Plan Review Details - Permit 13070828
Plan Review Stops For Permit 13070828
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-09-18 Cont ID  
Sent By jwitmer Date 2013-09-18 Time 15:59 Rev Time 0.00
Received By jwitmer Date 2013-09-18 Time 15:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-17 Cont ID  
Sent By jwitmer Date 2013-08-17 Time 14:14 Rev Time 0.00
Received By jwitmer Date 2013-08-17 Time 13:34 Sent To  
Notes
2013-08-17 13:46:00BUILDING PLAN REVIEW
 PERMIT:13070828
 ADD: 1741 PALM BEACH LAKES BLVD SUITE # ???????
 CONT:TO BE DETERMINED
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SATURDAY AUGUST 17/2013
 ACTION: DENIED
  
 1) THE PLANS NOR PERMIT APPLICATION PROVIDE THE SUITE #
 WHERE WORK IS TO BE COMPLETED UNDER THIS PERMIT. 2010
 FBC 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) PB OUTLET MALLS:
 BUILDING PROVISO:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 3) 0013/ SHEET A6.1 DETAIL #9 HIGH LOW DRINKING
 FOUNTAINS, PLEASE BE AWARE THAT THE HIGH SIDE DRINKING
 FOUNTAIN DOES NOT INDICATE THE VERTICAL CLEARANCE
 BENEATH WHERE BASIN PORTION OF THE UNIT, COMMONLY IT
 DOES NOT MEET SECTION 2010 FBC ACCESSIBILITY CODE:
 2010 FL ACCESSIBILITY CODE AT DRINKING FOUNTAIN THE
 UPPER DRINKING FOUNTAIN WILL TO COMPLY WITH
 2010 FL ACCESSIBILITY CODE 307.2 OBJECTS WITH LEADING
 EDGES MORE THAN 27 INCHES (685 MM) AND NOT MORE THAN 80
 INCHES (2030 MM) ABOVE THE FINISH FLOOR OR GROUND SHALL
 PROTRUDE 4 INCHES (100 MM) MAXIMUM HORIZONTALLY INTO
 THE CIRCULATION PATH.
  
 ADVISORY 307.2 PROTRUSION LIMITS.
 WHEN A CANE IS USED AND THE ELEMENT IS IN THE
 DETECTABLE RANGE, IT GIVES A PERSON SUFFICIENT TIME TO
 DETECT THE ELEMENT WITH THE CANE BEFORE THERE IS BODY
 CONTACT. ELEMENTS LOCATED ON CIRCULATION PATHS,
 INCLUDING OPERABLE ELEMENTS, MUST COMPLY WITH
 REQUIREMENTS FOR PROTRUDING OBJECTS.
  
 4) 0015/ SHEET A7.1 THE ACCESSIBLE DRESSING ROOM PLEASE
 REVIEW THE REQUIREMENTS FOR A BACK SUPPORT ON THE
 BENCH.
 2010 FBC- ACCESSIBILITY CODE 903.4 BACK SUPPORT.
 THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE
 AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 INCHES
 (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A POINT 2
 INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE TO A
 POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM)
 MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED
 HORIZONTALLY.
  
  
 ADVISORY 903.4 BACK SUPPORT.
 TO ASSIST IN TRANSFERRING TO THE BENCH, CONSIDER
 PROVIDING GRAB BARS ON A WALL ADJACENT TO THE BENCH,
 BUT NOT ON THE SEAT BACK. IF PROVIDED, GRAB BARS CANNOT
 OBSTRUCT TRANSFER TO THE BENCH.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-09-24 Cont ID  
Sent By dharvey Date 2013-09-24 Time 14:34 Rev Time 0.00
Received By dharvey Date 2013-09-24 Time 13:58 Sent To  
Notes
2013-09-24 14:34:47RL

