Plan Review Details - Permit 13071098
Plan Review Stops For Permit 13071098
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-05-02 Cont ID  
Sent By shill Date 2014-05-02 Time 09:16 Rev Time 0.00
Received By shill Date 2014-05-02 Time 09:16 Sent To  
Notes
2014-05-02 09:16:26STOREFRONT SHOPS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-01-02 Cont ID  
Sent By jwitmer Date 2014-01-02 Time 10:20 Rev Time 0.00
Received By jwitmer Date 2014-01-02 Time 09:13 Sent To  
Notes
2014-01-02 10:20:36BUILDING PLAN REVIEW
 PERMIT: 13071098
 ADD: 1865 PALM BEACH LAKES BLDG' "B1"SHELL
 CONT: EMJ KERI NEVEL
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURSDAY 01/02/2014
 ACTION: BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
  
  
  
 7) PLEASE SUBMIT THE FOLLOWING PRODUCT APPROVALS: 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, SWING DOORS, ROLL UP DOORS &
 ROOF HATCH
  
  
 BUILDING PROVISO:
 MIAMI-DADE PRODUCT APPROVAL: 11-0722.10 ROOF HATCH +/-
 70 PSF PLEASE REVIEW SHEET A-141, TENANT B-12 THIS ROOF
 HATCH IS IN ROOF ZONE # 2 WITH ASSOCIATED PRESSURES OF
 -76.5 IN EXCESS OF THE PRODUCT APPROVAL, THE ROOF HATCH
 NEEDS TO BE MOVED INTO ROOF ZONE # 1 FOR THE ROOF TOP
 PRESSURES TO BE LOWER THAN THE LIMITS IN THE PRODUCT
 APPROVAL. TENANTS B13, B14 & B15 OK.
  
 BUILDING PROVISO: SEPARATE PERMIT IS REQUIRED REVIEWED
 UNDER MASTER.
 NOA 12-0514.04 FIRESTONE - FIRESTONE ULTRA PLY TPO &
 TPO XR SINGLE PLY ROOF SYSTEMS OVER STEEL DECK.
 ++++++++++++++++++++++++++++++++++
 SHOP DRAWING STAMP COVER SHEET LIST THE FOLLOWING
 NOTES:
 1) PAGE 28 MECHANICALLY FASTENED ZONE 1
 2) PAGE 6 FULLY ADHERED INSTALATION FOR ZONE 2
 3) GENERAL LIMITATION # 7 ALLOWS FOR ZONE 3
 INSTALLATION PAGE 8 DEFINES ZONE 3
 4) INSULATION SEE PAGE 12 R-VALUE PAGE 30.
 ++++++++++++++++++++++++++++++++++
  
 NOA 11-1013.05 ALUMINUM SLIDING DOOR- NON-MOTORIZED HIS
 TYPE DOOR NOT SHOWN IN DOOR SCHEDULE PLEASE REMOVE FROM
 PACKAGE.
  
  
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-10-29 Cont ID  
Sent By jwitmer Date 2013-10-29 Time 10:51 Rev Time 0.00
Received By jwitmer Date 2013-10-29 Time 07:28 Sent To  
Notes
2013-10-29 10:51:32BUILDING PLAN REVIEW
 PERMIT: 13071098
 ADD: 1865 PALM BEACH LAKES BLDG' "B1"SHELL
 CONT: EMJ KERI NEVEL
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUESDAY OCT. 29/2013
 ACTION: DENIED
  
  
 1-4A) COMPLIED.
  
 4B) 2ND REQUEST FOUNDATIONS INDICATES THERE IS A SOILS
 REPORT THAT HAS BEEN COMPLETED, PLEASE SUPPLY REPORT BY
 ECS DATED JUNE 16/ 2012. 2010 FBC-B 1803.2
 INVESTIGATION REQUIED.
  
 4C) 2ND REQUEST, ADDING ANOTE TO THE PLANS DOES NOT
 MEET CODE COMPLIANCE. UNDER THE HEADING TILT-UP
 CONCRETE WALL PANELS, CITY OF WEST PALM BEACH LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING CODE (FBC) 2010
 CHAPTER 1 ADMINISTRATION 110.3.9 OTHER INSPECTION
 SEERVICES, THIS PROJECT BEING TILT WALL WILL QUALIFY
 FOR A RESIDENT INSPECTOR. SUCH INSPECTORS SHALL BE
 ADEQUATELY PRESENT AT TIMES WORK IS UNDERWAY ON THE
 STRUCTURAL ELEMENTS OF THE BUILDING. SUCH INSPECTORS
 SHALL BE A REGISTERED ARCHITECT, OR ENGINEER, OR A
 PERSON LICENSED UNDER CHAPTER 468, PART XII, FLORIDA
 STATUTES. SUCH INSPECTORS SHALL SUBMIT WEEKLY PROGRESS
 REPORTS INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
 PLEASE CONTACT KEN CONRAD THE DIRECTOR OF THE RESIDENT
 INSPECTOR PROGRAM FOR REQUIREMENTS FORMS AND ADDITIONAL
 INFORMATION ON THIS PROGRAM AND REQUIREMENTS :
 KEN CONRAD
 TEL: 561-805-6666
 FAX: 561-805-6676
 E-MAIL: KCONRAD @WPB.ORG
  
 5) BUILDING PROVISO:GC TO SUBMIT SIGNED & SEALED SHOP
 DRAWING, FL 61G1-23.015 (2) THE ARCHITECT IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC...BEFORE SUBMITTAL TO
 THE BUILDING DEPARTMENT.
 SHEET S002 RTU HEADING THE NOTE AS FOLLOWS: GC TO
 PROVIDE PRE-ENGINEERED RTU TIE DOWNS OR EQUIVALENT
 ENGINEERED TIE-DOWN SOLUTIONS THAT MEET OR EXCEEDS TTHE
 REQUIRED WIND DESIGN CRITERIA. PLEASE PROVIDE
 ENGINEERING FOR ROOF TOP UNITS PER 2010 FBC-B 1609.8
 ROOF TOP STRUCTURES & EQUIPMENT.
  
 6) 2ND REQUEST, ADDING THE GENERAL NOTE # 13 TO THE
 COVER SHEET DOES NOT RELIEVE THE DESIGNER OF RECORD
 FROM REVIEWING THE PRODUCT APPROVALS BEFORE SUBMITTAL
 TO THE BUILDING DEPARTMENT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT
 WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
 7) PLEASE SUBMIT THE FOLLOWING PRODUCT APPROVALS: 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, SWING DOORS, ROLL UP DOORS &
 ROOF HATCH .NOT REVIEWED BY DESIGNER OF RECORD
  
 11-0722.10 ROOF HATCH +/- 70 PSF
 PLEASE REVIEW SHEET A-141, TENANT B-12 THIS ROOF HATCH
 IS IN ROOF ZONE # 2 WITH ASSOCIATED PRESSURES OF -76.5
 IN EXCESS OF THE PRODUCT APPROVAL , TENANTS B13, B14 &
 B15 OK.
  
 NOA 11-1013.05 ALUMINUM SLIDING DOOR- NON-MOTORIZED HIS
 TYPE DOOR NOT SHOWN IN DOOR SCHEDULE PLEASE REMOVE FROM
 PACKAGE.
 (B) WINDOWS NOT REVIEWED BY THE DESIGNER OF RECORD
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, NOT REVIEWED BY DESIGN OF
 RECORD.
 (D) ROOFING PRODUCTS AND ASSEMBLIES NOTE BOTH FOR FULLY
 ADHERRED SYSTEMS AND MECHANICALLY FASTENED SYSTEMS,
 ALSO INCLUDE ROOF TOP INSULATION, & A/C CURBING.
  
 NOA 03-0625 FIRESTONE -EXPIRED, PLEASE REMOVE FROM
 PACKAGE
 NOA 12-0625.02 FIRESTONE NO SUB-SYSTEM IS CIRCLED,
 IDENTIFYING WHICH SYSTEM IS TO BE INSTALLED W/
 ASSOCIATED PRESSURES/ NO ROOFING INSULATION IDENTIFIED
  
 A(3RD) PRODUCT NOA08-0603.19 GAF SINGLE PLY TPO WAS
 SUMITTED NO SUB-SYSTEM INDENTIFIED, NOTE NOA 13-0603.19
 SUBMITTED INSULATION YPE OR SIZE NOT IDENTIFIED.
  
 F) SHUTTERS- NOA 13-0422.14 ALUMINUM /CANVAS AWNINGS +/
 50 PSF.
 3105.4.1
 DESIGN OF THE FRAMING MEMBERS SHALL NOT BE BASED ON
 REMOVAL OR REPOSITIONING OF PARTS, OR THE WHOLE, DURING
 PERIODS OF 75 MPH WIND VELOCITY.
 3105.4.2 DESIGN OF THE STRUCTURAL FRAMING MEMBERS SHALL
 BE BASED ON RATIONAL ANALYSIS, USING THE APPLICABLE
 WIND LOADS OF CHAPTER 16 AS SHOWN BELOW:
  
 3105.4.2.1 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING
 CRITERIA:
 1. MINIMUM WIND SPEED 105 MPH
 2. EXPOSURE CATEGORY B, C OR D AS DEFINED IN CHAPTER
 16.
 3105.4.2.2 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE COVERED STRUCTURE DESIGNED WITH A PERMANENT OR
 NONREMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON THE
 FOLLOWING CRITERIA:
 1. MINIMUM WIND SPEED VELOCITY AS REQUIRED IN CHAPTER
 16 USING FIGURE 1609C.
 2. EXPOSURE B, C OR D AS DEFINED IN CHAPTER 16.
 3105.4.3 THE FABRIC PORTIONS OF AWNINGS FABRIC COVERED
 FRAMES SHALL BE SECURELY LACED, TIED OR OTHERWISE
 FASTENED TO THE FRAME; NO RAFTER OR FRONT BAR WILL BE
 PERMITTED IN POCKETS; AND IN NO CASE SHALL A ROLLING
 CURTAIN BE CAUSED TO OPERATE OVER A CANOPY FRAME.
 3105.4.4 THE HORIZONTAL PROJECTION OF CANTILEVERED
 PORTIONS SHALL NOT BE GREATER THAN TWO TIMES THE
 HEIGHT, EXCEPT WHERE THE BUILDING CONSTRUCTION DOES NOT
 PERMIT A PROPER INSTALLATION; IN WHICH CASE, VARIANCE
 MAY BE PERMITTED BY THE BUILDING OFFICIAL, BASED ON
 SPECIAL DESIGN AND CONSTRUCTION.
  
 (G) PRE-ENGINEERED A/C STANDS IF THEY ARE GOING TO BE
 INSTALLED NO APPROVALS SUBMITTED.
  
 8-9) COMPLIED.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-26 Cont ID  
Sent By jwitmer Date 2013-08-26 Time 12:26 Rev Time 0.00
Received By jwitmer Date 2013-08-25 Time 11:04 Sent To  
Notes
2013-08-25 12:40:11BUILDING PLAN REVIEW
 PERMIT: 13071098
 ADD: 1855 PALM BEACH LAKES BLDG' "B1"SHELL
 CONT: EMJ KERI NEVEL
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUNDAY AUGUST 25/ 2013
 ACTION: DENIED
  
  
 1A) PLEASE UPDATE THE PLANS TO REFLECT THE BUILDING
 ADDRESS FOR SHELL BUILDING B1 TO 1855 PALM BEACH LAKES,
 THE SITE ADDRESS IS THE 1801 PALM BEACH LAKES ADDRESS.
  
 1B) PLEASE PROVIDE A OVER ALL SITE PLAN OF THE PB
 OUTLET MALL PROPERTY AND THE LOCATION OF THIS BUILDING
 COMPLIANCE WITH THE THE 2010 FBC-B TABLE 602 & TABLE
 705.8 CAN NOT BE DETERMINED.
  
 2) APPROVAL STAMPS FROM THE PALM BEACH OUTLET MALLS IS
 REQUIRED BEFORE PERMIT SUBMITTAL, PLEASE OBTAIN THE
 APPROVAL STAMP BEFORE THE NEXT SUBMITTAL PROCESS
 BEGINS.
  
 3) PB OUTLET MALLS: BE AWARE FOR TENANT BUILD OUTS.
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 4) SHEET S.001:
 4A) UNDER THE HEADING OF COMPONENTS AND CLADDING THE
 ROOFING PRESSURE CATEGORIES ARE MISSING THE 10 SQ FT
 COLUMN. THIS IS THE HIGHEST PRESSURES TO BE TAKEN UNDER
 THE COMPONENTS AND CLADDING CHARTS. THE FASTENERS FOR
 ROOFING WE USE THE 10 SQ FT COLUMN SINCE THE FASTENERS
 ARE HOLDING THE WORST CASE SCENERIO.
  
 4B) FOUNDATIONS INDICATES THERE IS A SOILS REPORT THAT
 HAS BEEN COMPLETED, PLEASE SUPPLY REPORT BY ECS DATED
 JUNE 16/ 2012. 2010 FBC-B 1803.2 INVESTIGATION REQUIED.
  
 4C) UNDER THE HEADING TILT-UP CONCRETE WALL PANELS,
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
 110.3.9 OTHER INSPECTION SEERVICES, THIS PROJECT BEING
 TILT WALL WILL QUALIFY FOR A RESIDENT INSPECTOR. SUCH
 INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES WORK IS
 UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE BUILDING.
 SUCH INSPECTORS SHALL BE A REGISTERED ARCHITECT, OR
 ENGINEER, OR A PERSON LICENSED UNDER CHAPTER 468, PART
 XII, FLORIDA STATUTES. SUCH INSPECTORS SHALL SUBMIT
 WEEKLY PROGRESS REPORTS INCLUDING THE DAILY INSPECTIONS
 TO THE BUILDING OFFICIAL, AND INCLUDING A CODE
 COMPLIANCE OPINION OF THE RESIDENT INSPECTOR.
 PLEASE CONTACT KEN CONRAD THE DIRECTOR OF THE RESIDENT
 INSPECTOR PROGRAM FOR REQUIREMENTS FORMS AND ADDITIONAL
 INFORMATION ON THIS PROGRAM AND REQUIREMENTS :
 KEN CONRAD
 TEL: 561-805-6666
 FAX: 561-805-6676
 E-MAIL: KCONRAD @WPB.ORG
  
 5) SHEET S002 RTU HEADING THE NOTE AS FOLLOWS: GC TO
 PROVIDE PRE-ENGINEERED RTU TIE DOWNS OR EQUIVALENT
 ENGINEERED TIE-DOWN SOLUTIONS THAT MEET OR EXCEEDS TTHE
 REQUIRED WIND DESIGN CRITERIA. PLEASE PROVIDE
 ENGINEERING FOR ROOF TOP UNITS PER 2010 FBC-B 1609.8
 ROOF TOP STRUCTURES & EQUIPMENT.
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) PLEASE SUBMIT THE FOLLOWING PRODUCT APPROVALS: 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, SWING DOORS, ROLL UP DOORS &
 ROOF HATCH .
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES NOTE BOTH FOR FULLY
 ADHERRED SYSTEMS AND MECHANICALLY FASTENED SYSTEMS,
 ALSO INCLUDE ROOF TOP INSULATION, & A/C CURBING.
 (G) PRE-ENGINEERED A/C STANDS IF THEY ARE GOING TO BE
 INSTALLED
  
 8) SHEET A401 WALL DETAIL A1 PROVIDES A ONE HOUR FIRE
 RATED WALL DETAIL BUT THE PLANS DOES NOT PROVIDE A FIRE
 1 HOUR FIRE RATED ASSEMLBY AT THE WALL TO ROOF
 CONNECTION.2010 FBC-B 714.1 FIRE-RESISTANT JOINT
 SYSTEM. 714.2 INSTALATION, & 714.3 FIRE TEST CRITERIA.
  
