Plan Review Details - Permit 13070820
Plan Review Stops For Permit 13070820
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-09-27 Cont ID  
Sent By jwitmer Date 2013-09-27 Time 15:40 Rev Time 0.00
Received By jwitmer Date 2013-09-27 Time 15:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-02 Cont ID  
Sent By jwitmer Date 2013-08-02 Time 17:08 Rev Time 0.00
Received By jwitmer Date 2013-08-02 Time 16:30 Sent To  
Notes
2013-08-02 17:08:54BUILDING PLAN REVIEW
 PERMIT: 13070820
 ADD: 846 SOUTHERN BLVD
 CONT: ITASCA CONSTRUCTION
 TEL: (561)241-4999
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: AUGUST 02/2013
 ACTION: DENIED
  
 1) SHEET A-3 INDICATES NEW STOREFRONT WINDOWS, NEW
 SLIDING BY-PASS DOORS & TRANSOM PLEASE PROVIDE THE
 FOLLOW INFORMATION:
 MISSING WIND DESIN CRITERIA FOR THE ASSOCIATED
 PRESSURES SHOWN, LOCATION IS A "C" EXPOSURE.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 1.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS & TRANSOM & MULLIONS..
 (B) WINDOWS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-09-03 Cont ID  
Sent By dharvey Date 2013-09-03 Time 14:06 Rev Time 0.00
Received By dharvey Date 2013-09-03 Time 14:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-09-18 Cont ID  
Sent By wjolin Date 2013-09-18 Time 16:26 Rev Time 0.00
Received By wjolin Date 2013-09-18 Time 16:26 Sent To  
Notes
2013-09-18 16:27:01846 SOUTHERN BOULEVARD
 PERMIT #13070820
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 GENERAL: ALL CONSTRUCTION AND DEMOLITION WORK SHALL
 CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH AND
 CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 GENERAL: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE
 DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE
 EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR
 MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED BY EMAIL ([email protected]) OR
 IN WRITING (FAX: 561-804-4774) AND APPROVED BY THE
 OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE
 HIGHWAY.
  
 GENERAL: SHELVING AND STORAGE SHALL NOT EXCEED 12 FEET
 IN HEIGHT; OTHERWISE, THE DESIGN SHALL MEET THE FIRE
 AND LIFE SAFETY REQUIREMENTS FOR "HIGH-PILED STORAGE."
  
 SHEET A-1 (DOOR #8): PER SECTION 7.2.1.9.1.3 - POWER
 OPERATED DOORS: THE POWERED SLIDING DOOR ASSEMBLY SHALL
 BE DESIGNED AND INSTALLED SO THAT, WHEN A FORCE IS
 APPLIED TO THE DOOR LEAF ON THE SIDE FROM WHICH EGRESS
 IS MADE, IT SHALL BE CAPABLE OF SWINGING FROM ANY
 POSITION TO PROVIDE FULL USE OF THE REQUIRED WIDTH OF
 THE OPENING IN WHICH IT IS INSTALLED. A READILY
 VISIBLE, DURABLE SIGN IN LETTERS NOT LESS THAN 1-INCH
 HIGH ON A CONTRASTING BACKGROUND THAT READS AS FOLLOWS
 SHALL BE LOCATED ON THE EGRESS SIDE OF EACH DOOR
 OPENING: IN EMERGENCY, PUSH TO OPEN.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-07-31 Cont ID  
Sent By wjolin Date 2013-07-31 Time 14:49 Rev Time 0.00
Received By wjolin Date 2013-07-31 Time 14:32 Sent To  
Notes
2013-07-31 14:49:14846 SOUTHERN BOULEVARD
 PERMIT #13070820
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 GENERAL: ALL CONSTRUCTION AND DEMOLITION WORK SHALL
 CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH AND
 CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 GENERAL: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE
 DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE
 EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR
 MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED BY EMAIL ([email protected]) OR
 IN WRITING (FAX: 561-804-4774) AND APPROVED BY THE
 OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE
 HIGHWAY.
  
 GENERAL: SHELVING AND STORAGE SHALL NOT EXCEED 12 FEET
 IN HEIGHT; OTHERWISE, THE DESIGN SHALL MEET THE FIRE
 AND LIFE SAFETY REQUIREMENTS FOR "HIGH-PILED STORAGE."
  
 SHEET A-1 (DOOR #8): PER SECTION 7.2.1.9.1.3 - POWER
 OPERATED DOORS: THE POWERED SLIDING DOOR ASSEMBLY SHALL
 BE DESIGNED AND INSTALLED SO THAT, WHEN A FORCE IS
 APPLIED TO THE DOOR LEAF ON THE SIDE FROM WHICH EGRESS
 IS MADE, IT SHALL BE CAPABLE OF SWINGING FROM ANY
 POSITION TO PROVIDE FULL USE OF THE REQUIRED WIDTH OF
 THE OPENING IN WHICH IT IS INSTALLED. A READILY
 VISIBLE, DURABLE SIGN IN LETTERS NOT LESS THAN 1-INCH
 HIGH ON A CONTRASTING BACKGROUND THAT READS AS FOLLOWS
 SHALL BE LOCATED ON THE EGRESS SIDE OF EACH DOOR
 OPENING: IN EMERGENCY, PUSH TO OPEN.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-09-27 Cont ID  
Sent By jwitmer Date 2013-09-27 Time 15:40 Rev Time 0.00
Received By jwitmer Date 2013-09-13 Time 07:13 Sent To  
Notes
2013-09-16 07:14:02C13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-03 Cont ID  
Sent By shill Date 2013-09-03 Time 14:10 Rev Time 0.00
Received By shill Date 2013-07-23 Time 16:00 Sent To  
Notes
2013-07-23 16:00:42C15

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-08-28 Cont ID  
Sent By hmoser Date 2013-08-28 Time 13:48 Rev Time 0.00
Received By hmoser Date 2013-08-28 Time 13:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-08-12 Cont ID  
Sent By lwagner Date 2013-08-12 Time 15:39 Rev Time 0.00
Received By lwagner Date 2013-08-12 Time 15:21 Sent To  
Notes
2013-08-12 15:35:36STACK FOR WASHING MACHINE SHALL BE 3" FBC PLUMBING
 406.3