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-09-07 Cont ID  
Sent By dharvey Date 2013-09-07 Time 14:55 Rev Time 0.00
Received By dharvey Date 2013-09-07 Time 14:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-09-18 Cont ID  
Sent By scaldero Date 2013-09-18 Time 17:03 Rev Time 0.00
Received By scaldero Date 2013-09-18 Time 17:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-07-30 Cont ID  
Sent By scaldero Date 2013-07-30 Time 15:08 Rev Time 0.00
Received By scaldero Date 2013-07-30 Time 15:08 Sent To  
Notes
2013-07-30 15:09:54PERMIT #13070828
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-09-26 Cont ID  
Sent By shill Date 2013-09-24 Time 07:32 Rev Time 0.00
Received By shill Date 2013-09-17 Time 14:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2013-09-09 Time   Rev Time 0.00
Received By rregueir Date 2013-07-29 Time 11:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-09-17 Cont ID  
Sent By rregueir Date 2013-09-17 Time 14:48 Rev Time 0.00
Received By rregueir Date 2013-09-17 Time 14:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-09-09 Cont ID  
Sent By rregueir Date 2013-09-09 Time 13:16 Rev Time 0.00
Received By rregueir Date 2013-09-09 Time 13:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-08-15 Cont ID  
Sent By lwagner Date 2013-08-15 Time 09:42 Rev Time 0.00
Received By lwagner Date 2013-08-15 Time 09:28 Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status P Date 2013-09-16 Cont ID  
Sent By   Date 2013-09-16 Time   Rev Time 0.00
Received By ktucker Date 2013-09-16 Time 13:29 Sent To  
Notes
2013-09-16 13:30:45 
 I SAW NO CAMERA PLAN OR SECURITY FOR THIS STORE OTHER
 THAN THE DOOR MOUNTS.
  
 CRIME PREVENTION THROUGH ENVIRONMENTAL DESIGN
 THE CITY OF WEST PALM BEACH HAS RECOGNIZED THAT
 TRADITIONAL CRIME PREVENTION STRATEGIES ARE NOT ENOUGH
 IN TODAY?S SOCIETY AND A NEW APPROACH IS NEEDED. THE
 NAME OF THIS APPROACH IS CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN (CPTED). CPTED ACKNOWLEDGES THAT
 THE MANNER IN WHICH PHYSICAL SPACE IS DESIGNED OR USED
 HAS A DIRECT BEARING ON CRIME AND SECURITY.
 THE PHYSICAL ENVIRONMENT HAS A DRAMATIC EFFECT ON OUR
 OWN BEHAVIOR AND THE WAY IN WHICH WE VIEW THE BEHAVIOR
 OF OTHERS. CPTED IS A CONCEPT SUPPORTED BY A SERIES OF
 OVERLAPPING PRINCIPLES BASED ON THE RELATIONSHIP OF THE
 BUILT ENVIRONMENT TO THE PRESENCE OR ABSENCE OF
 UNDESIRABLE BEHAVIOR. THE CPTED CONCEPT IS: ?THE PROPER
 DESIGN AND EFFECTIVE USE OF THE BUILT ENVIRONMENT CAN
 LEAD TO A REDUCTION IN THE INCIDENCE AND FEAR OF CRIME
 AND IMPROVEMENT IN THE QUALITY OF LIFE BY INCORPORATING
 ACCESS CONTROL, NATURAL SURVEILLANCE AND TERRITORIAL
 DEFENSIVE TACTICS.?
 CPTED THEORY IS BASED UPON THE CONTENTION THAT
 PLANNERS, DESIGNERS, ARCHITECTS, LANDSCAPERS AND LAW
 ENFORCEMENT CAN COOPERATIVELY CREATE A ?SAFE? CLIMATE
 WITHIN A BUILT ENVIRONMENT ? RIGHT FROM THE BEGINNING.
 SAFETY STRIKES AT THE VERY CORE OF WHAT IS GENERALLY
 REFERRED TO IN A COMMUNITY AS ?QUALITY OF LIFE.? A SAFE
 ENVIRONMENT IS ONE THAT REGULAR USERS PERCEIVE AS SAFE
 AND NON-USERS (CRIMINALS) PERCEIVE AS HIGHLY RISKY TO
 FREQUENT AND IN WHICH TO COMMIT CRIMES.
 THE WEST PALM BEACH POLICE DEPARTMENT HAS OUTLINED
 GUIDELINES WE WOULD LIKE TO SEE FOLLOWED. IN ADDITION
 TO THE GUIDELINES, WE ENCOURAGE YOU TO PLEASE ADOPT
 THESE MINIMUM STANDARDS:
  