 9) PLEASE PROVIDE HOW THIS BUILDING IS GOING TO MEET
 THE 2010 FL ENERGY CODE CODE REQUIREMENTS FOR SHELL
 BUILDINGS UNDER 502.1.1.1.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-12-05 Cont ID  
Sent By skennedy Date 2013-12-05 Time 10:52 Rev Time 0.00
Received By skennedy Date 2013-12-05 Time 10:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-09-17 Cont ID  
Sent By dharvey Date 2013-09-17 Time 12:35 Rev Time 0.00
Received By dharvey Date 2013-09-17 Time 10:19 Sent To  
Notes
2013-09-17 10:19:4913071098
 1855 PALM BEACH LAKES BLVD. #B01
 OUT PARCELS B12, B13,B14,B15,B16.
  
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING
 ARE SIX OR LESS AND GROUPED IN ONE LOCATION. CLARIFY
 THE ELECTRICAL RISER PLAN TO SHOW ALL METERS,
 GROUNDING, MAIN DISCONNECTS AND PANEL BOARDS FOR THE
 WHOLE BUILDING LOCATED IN ONE LOCATION.
 NEC 230.2, 230.71, 230.72
  
 SHEET E002 NOTE 17 REFERS TO A 1000 AMPERE MAIN
 DISCONNECT WHICH WOULD REQUIRE GFP PROTECTION. NEC
 230.95
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 PROVIDE A DESIGNATED CLEAR WORKING SPACE AROUND THE
 ELECTRICAL SERVICE EQUIPMENT AND PANEL BOARDS. NEC
 215.5, 110.26
  
 NOTE:
 SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE,
 DATA, FIRE ALARM, SITE LIGHTING, INTERIOR BUILD OUT AND
 SECURITY.
  
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2013-09-18 Cont ID  
Sent By shill Date 2013-09-18 Time 11:15 Rev Time 0.00
Received By shill Date 2013-09-18 Time 11:15 Sent To  
Notes
2013-09-18 11:16:53PER MANNY GONZALEZ EMAIL, ENGINEERING STOP CAN BE
 CLOSED WITH "N" - IT'S ON-SITE AND PRIVATE PARKING AND
 UTILITIES.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-12-06 Cont ID  
Sent By scaldero Date 2013-12-06 Time 15:02 Rev Time 0.00
Received By scaldero Date 2013-12-06 Time 15:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-08-24 Cont ID  
Sent By wjolin Date 2013-08-24 Time 11:44 Rev Time 0.00
Received By wjolin Date 2013-08-24 Time 10:58 Sent To  
Notes
2013-08-24 11:44:221801 PALM BEACH LAKES BOULEVARD - BULK MERCHANDISING
 RETAIL
 PERMIT #13071098
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS IS INDICATED AS 1801 PALM BEACH LAKES
 BOULEVARD; HOWEVER, THIS BUILDING ADDRESS ALREADY
 EXISTS ON THIS SITE FOR THE OUTLET MALL (BUILDING J1).
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION WORK
 SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH
 AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. PER FBC SECTION 907.1.1 CONSTRUCTION
 DOCUMENTS - "CONSTRUCTION DOCUMENTS FOR FIRE ALARM
 SYSTEMS SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE, THE FLORIDA FIRE PREVENTION CODE, AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL." FOR ISSUANCE OF A
 GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE
 FLORIDA BUILDING CODE REQUIRES SEALED FIRE PROTECTION
 CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF
 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
  
 NOTE: THE MAIN ENTRY IS PERMITTED TO BE EQUIPPED WITH A
 KEYED LOCK WITH LOCK/UNLOCK INDICATOR WINDOW AND
 SIGNAGE STATING THE DOOR IS TO REMAIN UNLOCKED DURING
 BUSINESS HOURS. NO OTHER LOCKING OR LATCHING MECHANISMS
 ARE PERMITTED.THUMB-TURN LOCKS TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2014-06-03 Time 12:12 Sent To  
Notes
2014-06-03 12:13:04STOREFRONT SHOPS TO JW DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-01-15 Cont ID  
Sent By rregueir Date 2014-01-13 Time 09:31 Rev Time 0.00
Received By rregueir Date 2013-12-16 Time 14:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-13 Cont ID  
Sent By skennedy Date 2013-12-13 Time 09:45 Rev Time 0.00
Received By skennedy Date 2013-10-18 Time 10:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-18 Cont ID  
Sent By shill Date 2013-09-18 Time 11:39 Rev Time 0.00
Received By shill Date 2013-07-31 Time 10:55 Sent To  
Notes
2013-09-18 11:40:03SENT EMAIL TO RR AND K CARSILLO
 NEED POLICE REVIEW
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2013-12-04 Cont ID  
Sent By jwitmer Date 2013-12-04 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2013-12-04 Time 08:30 Sent To  
Notes
2013-12-04 08:31:15P. B. CTY IMPACT FEE OFFICE:
 PLANS STAMPED NO FEES DUE
 RE: MU-2013-024552-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-10-29 Cont ID  
Sent By jwitmer Date 2013-10-29 Time 10:53 Rev Time 0.00
Received By jwitmer Date 2013-10-29 Time 10:53 Sent To  
Notes
2013-10-29 10:53:25BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-10-29 Cont ID  
Sent By jwitmer Date 2013-10-29 Time 10:52 Rev Time 0.00
Received By jwitmer Date 2013-10-29 Time 10:52 Sent To  
Notes
2013-10-29 10:52:53BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-09-12 Cont ID  
Sent By rregueir Date 2013-09-12 Time 10:17 Rev Time 0.00
Received By rregueir Date 2013-09-12 Time 10:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-10-30 Cont ID  
Sent By lwagner Date 2013-10-30 Time 13:23 Rev Time 0.00
Received By lwagner Date 2013-10-30 Time 10:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-08-30 Cont ID  
Sent By lwagner Date 2013-08-30 Time 09:22 Rev Time 0.00
Received By lwagner Date 2013-08-29 Time 15:34 Sent To  
Notes
2013-08-30 09:22:04FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 SHEETS P101 & P102: THE HORIZONTAL STORM LINES
 IN-GROUND APPEAR TO BE UNDERSIZED PER TABLE 1106.3 @ 5"
 RAINFALL. IF USING 1/4" OR 1/2" PER FOOT SLOPE, PLEASE
 INDICATE THIS ON THE PLAN FOR EACH STORM DRAIN.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop POLICE POLICE
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2013-10-22 Time   Rev Time 0.00
Received By   Date 2013-10-22 Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-01-23 Cont ID  
Sent By rregueir Date 2014-01-23 Time 16:00 Rev Time 0.00
Received By rregueir Date 2014-01-23 Time 16:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2014-01-13 Cont ID  
Sent By eschneid Date 2014-01-13 Time 11:42 Rev Time 0.50
Received By eschneid Date 2014-01-13 Time 11:42 Sent To  
Notes
2014-01-13 11:47:59AWNINGS, BICYCLE RACKS, BENCHES AND PARKING LOT
 STRIPING REQUIRE SEPARATE PERMITS. THE BICYCLE RACKS
 AND THE PARKING SHALL PASS FINAL INSPECTION PRIOR TO
 THE FINAL BUILDING INSPECTION FOR THIS BUILDING.
  
2013-12-18 10:58:3212/18/13

Review Stop Z ZONING
Rev No 2 Status F Date 2013-11-18 Cont ID  
Sent By eschneid Date 2013-11-18 Time 13:55 Rev Time 2.00
Received By eschneid Date 2013-11-18 Time 13:55 Sent To  
Notes
2013-11-18 16:47:15FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) REPEAT COMMENT: SIGHT LINE DRAWINGS TO VERIFY THAT
 THE ROOFTOP MECHANICAL EQUIPMENT IS SCREENED FROM VIEW
 WERE NOT SUBMITTED. THE SIGHT LINE DRAWING FOR BAYS B14
 AND B15 WERE NOT INCLUDED. THEY WERE SUBMITTED WITH THE
 MINOR PD AMENDMENT. SHEET A104.
  
