| 2013-07-31 06:36:26 | BUILDING PLAN REVIEW |
| | REVISION: 13071064 |
| | PERMIT: 13070469 |
| | ADD: 500 N CONGRESS # 217 |
| | CONT: FINE LINE CONSTRUCTION |
| | TEL: (954)214-8104 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | |
| | 1ST REVIEW |
| | DATE:JULY 31/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2) THE REVISION INDICATES THE 2 HR RATED OCCUPANCY |
| | SEPERATION WALL ONLY GOING TO THE CEILING SEE DETAIL |
| | U498 AS WELL AS FLOOR PLAN. 2010 FBC-B 439.2 SEPARATION |
| | WALLS. WALLS SEPARATING DWELLING UNITS IN THE SAME |
| | BUILDING, WALLS SEPARATING SLEEPING UNITS IN THE SAME |
| | BUILDING AND WALLS SEPARATING DWELLING OR SLEEPING |
| | UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE |
| | SAME BUILDING SHALL BE CONSTRUCTED AS FIRE PARTITIONS |
| | IN ACCORDANCE WITH SECTION 709. |
| | |
| | 2010 FBC-B 709.4 CONTINUITY. FIRE PARTITIONS SHALL |
| | EXTEND FROM THE TOP OF THE FOUNDATION OR FLOOR/CEILING |
| | ASSEMBLY BELOW TO THE UNDERSIDE OF THE FLOOR OR ROOF |
| | SHEATHING, SLAB OR DECK ABOVE OR TO THE |
| | FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING |
| | ASSEMBLY ABOVE, AND SHALL BE SECURELY ATTACHED THERETO. |
| | IF THE PARTITIONS ARE NOT CONTINUOUS TO THE SHEATHING, |
| | DECK OR SLAB, AND WHERE CONSTRUCTED OF COMBUSTIBLE |
| | CONSTRUCTION, THE SPACE BETWEEN THE CEILING AND THE |
| | SHEATHING, DECK OR SLAB ABOVE SHALL BE FIREBLOCKED OR |
| | DRAFTSTOPPED IN ACCORDANCE WITH SECTIONS 717.2 AND |
| | 717.3 AT THE PARTITION LINE. THE SUPPORTING |
| | CONSTRUCTION SHALL BE PROTECTED TO AFFORD THE REQUIRED |
| | FIRE-RESISTANCE RATING OF THE WALL SUPPORTED, EXCEPT |
| | FOR WALLS SEPARATING TENANT SPACES IN COVERED MALL |
| | BUILDINGS, WALLS SEPARATING DWELLING UNITS, WALLS |
| | SEPARATING SLEEPING UNITS AND CORRIDOR WALLS, IN |
| | BUILDINGS OF TYPE IIB, IIIB AND VB CONSTRUCTION. ALSO |
| | SEE EXCEPTION # 5. |
| | |
| | 3A) THE OTHER ISSUE IS THE LAUNDRY FIRE BARRIER 2010 |
| | FBC-B TABLE 508.2.5 REQUIRES ONLY A ONE HOUR FIRE |
| | RATING BETWEEN AN INCIDENTIAL ACCESSORY OCCUPANCY IT IS |
| | ODD THAT A BUSINESS OCCUPANCY REQUIRES A 2 HR OCCUPANCY |
| | SEPERATION WHERE AS THE LAUNDRY ROOM ONLY REQUIRES ONE, |
| | IT APPEARS A GREATER FIRE RISK IS IN THEBUSINESS |
| | OCCUPANCY THAN THE LAUNDRY WHERE THERE IS A GREATER |
| | RISK OF FIRE WITH THE LENT AND ASSOCIATED ELECTRIC, |
| | |
| | 3B) SINCE THE ONE HOUR FIRE BARRIER IS TO EXTEND TO THE |
| | ROOF DECK ABOVE (2010 FBC-B 707.5) PLEASE PROVIDE HOW |
| | THE RIDGE VENTING FOR BOTH THE LAUNDRY AND THE R-2 |
| | RESIDENCY WILL BE INSTALLED AND ACHIEVE CODE |
| | COMPLIANCE? |
| | |
| | 3C) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 707.8 |
| | JOINTS. JOINTS MADE IN OR BETWEEN FIRE BARRIERS, AND |
| | JOINTS MADE AT THE INTERSECTION OF FIRE BARRIERS WITH |
| | UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR DECK |
| | ABOVE, SHALL COMPLY WITH SECTION 714. |
| | |
| | 3D) PLEASE PROVIDE ADDITIONAL INFORMATION, WITH THE |
| | LAUNDRY AREA AND R2 LIVING ROOM IT IS ASSUMED THIS IS A |
| | ONE STORY PORTION OF THE BUILDING, PLEASE PROVIDE WHAT |
| | IS ABOVE THE R2 BEDROOM 102 AND SHOW COMPLIANCE WITH |
| | 2010 FBC-B 707.3.9. FIRE AREAS- HORIZONTAL ASSEMBLIES. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |