| Plan Review Stops For Permit 13071028 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2013-08-31 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-08-31 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-08-31 |
Time |
14:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-08-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-08-09 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-08-09 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2013-08-09 17:49:43 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE ROOM/USE DESIGNATIONS FOR THE AREAS EAST OF | | | THE GUESTROOM CORRIDOR FBC 107. | | | | | | 2. THE FOLLOWING DOORS LACK MANEUVERING CLEARANCE FBC | | | 2010 ACCESSIBILITY FIGURE 404.2.4.1: | | | | | | NORTH BATHROOM VESTIBULE | | | NORTH ENTRY DOOR (PLAN STATES THAT THE EXISTING FRAMED | | | PARTITION IS TO REMAIN, BUT NOT CLEAR WHY THIS DOOR | | | DOES NOT APPEAR TO COMPLY; IS THERE AN AUTOMATIC DOOR | | | OPENER AT THIS LOCATION?) | | | SOUTH ENTRY DOOR | | | | | | 3. FBC 2010 ACCESSIBILITY FIGURE 404.2.6, SHOW DISTANCE | | | BETWEEN EDGE OF FIRST DOOR AND SECOND DOOR FROM ENTRY | | | TO STORAGE DOOR MARKED D1 (DOORS IN SERIES). | | | | | | 4. SHEET A1.00 SHOWS A MAX TRAVEL DISTANCE OF 86'. | | | PLEASE SHOW DEAD END TRAVEL DISTANCE. IT IS NOTED AS | | | MAX 50', BUT NO DIMENSION SHOWN FOR THE DEAD END, | | | 1018.4 (DOOR D1 TO SW CORNER). | | | | | | 5. PLAN STATES THAT EXISTING USE IS BUSINESS. THE | | | ORIGINAL BUILDING PERMIT WAS FOR RESIDENTIAL ON THE 2ND | | | AND 3RD FLOORS. I WAS UNABLE TO LOCATE A CHANGE OF | | | OCCUPANCY FOR THIS SPACE. I WAS ALSO UNABLE TO LOCATE A | | | BUSINESS TAX RECEIPT FOR A BUSINESS FOR THIS UNIT. | | | | | | 6. PLEASE SEE PLUMBING NOTES REGARDING BATHROOM | | | ACCESSIBILITY. | | | | | | 7. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY MAY BE | | | REQUIRED. 233-5025 FOR MORE INFORMATION. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2013-09-12 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-09-12 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-09-10 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2013-09-10 14:58:24 | 13071028 | | | 477 S ROSEMARY | | | HOTEL ROOM MOCK UP | | | | | | PERMIT MAY BE ISSUED WITH THE FOLLOWING PROVISO: | | | | | | GUEST SUITES REQUIRE A WALL SWITCH-CONTROLLED LIGHTING | | | OUTLET OR RECEPTACLE FOR THE SLEEPING AREA. NEC 210.70 | | | (B) | | | AN ADDITIONAL RECEPTACLE THAT IS READILY ACCESSIBLE IS | | | REQUIRED IN EACH BEDROOM. NEC 210.60 | | | GUEST ROOM RECEPTACLES SHALL BE TAMPER RESISTANT NEC | | | 406.13 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-08-09 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-08-09 |
Time |
07:04 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-08-09 |
Time |
06:34 |
Sent To |
|
|
| Notes |
| 2013-08-09 07:03:38 | ALL OF THE BELOW LISTED ITEMS MAY BE ADDRESSED BY A | | | COVER LETTER, NOTE ON THE PLAN OR CONVERSATION WITH THE | | | REVIEWER AND PROVISOS BEING ADDED. | | | DOUG HARVEY | | | [email protected] | | | 561-805-6740 | | | | | | THANK YOU | | | | | | PLEASE PROVIDE ASSA ABLOY LISTING DATA FOR LOCKSETS IF | | | ELECTRICAL LOCKS WILL BE PUT IN MODEL | | | PROVIDE GFCI FOR DEMOLITION (MAY BE DONE WITH A NOTE) | | | 590.4 | | | PROVIDE LIGHTING FOR DEMOLITION (MAY BE DONE WITH A | | | NOTE) 590.4 | | | LIGHTING AND POWER TO BE ON SEPARATE CIRCUITS 590.4 D | | | TEMPORARY POWER TO COMPLY WITH NEC ARTICLE 590 | | | PLAN E4.0 CALLS FOR CAPPING ELECTRICAL OUTLETS ABOVE | | | CEILING. IF OUTLETS ARE NOT CONNECTED, WHY ARE THEY RUN | | | TO ABOVE THE CEILING? ARE OUTLETS BEING INSTALLED OR | | | REMOVED, OR ARE EXIATING OUTLETS REMAINING FOR FUTURE | | | RECONNECTION? | | | OUTLET HEIGHT IS NOT IN CONFORMANCE WITH FAIR HOUSING | | | GUIDELINES AS GENERALLY USED FOR ACCESSIBLE ROOMS. WILL | | | ADDITIONAL ROOMS IN COMFORMITY BE SPELLED OUT LATER OR | | | WILL THESE GUIDELINES BE CONSIDERED AS NON-APPLICABLE? | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2013-08-03 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2013-08-03 |
Time |