 2) AWNINGS, BICYCLE RACKS AND PARKING LOT STRIPING
 REQUIRE SEPARATE PERMITS. THE BICYCLE RACKS AND THE
 PARKING SHALL PASS FINAL INSPECTION PRIOR TO THE FINAL
 BUILDING INSPECTION FOR THIS BUILDING.
  
 3) THE CITY'S CRIME PREVENTION OFFICER SHALL APPROVE
 THE BENCH STYLE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
  
2013-10-30 15:09:1410/29/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-09-13 Cont ID  
Sent By eschnide Date 2013-09-05 Time 15:23 Rev Time 0.00
Received By eschneid Date 2013-09-05 Time 15:23 Sent To  
Notes
2013-09-13 15:55:489/13/13 - FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) THE MINOR PD AMENDMENT FOR THIS BUILDING HAS NOT
 BEEN APPROVED BY ZONING. THERE WERE OUTSTANDING
 COMMENTS BASED ON BUILDING B1 THAT NEED TO BE ADDRESSED
 PRIOR TO THIS PERMIT BEING PASSED BY ZONING.
  
 2) THE RAMPS ON THE EAST SIDE OF THE BUILDING AT
 TENANTS B13 AND B14 ON SHEETS A100 AND A101 DO NOT
 MATCH THE RAMP SIZE OR LOCATION ON THE MINOR AMENDMENT
 PLANS.
  
 3) THE AREA ON THE WEST SIDE OF THE BUILDING AT TENANTS
 B12, B13 AND B14 ON SHEETS A100 AND A101 DOES NOT MATCH
 THE MINOR AMENDMENT PLANS WHERE IT IS SHOWN AS
 LANDSCAPE, NOT HARDSCAPE.
  
 4) THERE ARE ADDITIONAL BICYCLE RACKS SHOWN ON THE
 ARCHITECTURAL SITE AND SIDEWALK PLAN AS OPPOSED TO THE
 APPROVED SITE PLAN.
  
 5) SIGHT LINE DRAWINGS TO VERIFY THAT THE ROOFTOP
 MECHANICAL EQUIPMENT IS SCREENED FROM VIEW WERE NOT
 SUBMITTED.
  
 6) THE INSTALLATION OF PARKING SPACES TO THE WEST OF
 THE PBA 1 BUILDING DRAWS MORE THAN JUST THE SERVICE
 VEHICLES BEHIND THE BUILDING AND REQUIRES THAT THE
 COMPACTOR ENCLOSURE OPENINGS BE SCREENED WITH A GATE.
  
 7) ALL PARAPET CORNICE ELEMENTS NEED TO WRAP AROUND THE
 EDGE OF EXPOSED PARAPET ENDS. STAFF NOTICED THIS ON THE
 B1 ELEVATION SHEETS. SOME OF THE PARAPET ENDS DO MEET
 THIS STANDARD.
  
 8) WHAT OCCURS IN THE TENANT B16 SPACE?
  
 9) SIGNAGE, AWNINGS, LANDSCAPE AND PARKING LOT STRIPING
 REQUIRE SEPARATE PERMITS. THE LANDSCAPE AND THE PARKING
 SHALL PASS FINAL INSPECTION PRIOR TO THE FINAL BUILDING
 INSPECTION FOR THIS BUILDING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
2013-09-05 15:24:38ZONING REVIEW ON HOLD PENDING THE REVIEW OF THE MINOR
 PD AMENDMENT SUBMITTED ON 8/21/13 TO REVISE THE
 BUILDING FOOTPRINT FOR PBA 1.
2013-08-28 14:32:048/28/13


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved