Plan Review Details - Permit 13070893
Plan Review Stops For Permit 13070893
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-09-25 Cont ID  
Sent By jwitmer Date 2013-09-25 Time 17:55 Rev Time 0.00
Received By jwitmer Date 2013-09-25 Time 17:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-06 Cont ID  
Sent By jwitmer Date 2013-08-06 Time 09:39 Rev Time 0.00
Received By jwitmer Date 2013-08-06 Time 07:40 Sent To  
Notes
2013-08-06 08:01:06BUILDING PLAN REVIEW
 PERMIT: 13070893
 ADD: 511 S OLIVE AVE
 CONT: M.V.P. CONSTRUCTION, INC
 TEL: (954)214-0226
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: AUGUST 06/2013
 ACTION: DENIED
  
 1) PLEASE CLARIFY WHERE THE WORK IS GOING TO BE
 COMPLETED UNDER THIS PERMIT. THE SITE ADDRESS IS 509 S
 OLIVE, IF WORK IS GOING TO BE COMPLETED ON THE ROOF OR
 OUTSIDE OF THE BUILDING, PLEASE PROVIDE THE TENANT
 ADDRESSES TO WHERE WORK IS GOING TO BE COMPLETED AND
 MAKE CORRECTIONS TO THE PERMIT APPLICATION AS WELL AS
 PLANS. 107.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE
 PROJECT.
  
 2) CLARIFICATION, SHEET # 1 INDICATES LEVEL OF
 ALTERATION: TYPE III- UNPROTECTED. IT APPEARS TO
 HEADINGS WERE COMBINED:
 2A) BUILDING TYPE OF CONSTRUCTION FROM 2010 FBC-B TABLE
 503
  
 2B) 2010 EXISTING BUILDING CODE, LEVEL OF ALTERATION?
 PLEASE REVIEW 2010 FL EXISTING BUILDING CODE CHAPTER 4
 CLASSIFICATION OF WORK, IT DOES NOT APPEAR THIS PROJECT
 IS A LEVEL 3 ALTERATION. LEVEL 3 ALTERATIONS APPLY
 WHERE THE WORK AREA EXCEEDS 50 PERCENT OF THE AGGREGATE
 AREA OF THE BUILDING AND MADE WITHIN ANY 12-MONTH
 PERIOD.
 807.4.2 SUBSTANTIAL STRUCTURAL ALTERATION.
 WHERE MORE THAN 30 PERCENT OF THE TOTAL FLOOR AND ROOF
 AREAS OF THE BUILDING OR STRUCTURE HAVE BEEN OR ARE
 PROPOSED TO BE INVOLVED IN STRUCTURAL ALTERATION WITHIN
 A 12-MONTH PERIOD, THE EVALUATION AND ANALYSIS SHALL
 DEMONSTRATE THAT THE ALTERED BUILDING OR STRUCTURE
 COMPLIES WITH THE FLORIDA BUILDING CODE, BUILDING FOR
 WIND LOADING.
  
 807.4.3 LIMITED STRUCTURAL ALTERATION.
 WHERE NOT MORE THAN 30 PERCENT OF THE TOTAL FLOOR AND
 ROOF AREAS OF THE BUILDING ARE INVOLVED IN STRUCTURAL
 ALTERATION WITHIN A 12-MONTH PERIOD, THE EVALUATION AND
 ANALYSIS SHALL DEMONSTRATE THAT THE ALTERED BUILDING OR
 STRUCTURE COMPLIES WITH THE LOADS APPLICABLE AT THE
 TIME OF THE ORIGINAL CONSTRUCTION OR OF THE MOST RECENT
 SUBSTANTIAL STRUCTURAL ALTERATION AS DEFINED BY SECTION
 807.4.2.
  
 3) SHEET # 2:
  
 3A) TENANT SEPERATION WALLS ARE INDICATED AS 2 HR CBS
 WALLS, PLEASE PROVIDE A UL OR GYPSUM ASSOCIATION
 LISTING FOR THE TYPE OF INFILL WILL BE USED IN THESE
 WALLS. 2010 FBC-B 709.1.6 .
  
 3B) THE WIND DESIGN CRITERIA IS NOT A COMPLETE: 2010
 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6
 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 3B)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3B)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE
 7-10.
  
 3B)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3B)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3B)(5) COMPONENTS & CLADDING PRESSURES POSITVE &
 NEGATIVE TABLE 1609.2(2) .
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 6) PLEASE PROVIDE WHAT THE DISTANCE IS FROM THE NORTH
 SIDE OF THE BUILDING TO THE PROPERTY LINE. PLEASE
 REVIEW 2010 FBC-B TABLE 705.8 AS TO ALLOWABLE OPENING
 AREA IN RELATION TO THE PROPERTY LINE. PLANS DO
 INDICATE GLASS BLOCK, PLEASE PROVIDE THE FIRE RATING OF
 THE GLASS BLOCK, TO SEE IF IT MEETS THE REQUIREMENT NOT
 FOR A OPENING BUT AS A WALL. THE RESPONCE TO COMMENT
 (2A) WILL AFFECT THIS COMMENT, 2010 FBC-TABLE 602 FIRE
 RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED
 ON FIRE SEPERATION DISTANCE.
  
 7) ON THE WEST WALL A GARGE DOOR OPENING IS BEING FILED
 IN AND A NEW DOOR AND WINDOW ARE BEING CREATED, THERE
 IS NO STRUCTURAL INFORMATION ON THE INFILL STRUCTURAL
 COMPONENTS, THEY ARE PART OF THE MWFRS (MAIN WIND FORCE
 RESISTING SYSTEM) 2010 FBC-B 1609.6.4.
  
 8) SHEET A2 THE FRONT LEFT OFFICE SHOWS A NEW DOUBLE
 DOORWAY IN THE BEARING WALL, THERE IS NO FRAMING DETAIL
 FOR THIS BEARING PARTITION.
 MWFRS FBC-B 1609.6.4.
  
 9) THE LIFE SAFETY SHEET 6 OF 7 INDICATES 30 SQ FT /
 OCCUPANT, PLEASE UPDATE TO 2010 FBC-B 1004.1.1.
  
 10) THE LIFE SAFETY SHET 6 OF 7 ALSO INDICATES THE
 REMOVAL OF A BEARING WALL WITH EXISTING STEEL AND WOOD
 POST OR COLUMNS AND WOOD BEAM ABOVE. THIS WAS AN
 EXISTING CONDITION?
  
 11A) WITH THE COMBINING OF THE TWO SUITES INTO ONE
 SUITE THE OCCUPANT LOAD IS NOW 61 WHICH REQUIRES THE
 EGRESS DOORS TO SWING OUT PER
 2010 FBC-B 1008.1.2.9.
  
 11B) WITH THE NEW SUITES AND THE REQUIRED DOOR SWING TO
 THE EXTERIOR, PLEASE PROVIDE WHERE THE PROPERTY LINE IS
 LOCATED. 2010 FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE
 AND BELOW 8 FEET IN HEIGHT.
 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE
 AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE
 PROHIBITED, DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT
 INTO THE PUBLIC RIGHT-OF-WAY.
  
 12) SHEET 5 OF 7 INDICATES A DROPPED CEILING AND SOFFIT
 SYSTEM, NO INFORMATTION AS TO MATERIALS OR SYSTEMS ARE
 PROVIDED, NOR ANCHORING TO WHAT TYPE OF FRAMING ABOVE?
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS 107.3.5.1.1(8) STRUCTURAL ELEMENTS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-10-18 Cont ID  
Sent By dharvey Date 2013-10-18 Time 09:07 Rev Time 0.00
Received By dharvey Date 2013-10-18 Time 09:06 Sent To  
Notes
2013-10-18 09:12:00I MET WITH THE ARCHITECT THIS MORNING TO DISCUSS THE
 ITEMS NEEDED FOR COMPLIANCE. ALL ITEMS WERE CORRECTED
 AS FOLLOWS:
 1. IN LIEU OF A SITE PLAN, A NOTE AS TO THE BLDG. AREA
 AND THE WORK AREA HAD BEEN PREVIOUSLY ENTERED IN THE
 PLANS. I HIGHLIGHTED THE NOTE. A SITE PLAN WAS ALSO
 SUBMITTED FOR ADDITIONAL CLARIFICATION.
 2. THE WIRING QUESTIONS WERE ADDRESSED AND HE ENTERED
 THEM MANUALLY ON BOTH SETS.
 3. THE SHOW WINDOW OUTLET WAS ADDED AS WELL, WITH IT'S
 CORRESPONDING CIRCUIT DESIGNATION.
  
 ALL ENTRIES WERE MADE BY HAND IN MY PRESENCE AND SIGNED
 BY HIM.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-10-16 Cont ID  
Sent By dharvey Date 2013-10-16 Time 16:56 Rev Time 0.00
Received By dharvey Date 2013-10-16 Time 15:40 Sent To  
Notes
2013-10-16 16:54:05THE FOLLOWING SHALL BE ADDRESSED FOR A SUCCESSFUL
 ELECTRICAL PLAN REVIEW:
 1. MUST SUBMIT A SITE PLAN INDICATING THE AREA TO BE
 WORKED IN. THIS SITE PLAN SHALL INCLUDE THE TOTAL AREA
 OF THE BLDG. TO ASCERTAIN APPLICABLE FBCE REQUIREMENTS.
 APPLICABLE REQUIREMENTS OF THE FBCE SHALL BE INCLUDED
 ON THE SUBMITTED PLANS.
 2. EXISTING FLOOR PLAN & DEMO PLAN INDICATE THAT THE
 ELECTRICAL PANEL WITHIN UNIT 513 IS BEING RELOCATED,
 THE NEW LOCATION HAS TO BE SHOWN ON THE PLANS.
 3. AS PER NEC 210.60, THE STORE FRONT/SHOW WINDOW
 OUTLET REQUIREMENTS ARE NOT ADDRESSED ON THE PLANS.
 4. ELECTRICAL RISER DIAGRAM SHALL INCLUDE PROPER WIRE
 SIZING AND GROUNDING DETAILS.
  
 THIS FILE WAS RETURNED TO THE BIN, PENDING SUBMITTAL OF
 REQUIRED CORRECTIONS BY: MA
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-09-04 Cont ID  
Sent By dharvey Date 2013-09-04 Time 13:55 Rev Time 0.00
Received By dharvey Date 2013-09-04 Time 13:55 Sent To  
Notes
2013-09-04 13:57:10FIRST REVIEW - 9-4-13
  
 1. IF TENANT SPACE IS LOCATED IN A LARGER BUILDING
 GREATER THAN 5000 SQ FT, LIGHTING CONTROLS MUST BE
 PROVIDED PER RESIDENTIAL CODE 314
  
 2. PROVIDE A ONE LINE FEEDER RISER DIAGRAM PER NEC 220
  
 END OF REVIEW - VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-09-19 Cont ID  
Sent By wjolin Date 2013-09-19 Time 14:52 Rev Time 0.00
Received By wjolin Date 2013-09-19 Time 14:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-07-30 Cont ID  
Sent By wjolin Date 2013-07-30 Time 16:12 Rev Time 0.00
Received By wjolin Date 2013-07-30 Time 15:55 Sent To  
Notes
2013-07-30 16:12:37511 SOUTH OLIVE AVENUE
 PERMIT #13070893
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS PROVIDED ON THE PLANS (509 S OLIVE AVE)
 DOES NOT MATCH THE ADDRESS (511 S OLIVE AVE) PROVIDED
 ON THE PERMIT APPLICATION.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE FIRE EXTINGUISHERS, ILLUMINATION AND
 ILLUMINATED EXIT SIGNS FOR ADJACENT SHELL SPACES.
  
 SHEET 5: IT IS UNCLEAR FROM THE PLAN TO DETERMINE IF
 THE EXISTING DUCT WORK PENETRATES INTO THE ADJACENT
 SHELL SPACE WHEREBY A FIRE DAMPER MAY BE NEEDED.
  
 SHEET 4 & 7: THE EXIT SIGNS AND EMERGENCY LIGHTING WALL
 PACKS SHOWN ON THE LIFE SAFETY PLAN ARE NOT SHOWN ON
 THE ELECTRICAL DRAWING.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-18 Cont ID  
Sent By dharvey Date 2013-10-18 Time 09:14 Rev Time 0.00
Received By dharvey Date 2013-09-12 Time 12:20 Sent To  
Notes
2013-10-18 09:15:11SENT TO SH BY: MA
2013-09-13 12:30:53B29
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-04 Cont ID  
Sent By dharvey Date 2013-09-04 Time 13:57 Rev Time 0.00
Received By dharvey Date 2013-09-04 Time 13:57 Sent To  
Notes
2013-07-24 18:55:49B29

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-10-16 Cont ID  
Sent By hmoser Date 2013-10-16 Time 10:14 Rev Time 0.00
Received By hmoser Date 2013-10-16 Time 10:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-08-28 Cont ID  
Sent By hmoser Date 2013-08-28 Time 14:20 Rev Time 0.00
Received By hmoser Date 2013-08-28 Time 13:50 Sent To  
Notes
2013-08-28 14:20:28NO PLANS SUBMITTED FOR MECHANICAL.
 HAROLD MOSER
 [email protected].
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-09-19 Cont ID  
Sent By lwagner Date 2013-09-19 Time 13:21 Rev Time 0.00
Received By lwagner Date 2013-09-19 Time 10:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-07-29 Cont ID  
Sent By lwagner Date 2013-07-29 Time 13:34 Rev Time 0.00
Received By lwagner Date 2013-07-29 Time 11:17 Sent To  
Notes
2013-07-29 11:31:53FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1.SHEET 7: BUISNESS OCCUPANCIES WITH OVER 15 OCCUPANTS
 REQUIRE A DRINKING FOUNTAIN. THE ACCESSIBILITY CODE
 REQUIRES THAT IT IS A HI/LOW DRINKING FOUNTAIN.
 FBC PLUMBING 403.1 (D, & E)
 FBC ACCESSIBILITY 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2013-08-15 Cont ID  
Sent By aaponte Date 2013-08-15 Time 14:12 Rev Time 0.00
Received By aaponte Date 2013-08-15 Time 14:11 Sent To  
Notes
2013-08-15 14:13:09INTERIOR MODIFICATIONS ONLY.