Plan Review Details - Permit 13071054
Plan Review Stops For Permit 13071054
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-12-26 Cont ID  
Sent By jwitmer Date 2013-12-26 Time 14:09 Rev Time 0.00
Received By jwitmer Date 2013-12-26 Time 14:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-25 Cont ID  
Sent By jwitmer Date 2013-08-19 Time 08:07 Rev Time 0.00
Received By jwitmer Date 2013-08-19 Time 16:06 Sent To  
Notes
2013-08-19 16:50:54BUILDING PLAN REVIEW
 REVISION: 13071054
 PERMIT: 133020651
 ADD: 400 CLEMATIS ST # 103
 CONT: ADVANCED AIR & PLUMBING
 TEL: (561)662-8144
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 08/19/2013
 ACTION: DENIED
  
 1) THE DEAD END CORRIDOR IN FRONT OF RESTROOM # 2
 EXCEEDS 20'-0", 2010 FBC-B 1018.4.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-09-04 Cont ID  
Sent By dharvey Date 2013-09-04 Time 15:19 Rev Time 0.00
Received By dharvey Date 2013-09-04 Time 15:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-12-14 Cont ID  
Sent By wjolin Date 2013-12-14 Time 12:06 Rev Time 0.00
Received By wjolin Date 2013-12-14 Time 11:51 Sent To B
Notes
2013-12-14 12:06:56400 CLEMATIS STREET - SUITE #103
 TRACKING #13071054
 PERMIT # 13020651
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 VENTLESS HOOD FILTERS:
 BAFFLE FILTER CLEAN DAILY
 PRE-FILTER REPLACE WEEKLY
 EAC FILTER CLEAN DAILY
 CHARCOAL FILTER REPLACE EVERY 30 DAYS
 UV LAMP CLEAN EVERY 30 DAYS/REPLACE ANNUALLY
  
 HOOD:
 PERFORM MONTHLY INTERLOCK CHECK
 CLEAN EVERY 3 MONTHS
  
 SUPPRESSION SYSTEM:
 SERVICE SYSTEM EVERY 6-MONTHS
 REPLACE FUSIBLE LINKS ANNUALLY
  
 **FAILURE TO STRICTLY ADHERE TO THIS CLEANING,
 MAINTENANCE, AND SERVICE SCHEDULE WILL RESULT IN A
 CEASE & DESIST FOR ALL COOKING OPERATIONS.**
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-08-09 Cont ID  
Sent By wjolin Date 2013-08-09 Time 11:25 Rev Time 0.00
Received By wjolin Date 2013-08-09 Time 10:50 Sent To  
Notes
2013-08-09 11:25:41400 CLEMATIS STREET - SUITE #103
 TRACKING #13071054
 PERMIT # 13020651
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A1.O: THE REAR SERVICE CORRIDOR INDICATED AS
 "PRIVATE USE ONLY" SHALL ONLY FUNCTION AS A DELIVERY
 CORRIDOR. WALLS AND PENETRATIONS SHALL BE REPAIRED.
 PERMANENT SIGNAGE SHALL BE POSTED INDICATING "NO
 STORAGE PERMITTED." ADDITIONALLY, THE ILLUMINATED EXIT
 SIGNS, DAYTIME LIGHTING AND EMERGENCY IN THIS CORRIDOR
 NEEDS TO BE FIXED AS IT WAS VERY DARK DURING
 INSPECTION.
  
 SHEET M1.01: PLANS INDICATE A NEW VENTLESS KITCHEN
 HOOD. SUBMIT CUT SHEET INFORMATION FOR NEW HOOD. PLANS
 SHALL INDICATE THE CLEANING AND MAINTENACE SCHEDULE
 ASSOCIATED WITH THE VENTLESS HOOD SO THE TENANT IS
 AWARE THIS SCHEDULE NEEDS TO BE FOLLOWED STRICLTY
 OTHERWISE THE TENANT WILL NOT BE PERMITTED TO RESUME
 COOKING OPERATIONS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By skennedy Date 2013-12-09 Time 17:21 Sent To  
Notes
2013-12-22 12:34:3712/22 TO JW DESK
  
2013-12-09 17:21:52SENT TO HMOSER DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-04 Cont ID  
Sent By shill Date 2013-09-04 Time 16:25 Rev Time 0.00
Received By shill Date 2013-07-29 Time 10:28 Sent To  
Notes
2013-07-31 10:32:44B18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-12-10 Cont ID  
Sent By hmoser Date 2013-12-10 Time 08:52 Rev Time 0.00
Received By hmoser Date 2013-12-10 Time 06:37 Sent To FIRE
Notes
2013-12-10 08:52:25AIR CONDITIONING REVISION OK. HOOD REVISION FAIL MUST
 BE SUBMITTED
 UNDER HOOD PERMIT NUMBER . CAN NOT FIND A LISTING ON
 THE HOOD
 SUBMITTAL YOU SENT US . YOU ALSO NEED TWO COPIES.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-08-30 Cont ID  
Sent By hmoser Date 2013-08-30 Time 14:15 Rev Time 0.00
Received By hmoser Date 2013-08-30 Time 14:15 Sent To  
Notes
2013-08-30 15:01:52PLANS DENIED
 REFER TO SECTION 507.2 WHERE REQUIRED ( HOODS )
 AND 501.2 EXHAUST DISCHARGE 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-08-07 Cont ID  
Sent By lwagner Date 2013-08-07 Time 15:38 Rev Time 0.00
Received By lwagner Date 2013-08-07 Time 14:49 Sent To  
Notes
***NONE***