 (1) A FULLY FUNCTIONING AND OPERATIONAL CCTV SYSTEM
 CAPABLE OF RECORDING AND RETRIEVING ON SITE, AN
 IDENTIFIABLE IMAGE TO ASSIST IN OFFENDER IDENTIFICATION
 AND APPREHENSION. MONITORS FOR THE SYSTEM SHOULD BE
 PLACED IN A MANAGER?S OFFICE OR BACK ROOM, WITH A
 MONITOR IN PUBLIC VIEW FROM THE SALES FLOOR.
 (2) CAMERA COVERAGE SHOULD BE AT SENSITIVE LOCATIONS:
 (A) DOORS THAT LEADS TO THE BACK OF HOUSE (B) HALLWAYS
 THAT LEAD TO REAR EXITS (C) SALES FLOOR (D) REGISTERS
 (LOW FOR FACIAL RECOGNITION) (E) FRONT ENTRY.
 (3) DOOR THAT LEADS TO THE BACK OF HOUSE AND EXITING
 REAR DOORS SHOULD BE ALARMED WITH A SENSOR AND VIEW
 FINDER.
 (4) SILENT PANIC ALARM UNDER EACH REGISTER, ONE IN THE
 BACK OF HOUSE WORK AREA
 (5) A SECURED DROP SAFE OR CASH MANAGEMENT DEVICE FOR
 RESTRICTED ACCESS TO MONEY/CASH RECEIPTS AT THE
 REGISTER AND A SECURED DROP SAFE OR CASH MANAGEMENT
 DEVICE IN THE STORAGE AREA.
 (6) CASH OUT AREA SHOULD BE IN THE FRONT OF THE STORE,
 CLOSE TO THE ENTRANCE.
 (7) SECURE THE REGISTERS TO THE COUNTER.
 (8) INSTALL ANTI-THEFT DEVICES INCLUDING SECURITY
 TOWERS AT ENTRANCES.
 (9) USE CONVEX MIRRORS IN CORNERS AND ANTI-THEFT TAGS
 ON MERCHANDISE.
 (10) HEIGHT MARKERS AT THE ENTRANCE AND EXIT.
 (11) EMPLOYEE ACCESS CONTROL ON ALL DOORS THAT LEAD
 INTO THE BACK.
 (12) WHERE WINDOW(S) ARE PRESENT, A CLEAR AND
 UNOBSTRUCTED VIEW FROM OUTSIDE THE STORE AND IN A
 NORMAL LINE OF SIGHT OF THE CASH REGISTER AND SALES
 TRANSACTION AREA
 (13) IF INSTALLING SWING GATE AT REGISTERS THEY SHOULD
 HAVE SIMPLE ACCESS CONTROL.
 (14) ALL SHOWCASES SHOULD HAVE LOCKS AND IN THE
 EXPENSIVE SHOWCASES, CONSIDER AN ALARM.
 (15) INTERIOR SHELVING AND DISPLAYS SHOULD BE NO HIGHER
 THAN FIVE FEET, EVEN LESS IN FRONT OF WINDOWS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-11-26 Cont ID  
Sent By rregueir Date 2013-11-26 Time 16:32 Rev Time 0.00
Received By rregueir Date 2013-11-26 Time 16:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-08-14 Cont ID  
Sent By eschnide Date 2013-08-14 Time 14:29 Rev Time 0.50
Received By eschneid Date 2013-08-14 Time 14:29 Sent To  
Notes
2013-08-14 14:30:15SIGNS AND AWNINGS REQUIRE SEPARATE PERMITS WITH PLANS.