| 2013-08-17 13:46:00 | BUILDING PLAN REVIEW |
| | PERMIT:13070828 |
| | ADD: 1741 PALM BEACH LAKES BLVD SUITE # ??????? |
| | CONT:TO BE DETERMINED |
| | TEL: (561)###-#### |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SATURDAY AUGUST 17/2013 |
| | ACTION: DENIED |
| | |
| | 1) THE PLANS NOR PERMIT APPLICATION PROVIDE THE SUITE # |
| | WHERE WORK IS TO BE COMPLETED UNDER THIS PERMIT. 2010 |
| | FBC 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) PB OUTLET MALLS: |
| | BUILDING PROVISO: |
| | A LETTER FROM THE QUALIFIER OF BOTH THE SHELL |
| | CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT |
| | CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT |
| | PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| | CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK |
| | HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY |
| | WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| | DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND |
| | NOTARIZED. |
| | |
| | 3) 0013/ SHEET A6.1 DETAIL #9 HIGH LOW DRINKING |
| | FOUNTAINS, PLEASE BE AWARE THAT THE HIGH SIDE DRINKING |
| | FOUNTAIN DOES NOT INDICATE THE VERTICAL CLEARANCE |
| | BENEATH WHERE BASIN PORTION OF THE UNIT, COMMONLY IT |
| | DOES NOT MEET SECTION 2010 FBC ACCESSIBILITY CODE: |
| | 2010 FL ACCESSIBILITY CODE AT DRINKING FOUNTAIN THE |
| | UPPER DRINKING FOUNTAIN WILL TO COMPLY WITH |
| | 2010 FL ACCESSIBILITY CODE 307.2 OBJECTS WITH LEADING |
| | EDGES MORE THAN 27 INCHES (685 MM) AND NOT MORE THAN 80 |
| | INCHES (2030 MM) ABOVE THE FINISH FLOOR OR GROUND SHALL |
| | PROTRUDE 4 INCHES (100 MM) MAXIMUM HORIZONTALLY INTO |
| | THE CIRCULATION PATH. |
| | |
| | ADVISORY 307.2 PROTRUSION LIMITS. |
| | WHEN A CANE IS USED AND THE ELEMENT IS IN THE |
| | DETECTABLE RANGE, IT GIVES A PERSON SUFFICIENT TIME TO |
| | DETECT THE ELEMENT WITH THE CANE BEFORE THERE IS BODY |
| | CONTACT. ELEMENTS LOCATED ON CIRCULATION PATHS, |
| | INCLUDING OPERABLE ELEMENTS, MUST COMPLY WITH |
| | REQUIREMENTS FOR PROTRUDING OBJECTS. |
| | |
| | 4) 0015/ SHEET A7.1 THE ACCESSIBLE DRESSING ROOM PLEASE |
| | REVIEW THE REQUIREMENTS FOR A BACK SUPPORT ON THE |
| | BENCH. |
| | 2010 FBC- ACCESSIBILITY CODE 903.4 BACK SUPPORT. |
| | THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE |
| | AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 INCHES |
| | (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A POINT 2 |
| | INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE TO A |
| | POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT |
| | SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM) |
| | MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED |
| | HORIZONTALLY. |
| | |
| | |
| | ADVISORY 903.4 BACK SUPPORT. |
| | TO ASSIST IN TRANSFERRING TO THE BENCH, CONSIDER |
| | PROVIDING GRAB BARS ON A WALL ADJACENT TO THE BENCH, |
| | BUT NOT ON THE SEAT BACK. IF PROVIDED, GRAB BARS CANNOT |
| | OBSTRUCT TRANSFER TO THE BENCH. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |