR
 TO HAVE BEEN ADDRESSED IN THIS RESUBMITTAL. PLEASE
 RESUBMIT AND INCLUDE A TRANSMITTAL LETTER IDENTIFYING
 RESPONSES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-08-15 Cont ID  
Sent By dharvey Date 2013-08-15 Time 16:08 Rev Time 0.00
Received By dharvey Date 2013-08-15 Time 14:45 Sent To  
Notes
2013-08-15 16:08:46WHOLE BUILDING ENERGY CODE REPORT REQUIRED PER FBC-EC
 101.4.9
 NOTE ON FRONT PAGE STATE "2010 NATIONAL ELECTRIC CODE,
 NFPA" AND NO SUCH DOCUMENT EXISTS
 PROVIDE LISTING INFORMATION ON SUSPENDED CEILING IF
 USED FOR SUPPORT OF FIXTURES 110.3, 410.36 (B)
 LIGHTING LOADS ON LOAD CALCS DO NOT APPEAR TO AGREE
 WITH THE ENERGY CALCULATION PROVIDED?
 NO FIRE ALARM SHOWN, ASSUMED TO BE PERMITTED SEPARATELY
 ENSURE STROBES ARE VISIBLE IN DRESSING ROOMS
 SEPARATE PERMITS REQUIRED FOR: VIDEO, AUDIO, ALARM,
 PHONE, DATA AND/OR OTHER SYSTEMS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-10-07 Cont ID  
Sent By scaldero Date 2013-10-07 Time 12:49 Rev Time 0.00
Received By scaldero Date 2013-10-07 Time 12:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-08-06 Cont ID  
Sent By scaldero Date 2013-08-06 Time 15:53 Rev Time 0.00
Received By scaldero Date 2013-08-06 Time 15:53 Sent To  
Notes
2013-08-06 15:56:33PERMIT #13071103
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ***PLANS STAMPED, HOWEVER "FAILED" UNTIL BUILDING
 COMMENTS ADDRESSED.****
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-11-18 Cont ID  
Sent By skennedy Date 2013-11-18 Time 11:20 Rev Time 0.00
Received By skennedy Date 2013-11-12 Time 11:37 Sent To  
Notes
2013-11-13 11:39:18PLACED IN LARGE DENIED TBD. EXPEDITER TO COME BACK IN
 AND INSERT SHEETS. THEREAFTER, PLEASE RETURN TO SAK
 DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-18 Cont ID  
Sent By skennedy Date 2013-10-18 Time 14:40 Rev Time 0.00
Received By skennedy Date 2013-10-18 Time 14:40 Sent To  
Notes
2013-10-18 14:42:11NOTIFIED CONTACT GARY BARSON (SPOKE TO JASON). PLACED
 SUBMITTAL IN DENIED PLANS LARGE, TBD.
2013-09-28 06:58:14B30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-22 Cont ID  
Sent By jwitmer Date 2013-08-22 Time 08:53 Rev Time 0.00
Received By jwitmer Date 2013-07-30 Time 06:42 Sent To  
Notes
2013-07-31 06:44:22B19

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-10-16 Cont ID  
Sent By hmoser Date 2013-10-16 Time 14:07 Rev Time 0.00
Received By hmoser Date 2013-10-16 Time 14:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-08-13 Cont ID  
Sent By hmoser Date 2013-08-13 Time 12:32 Rev Time 0.00
Received By hmoser Date 2013-08-13 Time 10:51 Sent To  
Notes
2013-08-13 12:32:34PLANS DENIED
 PLANS NOT STAMPED OR REVIEWED BY PALM BEACH OUTLET MALL
 .
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2013-09-30 Cont ID  
Sent By lwagner Date 2013-09-30 Time 16:22 Rev Time 0.00
Received By lwagner Date 2013-09-30 Time 16:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-08-08 Cont ID  
Sent By lwagner Date 2013-08-08 Time 11:09 Rev Time 0.00
Received By lwagner Date 2013-08-08 Time 09:59 Sent To  
Notes
2013-08-08 10:51:13FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
  
 1. THE COMMON AREA TOILET FACILITIES APPEAR TO BE OVER
 500' FROM THE STORE ENTRANCE. PLEASE VERIFY THE PUBLIC
 ACCESS DISTANCE WITH THE PALM BEACH OUTLET MALL. THE
 ROUTE TO THE STORE FACILITIES IS THROUGH A STORAGE
 (STOCK) AREA.
  
 403.3.2 LOCATION OF TOILET FACILITIES IN OCCUPANCIES
 OTHER THAN COVERED MALLS.
 IN OCCUPANCIES OTHER THAN COVERED MALL BUILDINGS, THE
 REQUIRED PUBLIC AND EMPLOYEE TOILET FACILITIES SHALL BE
 LOCATED NOT MORE THAN ONE STORY ABOVE OR BELOW THE
 SPACE REQUIRED TO BE PROVIDED WITH TOILET FACILITIES,
 AND THE PATH OF TRAVEL TO SUCH FACILITIES SHALL NOT
 EXCEED A DISTANCE OF 500 FEET (152 M).
  
 403.3.1 ACCESS.
 THE ROUTE TO THE PUBLIC TOILET FACILITIES REQUIRED BY
 SECTION 403.3 SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS OR CLOSETS. ACCESS TO THE REQUIRED FACILITIES
 SHALL BE FROM WITHIN THE BUILDING OR FROM THE EXTERIOR
 OF THE BUILDING. ALL ROUTES SHALL COMPLY WITH THE
 ACCESSIBILITY REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY. THE PUBLIC SHALL HAVE ACCESS TO
 THE REQUIRED TOILET FACILITIES AT ALL TIMES THAT THE
 BUILDING IS OCCUPIED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop POLICE POLICE
Rev No 1 Status N Date 2013-08-22 Cont ID  
Sent By jwitmer Date 2013-08-22 Time 08:53 Rev Time 0.00
Received By jwitmer Date 2013-08-22 Time 08:53 Sent To  
Notes
2013-08-22 08:55:34REVIEW NOT REQUIRED AS PER E-MAIL SENT BY R BROWN DATED
 8/21/2013 8:37 PM.

Review Stop Z ZONING
Rev No 1 Status P Date 2013-08-08 Cont ID  
Sent By eschnide Date 2013-08-08 Time 14:40 Rev Time 0.75
Received By eschneid Date 2013-08-08 Time 14:40 Sent To  
Notes
2013-08-08 14:40:45SIGNS AND AWNINGS REQUIRE SEPARATE PERMITS.
2013-08-01 16:16:258/1/13