17:31 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2013-08-03 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2013-08-03 17:31:51 | 477 SOUTH ROSEMARY AVENUE - SUITE #214 | | | PERMIT #13071028 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO***** | | | | | | GENERAL: NO SLEEPING IS TO BE PERMITTED. **NOTE: THIS | | | IS A BUSINESS OCCUPANCY USED ONLY FOR | | | SHOWING/DISPLAYING A HOTEL SUITE.** | | | | | | SHEET E4.1: PROVIDE AN ADDITIONAL FIRE ALARM | | | NOTIFICATION APPLIANCE AND EMERGENCY LIGHT FOR REMOTE | | | PORTION OF STORAGE AREA. | | | | | | SHEET E4.1: NO EXISTING FIRE ALARM DEVICES AND ONLY ONE | | | EMERGENCY LIGHT COULD BE FOUND FOR THE KITCHEN AND | | | ENTRANCE AREA. | | | | | | SHEET FP4.0: STORAGE AREAS SHALL BE PROTECTED AS | | | ORDINARY HAZARD. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | (561) 805-6730 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-09-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-09-10 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-08-23 |
Time |
15:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-08-12 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2013-08-12 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2013-07-30 |
Time |
14:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2013-08-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-08-15 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-08-15 |
Time |
12:11 |
Sent To |
|
|
| Notes |
| 2013-08-15 12:11:52 | PER WILLIE SWOPE - NO IMPACT FEES DUE (EXISTING USE | | | CREDIT) | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2013-08-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-08-12 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-08-12 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2013-08-12 11:56:21 | IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY MAY BE | | | REQUIRED. | | | 233-5025 - A MESSAGE HAS BEEN LEFT FOR PB COUNTY IMPACT | | | FEES TO ADVISE AS TO WHETHER OR NOT THIS IS REQUIRED | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2013-07-30 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2013-07-30 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2013-07-30 |
Time |
14:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2013-09-10 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2013-09-10 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-09-10 |
Time |
09:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2013-08-09 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2013-08-09 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-08-09 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2013-08-09 08:37:49 | FBC 2010 EXISTING BUILDING CODE | | | FBC 2010 ACCESSIBILITY CODE | | | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1. SHEET A1.01 SHOWS WHAT APPEARS TO BE AN OFFICE AREA | | | WITH 2 ACCESSABLE RESTROOMS. THE RESTROOMS WOULD NOT | | | MEET THE REQUIREMENTS OF THE FBC ACCESSIBILITY CODE | | | 604.3.1 SIZE. | | | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES | | | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE | | | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED | | | PERPENDICULAR FROM THE REAR WALL. | | | 604.8.1.6 LAVATORY. | | | IN NEW CONSTRUCTION, THE WHEELCHAIR ACCESSIBLE TOILET | | | COMPARTMENT SHALL CONTAIN AN ACCESSIBLE LAVATORY WITHIN | | | IT, WHICH MUST BE AT LEAST 19 INCHES WIDE BY 17 INCHES | | | DEEP, NOMINAL SIZE, AND WALL-MOUNTED. THE LAVATORY | | | SHALL BE MOUNTED SO AS NOT TO OVERLAP THE CLEAR FLOOR | | | SPACE AREAS REQUIRED BY SECTION 604 FOR THE WHEELCHAIR | | | ACCESSIBLE TOILET COMPARTMENT AND SHALL COMPLY WITH | | | SECTION 606. SUCH LAVATORIES SHALL BE COUNTED AS PART | | | OF THE REQUIRED FIXTURE COUNT FOR THE BUILDING. SEE | | | ALSO SECTION 213.3.4. | | | | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2013-09-16 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2013-09-16 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2013-09-16 |
Time |
09:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2013-08-12 |
|
|
Cont ID |
|
| Sent By |
eschnid |
Date |
2013-08-12 |
Time |
16:17 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2013-08-12 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2013-08-12 16:20:41 | THE CITYPLACE LOFTS 2ND FLOOR ONLY PERMIT OFFICE AND | | | RESIDENTIAL USE. IN ORDER FOR THIS TO CLASSIFY AS AN | | | OFFICE USE FOR ZONING PURPOSES, AT LEAST ONE EXISTING | | | BATHROOM SHALL REMAIN FUNCTIONING. | | 2013-08-01 16:29:55 | 8/1/13 |
|
|