Plan Review Details - Permit 13070818
Plan Review Stops For Permit 13070818
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2013-09-04 Cont ID  
Sent By   Date 2013-09-04 Time   Rev Time 0.00
Received By   Date 2013-09-04 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-04-01 Cont ID  
Sent By jwitmer Date 2014-04-01 Time 11:33 Rev Time 0.00
Received By jwitmer Date 2014-04-01 Time 11:33 Sent To  
Notes
2014-04-01 11:37:39SUBMITTALS REGARDING TRULITE GLAZING WERE E-MAILED NOA
 12-0109.04/ NOA 11-0624.02 AND PICTURE DOCUMENT OF
 STICKER ON GLAZING WITH REQUIRED VERBAGE. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-10-27 Cont ID  
Sent By jwitmer Date 2013-10-27 Time 12:32 Rev Time 0.00
Received By jwitmer Date 2013-10-27 Time 09:20 Sent To  
Notes
2013-10-27 10:56:58BUILDING PLAN REVIEW
 PERMIT: 13070818
 ADD: 1807 PALM BEACH LAKES
 CONT: HALEY CONSTRUCTION, INC
 TEL: (386)566-7437
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SUNDAY OCT. 27/ 2012
 ACTION: BUILDING PROVISO:
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET S4.1 DETAIL # 2 THE CLEAR VERTICAL SPACE UNDER
 A/C CONDENSER STANDS IS TAKEN FROM FINISH ROOF TO THE
 BOTTOM HORIZONTAL FRAMING MEMBER OF THE STAND.
 VERTICAL CLEARANCE IS TO COMPLY WITH THE 2010 FBC-B
 TABLE 1509.7
  
 2) ROOF PRODUCT APPROVAL:
 FL 10128-R4
 FIRESTONE SINGLE PLY SYSTEM
 SUB-SYSTEMS NOT IDENTIFIED, WILL REQUIRE A SEPARATE
 ROOFING PERMIT, REVIEW & ASSOCIATED FEES!!!
  
 3) REVISION REQUIRED:
 NOA 09-0122.01 - EXPIRED
 KD WINDOWS/ HORIZONTAL SLIDERS
 NON-IMPACT
  
 4) REVISION REQUIRED:
 FL812-R5
 ARMOUR SCREEN
 SYSTEM NOT IDENTIFIED AS TO INSTALLATION LOCATION,
 SYSTEM TYPE APPLICATION NOT IDENTIFIED, WIDTH & HEIGHT
 OF OPENING, FASTENRES NOR PRESSURES ASSOCIATED WITH
 OPENING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-10-17 Cont ID  
Sent By jwitmer Date 2013-10-17 Time 18:49 Rev Time 0.00
Received By jwitmer Date 2013-10-17 Time 17:00 Sent To  
Notes
2013-10-17 17:35:49BUILDING PLAN REVIEW
 PERMIT: 13070818
 ADD: 1807 PALM BEACH LAKES
 CONT: HALEY CONSTRUCTION, INC
 TEL: (386)566-7437
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: OCT. 17/ 2012
 ACTION: DENIED
  
 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE AND REPLACE ANY PAGES AS
 NECESSARY. DO NOT LEAVE THE VOID SHEETS INTHE SET!!!!!
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1A) PLEASE CORRECT THE ADDRESS ON BOTH THE PERMIT
 APPLICATION AND PLANS FOR ALL TRADES. THE PERMIT
 APPLICATION READS 1801 PALM BEACH LAKES WHICH WAS THE
 OVER ALL SITE ADDRESS, AND THE PLANS INDICATE A
 ADDRESSS OF 1721 WHICH IS ASSIGNED TO BUILDINF J-6 OF
 THE PLAM BEACH OUTLETMALL, THE 1721 ADDRESS ALSO HAD
 BEEN ASSIGNED TO THE OVERALL SITE ADRESS BUT WENT TO
 BEING THE ADDRESS FOR BUILDING J6. SHEET C-3 INDICATES
 THE LOCATION OF THE BUILDING AS A OUT PARCEL LOCATED AT
 THE SITE 1721 PALM BEACH LAKES. ALL SHEETS WILL NEED TO
 BE CORRECTED TO 1807 PALM BEACH LAKES BLVD!!!!!!
  
 1B) COMPLIED. CALCULATED VALUETHE PERMIT APPLICATION
 INDICATES A VALUE OF $500,000.00. CALCULATED VALUE OF
 PROJECT IS $960,000.00.
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 1C) PROJECTS LOCATED AT THE PALM BEACH OUTLET MALL
 REQUIRE THE PLANS TO BE STAMPED REVIEWED BY PALM BEACH
 OUTLET MALL.
  
 2) 2ND REQUEST. THE ARCHITECTURAL SHEETS ARE SIGNED BY
 RUBBER STAMP NOT AN ORIGINAL SIGNATURE. PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN CODE
 61G16.003 ARCHITECTS
  
 3) COMPLIED.
  
 4) 2ND REQUEST, SHEET S0.0 UNDER THE HEADING OF SPECIAL
 INSPECTION NOTES INDICATES THE OWNER TO PROVIDE A
 RESIDENT INSPECTOR TO OVERSEE THE STRUCTURAL JOBSITE
 INSPECTIONS.AMENDMENT TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 2010 EDITION, WEST PALM
 BEACH 110.3.9 THE BUILDING OFFICIAL MAY MAKE, OR CAUSE
 TO BE MADE
 BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109.
 HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF RECOGNIZED
 INSPECTION SERVICES, PROVIDED THAT AFTER INVESTIGATION
 HE/SHE IS SATISFIED AS TO THEIR QUALIFICATIONS AND
 RELIABILITY. A CERTIFICATE CALLED FOR BY ANY PROVISION
 OF THE TECHNICAL CODES SHALL NOT BE BASED ON SUCH
 REPORTS UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY
 A RESPONSIBLE OFFICER OF SUCH SERVICE.
  
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH
 INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
  
 AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT,
 SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF
 COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE
 WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN
 ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION
 SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A
 CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION
 IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT
 ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS.
  
 PLEASE CONTACT KEN CONRAD THE MANAGER OF THE RESIDENT
 INSPECTOR PROGRAM FOR REQUIREMENTS AND DOCUMENTS THAT
 MUST BE SUBMITTED FOR A RESIDENT INSPECTOR TO BE
 APPROVED WITHIN THE CITY OF WEST PALM BEACH. CONTACT
 INFO;
 KEN CONRAD CHIEF BUILDING INSPECTOR
 TEL: 561-805-6666
 FAX: 561-805- 6676
 E-MAIL: KCONRAD @WPB.ORG
  
 5) 2ND REQUEST, ONLY 2 SETS SUBMITTED.PLEASE SUBMIT 3
 SETS OF PLANS AND PRODUCT APPROVALS (STRUCTURAL &
 ACHITECTURAL) FOR THE RESIDENT INSPECTOR, 1 SET FOR THE
 CONTRACTOR, ONE SET FOR THE RESIDENT INSPECTOR AND THE
 THIRD WILL BE THE OFFICE FILE SET.
  
 6) 2ND REQUEST. MISSING SOILS REPORT 2010 FBC-B
 1803.5.2 QUESTIONABLE SOILS.
 1803.6 REPORTING.
 WHERE GEOTECHNICAL INVESTIGATIONS ARE REQUIRED, A
 WRITTEN REPORT OF THE INVESTIGATIONS SHALL BE SUBMITTED
 TO THE BUILDING OFFICIAL BY THE OWNER OR AUTHORIZED
 AGENT AT THE TIME OF PERMIT APPLICATION. THIS
 GEOTECHNICAL REPORT SHALL INCLUDE, BUT NEED NOT BE
 LIMITED TO, THE FOLLOWING INFORMATION:
 6.1. A PLOT SHOWING THE LOCATION OF THE SOIL
 INVESTIGATIONS.
 6.2. A COMPLETE RECORD OF THE SOIL BORING AND
 PENETRATION TEST LOGS AND SOIL SAMPLES.
 6.3. A RECORD OF THE SOIL PROFILE.
 6.4. ELEVATION OF THE WATER TABLE, IF ENCOUNTERED.
 6.5. RECOMMENDATIONS FOR FOUNDATION TYPE AND DESIGN
 CRITERIA, INCLUDING BUT NOT LIMITED TO: BEARING
 CAPACITY OF NATURAL OR COMPACTED SOIL; PROVISIONS TO
 MITIGATE THE EFFECTS OF EXPANSIVE SOILS; MITIGATION OF
 THE EFFECTS OF LIQUEFACTION, DIFFERENTIAL SETTLEMENT
 AND VARYING SOIL STRENGTH; AND THE EFFECTS OF ADJACENT
 LOADS.
 6.6. EXPECTED TOTAL AND DIFFERENTIAL SETTLEMENT.
  
 7-9) COMPLIED.
  
 10) 2ND REQUEST. SHEET A0.1 & A0.1A IS ANSI 117.1,
 PLEASE REFER TO THE 2010 FBC-ACCESSIBILITY CODE.
 FLORIDA STATUTE 553.80 PROVIDES FOR THE ENFORCEMENT
 OF THIS PART OF THE CODE, THE DEPARTMEENT OF JUSTICE
 HAS CERTIFIED THIS CODE.
  
 11-14) COMPLIED.
  
 15) 2ND REQUEST, SEMI-COMPLIED. SHEET S4.0:
 15A) SEMI-COMPLIED. SHEET A3.1 ROOF TOP ELEVATION OF
 34'-0"/ PARAPET AT 35'-0".
  
 15B) COMPLIED.
  
 15C) COMPLIED.
  
 15D) 2ND REQUEST. ROOF PRESSURES FOR ROOF ZONE # 3 ARE
 TAKEN AS THE SAME FOR ROOF ZONE # 2, WHICH IS CORRECT
 WHEN THERE IS A ROOF PARPET OF AT LEASRT 3'-0" TALL.
 PLEASE REFER TO SHEET A3.1 WHERE THE ROOF TOP ELEVATION
 IS 34'-0".
  
 16) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 17) 2ND REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING, NO PRODUCT
 APPROVALS SUBMITTED THIS REVIEW, RESONSE SHEET
 INDICATES PROVIDED???
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 18) 2ND REQUEST,, SHEET S4.1 A/C STANDS (RACKS, NOT
 CURBS) ARE TO COMPLY WITH 2010 FBC-B 1509.7 MECHANICAL
 UNITS. THE VERTICAL CLEAR DIMENSION FOR A/C CONDENSORS
 ON THE ROOF IS FROM THE BOTTOM OF THE RACK FRAMING
 MEMBERS TO FINISH ROOF NOT THE STEEL STRUCTURAL DECK.
 ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS
 RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.7.
  
 19) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-05 Cont ID  
Sent By jwitmer Date 2013-08-05 Time 16:15 Rev Time 0.00
Received By jwitmer Date 2013-08-05 Time 07:05 Sent To  
Notes
2013-08-05 08:51:22BUILDING PLAN REVIEW
 PERMIT: 13070818
 ADD: 1801 PALM BEACH LAKES (WILL NEED TO BE CORRECTED,
 THIS IS THE OVERALL SITE ADDRESS)
 CONT: HALEY CONSTRUCTION, INC
 TEL: (386)566-7437
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: AUGUST 05/ 2012
 ACTION: DENIED
  
 1A) PLEASE CORRECT THE ADDRESS ON BOTH THE PERMIT
 APPLICATION AND PLANS. THE PERMIT APPLICATION READS
 1801 PALM BEACH LAKES WHICH IS THE OVER ALL SITE
 ADDRESS, AND THE PLANS INDICATE A ADDRESSS OF 1721
 WHICH IS ASSIGNED TO BUILDINF J-6 OF THE PLAM BEACH
 OUTLET MALL. SHEEET C-3 INDICATES THE LOCATION OF THE
 BUILDING AS A OUT PARCEL LOCATED AT THE SITE 1801 PALM
 BEACH LAKES.
  
 1B) THE PERMIT APPLICATION INDICATES A VALUE OF
 $500,000.00. CALCULATED VALUE OF PROJECT IS
 $960,000.00.
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFRENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 1C) PROJECTS LOCATED AT THE PALM BEACH OUTLET MALL
 REQUIRE THE PLANS TO BE STAMPED REVIEWED BY PALM BEACH
 OUTLET MALL.
  
 2) THE ARCHITECTURAL SHEETS ARE SIGNED BY RUBBER STAMP
 NOT AN ORIGINAL SIGNATURE. PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC RECORD SHALL
 HAVE THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL
 AFFIXED TO THE DOCUMENT. FL ADMIN CODE 61G16.003
 ARCHITECTS
  
 3) THE STRUCTURAL SHEETS ARE NOT SIGNED NOR SEALED,
 BEFORE PERMIT ISSUANCE THEY WILL NEED TO MEET THE
 REQUIREMENTS OF :
 FL ADMIN CODE 61G15-23.002 ENGINEERS PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 4) SHEET S0.0 UNDER THE HEADING OF SPECIAL INSPECTION
 NOTES INDICATES THE OWNER TO PROVIDE A SPCEIAL
 INSPECTOR. PLEASE BE AWARE THE TERM SPECIAL INSPECTOR
 RELATES TO FL S 553.79 SPECIAL INSPECTORS FOR THRESHOLD
 BUILDINGS. THIS BUILDING MAY BE AN A2 ASSEMBLY BUILDING
 AND OVER 5,000 SQ FT BUT DOESN'T HAVE AN OCCUPANT LOAD
 OF 500 THEREFORE A SPECIAL INSPECTOR IS NOT REQUIRED BY
 FL S 553.79.
  
 THE OWNER MAY WANT TO HIRE ON A RESIDENT INSPECTOR TO
 OVERSEE THE STRUCTURAL JOBSITE INSPECTIONS.AMENDMENT TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 2010 EDITION, WEST PALM BEACH 110.3.9 THE BUILDING
 OFFICIAL MAY MAKE, OR CAUSE TO BE MADE
 BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109.
 HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF RECOGNIZED
 INSPECTION SERVICES, PROVIDED THAT AFTER INVESTIGATION
 HE/SHE IS SATISFIED AS TO THEIR QUALIFICATIONS AND
 RELIABILITY. A CERTIFICATE CALLED FOR BY ANY PROVISION
 OF THE TECHNICAL CODES SHALL NOT BE BASED ON SUCH
 REPORTS UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY
 A RESPONSIBLE OFFICER OF SUCH SERVICE.
  
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH
 INSPECTORS SHALL SUBMIT
 WEEKLY PROGRESS REPORTS INCLUDING THE DAILY INSPECTIONS
 TO THE BUILDING OFFICIAL, AND INCLUDING A CODE
 COMPLIANCE OPINION OF THE RESIDENT INSPECTOR.
  
 AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT,
 SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF
 COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE
 WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN
 ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION
 SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A
 CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION
 IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT
 ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS.
  
 PLEASE CONTACT KEN CONRAD THE MANAGER OF THE RESIDENT
 INSPECTOR PROGRAM FOR REQUIREMENTS AND DOCUMENTS THAT
 MUST BE SUBMITTED FOR A RESIDENT INSPECTOR TO BE
 APPROVED WITHIN THE CITY OF WEST PALM BEACH. CONTACT
 INFO;
 KEN CONRAD CHIEF BUILDING INSPECTOR
 TEL: 561-805-6666
 FAX: 561-805- 6676
 E-MAIL: KCONRAD @WPB.ORG
  
 5) PLEASE SUBMIT 3 SETS OF PLANS AND PRODUCT APPROVALS
 (STRUCTURAL & ACHITECTURAL) FOR THE RESIDENT INSPECTOR,
 1 SET FOR THE CONTRACTOR, ONE SET FOR THE RESIDENT
 INSPECTOR AND THE THIRD WILL BE THE OFFICE FILE SET.
  
 6) MISSING SOILS REPORT 2010 FBC-B 1803.5.2
 QUESTIONABLE SOILS.
 1803.6 REPORTING.
 WHERE GEOTECHNICAL INVESTIGATIONS ARE REQUIRED, A
 WRITTEN REPORT OF THE INVESTIGATIONS SHALL BE SUBMITTED
 TO THE BUILDING OFFICIAL BY THE OWNER OR AUTHORIZED
 AGENT AT THE TIME OF PERMIT APPLICATION. THIS
 GEOTECHNICAL REPORT SHALL INCLUDE, BUT NEED NOT BE
 LIMITED TO, THE FOLLOWING INFORMATION:
 6.1. A PLOT SHOWING THE LOCATION OF THE SOIL
 INVESTIGATIONS.
 6.2. A COMPLETE RECORD OF THE SOIL BORING AND
 PENETRATION TEST LOGS AND SOIL SAMPLES.
 6.3. A RECORD OF THE SOIL PROFILE.
 6.4. ELEVATION OF THE WATER TABLE, IF ENCOUNTERED.
 6.5. RECOMMENDATIONS FOR FOUNDATION TYPE AND DESIGN
 CRITERIA, INCLUDING BUT NOT LIMITED TO: BEARING
 CAPACITY OF NATURAL OR COMPACTED SOIL; PROVISIONS TO
 MITIGATE THE EFFECTS OF EXPANSIVE SOILS; MITIGATION OF
 THE EFFECTS OF LIQUEFACTION, DIFFERENTIAL SETTLEMENT
 AND VARYING SOIL STRENGTH; AND THE EFFECTS OF ADJACENT
 LOADS.
 6.6. EXPECTED TOTAL AND DIFFERENTIAL SETTLEMENT.
  
 7) SHEET G1.0;
 7A) OCCUPANT LOAD CALCULATIONS ARE ALL GIVEN UNDER THE
 FFPC, PLEASE PROVIDE THE SAME CALCULATIONS UNDER THE
 2010 FBC-B TABLE 1004.1.1. THE BAR IS CHAIRS ONLY,
 CONCENTRATED 7 SQ FT/ OCCUPANT. THE SECOND QUESTION IS
 THE OCCUPANT LOAD STATED A NET FIGURE THAT ALLOWS FOR
 THE AREA USED FOR PERMANENT BUILDING COMPONENTS, SUCH
 AS SHAFTS, FIXED EQUIPMENT, THICKNESS OF WALLS,
 CORRIDORS, TOILET ROOMS, MECHANICAL ROOMS AND CLOSETS
 ARE NOT TO BE INCLUDED IN THE NET FLOOR AREA.
  
 7B) CODE INFORMATION, BUILDING DESCRIPTION INDICATES
 THIS BUILDING TO BE A VB- SPRINKLERED BUILDING. AREA
 INCREASES WERE TAKEN FOR A FIRE SPRINKLERED BUILDING
 BUT NO FIRE SPRINKLER PLANS WERE SUBMITTED.
  
 8) SHEET G1.0 NOR THE C-3 PROVIDE A ANALYSIS ON
 ACCESSIBLE PARKING AND HOW COMPLIANCE WITH 2010 FL
 ACCESSIBILITY CODE TABLE 208.2 WAS ACHIEVED?
  
 9) SHEET C6 SHOWS PARKING STALL LINES AS SINGLE
 STRIPED, PLEASE SEE WEST PALM BEACH ZONING CODE FOR
 DOUBLE STRIPPING.
  
  
 10) SHEET A0.1 & A0.1A IS ANSI 117.1, PLEASE REFER TO
 THE 2010 FBC-ACCESSIBILITY CODE. FLORIDA STATUTE 553.80
 PROVIDES FOR THE ENFORCEMENT
 OF THIS PART OF THE CODE, THE DEPARTMEENT OF JUSTICE
 HAS CERTIFIED THIS CODE.
  
 11) SHEET A1.0;
  
 11A) SHEET A1.0, A1. A1.2 & A4.2 DETAIL # 15 ALL
 INDICATE A STAIR TREAD OF 11". PLEASE SHOW COMPLIANCE
 WITH 2010 FBC-B 1003.5 EXCEPTION # 2 THAT REQUIRES A 13
 INCH TREAD, ALSO REVIEW HANDRAIL REQUIREMENTS.
  
 11B) SHEET A1.0, A1.2 & A4.2 DETAIL # 18 INDICATE A ONE
 FOOT DIFFERENCE IN GRADE, THESE DETAILS DO NOT SHOW
 COMPLIANCE WITH FBC-B 1003.5 ELEVATION CHANGE.
  
 12) SHEET A1.1 THE EMPLOYEES RESTROOM # 117 , THE
 INSWING DOOR SWINGS OVER THE CLEAR FLOOR SPACE REQUIRED
 FOR THE WATER CLOSET. 2010 FL ACCESSIBILITY CODE
 604.3.2 NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE
 LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
 PLEASE NOTE: 603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
 EXCEPTIONS: 2. WHERE THE TOILET ROOM OR BATHING ROOM IS
 FOR INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING
 WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC
 OF THE DOOR SWING, DOORS SHALL BE PERMITTED TO SWING
 INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR
 ANY FIXTURE.
  
 13A) SHEET A1.1 , A3.4-01 & S1.0 DEAL WITH AN ATTIC
 ACCESS, AND ATTIC, AND ACCESS TO THE ROOF TOP. THE
 PLANS ARE NOT CLEAR HOW YOU LEAVE THE LOWER LADDER AND
 TRANSVERSE ACROSS THE FLOOR DECK TO GAIN ACCESS TO THE
 UPPER LADDER TO GAIN ACCESS TO THE ROOF LEVEL. THERE IS
 TWO ISSUES AT HAND, VERTICAL ACCESS TO THE ROOF AS WELL
 AS ATTIC STORAGE WITHOUT SEPERATION. 10107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 13B) THE PLANS ALSO FAIL TO PROVIDE WHERE THE WALLS ARE
 LOCATED AROUND THE VERTICAL ACCESS SCUTTLE HOLE AS WELL
 AS THE STORAGE AERA? 107.2.1.3. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 13C) SHOW COMPLIANCE WITH: 413.2 ATTIC, UNDER-FLOOR AND
 CONCEALED SPACES.
 ATTIC, UNDER-FLOOR AND CONCEALED SPACES USED FOR
 STORAGE OF COMBUSTIBLE MATERIALS SHALL BE PROTECTED ON
 THE STORAGE SIDE AS REQUIRED FOR 1-HOUR
 FIRE-RESISTANCE-RATED CONSTRUCTION. OPENINGS SHALL BE
 PROTECTED BY ASSEMBLIES THAT ARE SELF-CLOSING AND ARE
 OF NONCOMBUSTIBLE CONSTRUCTION OR SOLID WOOD CORE NOT
 LESS THAN 13/4 INCH (45 MM) IN THICKNESS.
 EXCEPTIONS: 1. AREAS PROTECTED BY APPROVED AUTOMATIC
 SPRINKLER SYSTEMS.
  
 13D) 703.6 MARKING AND IDENTIFICATION. FIRE WALLS, FIRE
 BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE
 PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE PROTECTED
 OPENINGS OR PENETRATIONS SHALL BE EFFECTIVELY AND
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING. SUCH
 IDENTIFICATION SHALL: 1. BE LOCATED IN ACCESSIBLE
 CONCEALED FLOOR, FLOOR-CEILING OR ATTIC SPACES;
  
 13E) DRAFTSTOPPING IN ATTICS: 17.4.3 OTHER GROUPS.
 DRAFTSTOPPING SHALL BE INSTALLED IN ATTICS AND
 CONCEALED ROOF SPACES, SUCH THAT ANY HORIZONTAL AREA
 DOES NOT EXCEED 3,000 SQUARE FEET (279 M2). EXCEPTION:
 DRAFTSTOPPING IS NOT REQUIRED IN BUILDINGS EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.3.1.1
  
 13F) PLEASE PROVIDE THE FLOOR LOADING OF THE ATTIC
 SPACE STORAGE, ABOVE GRADE LEVEL TO COMPLY WITH 2010
 FBC-B TABLE 1607.1 (36) 125 PSF LIGHT.
  
 13G) THE STRUCTURAL SHEET S1 KEY NOTE # 1 INDICATES THE
 NORTH SOUTH BEARING WALL CONTINUES TO GRID LINE # 3
 DOES THE ENCLOSED AND RAISED STORAGE CLOSET CONTINUE
 NORTH TO GRID LINE # 3?
  
 14A) SHEET A5.0 INDICATES IN THE DOOR SCHEDULE DOOR #
 15 & 15A PATIO DINING, GATE # 15 IT APPEARS TO BE
 BLOCKED BY TABLES AND 15A NOT SHOWN ON PLANS BUT THERE
 IS A UNMARKED GATE LOCATION? DISCREPANCY IN PLANS
 107.2.1.3.
  
 14B) THE DOOR SCHEDULE FOR DOOR 15, 15A INDICATES
 HARDWARE GROUP # 6 PLANS DO NOT INCLUDE PANIC HARDWARE.
 1008.2 GATES. GATES SERVING THE MEANS OF EGRESS SYSTEM
 SHALL COMPLY WITH THE REQUIREMENTS OF THIS SECTION.
 GATES USED AS A COMPONENT IN A MEANS OF EGRESS SHALL
 CONFORM TO THE APPLICABLE REQUIREMENTS FOR DOORS.
 1008.1.10 PANIC AND FIRE EXIT HARDWARE.
 DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING
 ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN
 A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A
 LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 15) SHEET S4.0:
 15A) WIND PRESSURES, PLEASE PROVIDE AT WHAT THE MEAN
 ROOF HEIGHT THSES VALUES ARE FOR ? ASSUMED 20'-0".
  
 15B) PLEASE PROVIDE IF THESE PRESSURES ARE IN V-ULT OR
 VASD? ASSUMED VULT.
  
 15C) PLEASE PROVIDE THE PRESURES IN VASD SINCE THE
 PRODUCT APPROVALS ARE ALL IN VASD, IT APPEARS THE ROOF
 PRESSURES ARE CORRECT BUT THE
 WALL ZONES 4 & 5 APPEAR TO BE LOW IN PRESSURE ZONE 4 &
 ZONE 5. 132 MPH VASD 20' MEAN ROOF HEIGHT, EXP "C"
 ZONE 4/ 10 SQ FT +40.4/ -43.8
 ZONE 5/ 10 SQ FT +40.4/ 54.1
  
 16) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 17) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 18) SHEET S4.1 A/C STANDS ARE TO COMPLY WITH 2010 FBC-B
 1509.7 MECHANICAL UNITS.
 ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS
 RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.7.
  
 19) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-10-10 Cont ID  
Sent By dharvey Date 2013-10-10 Time 15:47 Rev Time 0.00
Received By dharvey Date 2013-10-10 Time 14:01 Sent To B1
Notes
2013-10-10 14:51:42REVIEWED BY WDS.
 PLACED IN BIN C-35

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-09-04 Cont ID  
Sent By dharvey Date 2013-09-04 Time 12:34 Rev Time 0.00
Received By dharvey Date 2013-09-04 Time 12:00 Sent To  
Notes
2013-09-04 12:18:11 
 FIRST REVIEW 9-4-13
  
 1. ALL LV SYSTEMS WILL REQUIRE SEPARATE APPLICATIONS
 AND PERMITS
 2. ALL LV CABLES INSTALLED UNDERGROUND OR IN THE
 SLAB,WHETHER IN CONDUIT OR NOT, SHALL BE RATED AS A WET
 LOCATION AND CABLES SHALL BE LISTED FOR SUCH USE
 3. ALL OUTDOOR GFCI RECPTS SHALL HAVE IN USE TYPE
 COVERS. REVISE NOTE 21 ON PAGE E0,1
 4. ARC FLASH PROTECTION LABELING SHALL BE AFFIXED TO
 ELECTRICAL EQUIPMENT PER NEC 110.16
 5. PROVIDE SPECIFICATIONS FOR LIGHTING CONTRIL PANEL
 6. ALL LIGHTING SHALL CONFORM TO FBC ENERGY CODE
 SECTION 505, (SUCH AS DESIGNATED NIGHT LIGHTING)
 7. PROVIDE CUT SHEETS WITH MOUNTING DETAILS FOR
 CHANDELIERS AND ANY FIXTURES OVER 50 POUNDS
  
 END OF FIRST REVIEW - VB

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2013-09-05 Cont ID  
Sent By Mgonzale Date 2013-09-05 Time   Rev Time 1.00
Received By shill Date 2013-09-05 Time 11:41 Sent To Z
Notes
2013-09-05 14:52:23PLANS ARE ACCEPTABLE.
 WILL STAMP FINAL PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-10-07 Cont ID  
Sent By wjolin Date 2013-10-07 Time 11:21 Rev Time 0.00
Received By scaldero Date 2013-10-07 Time 11:21 Sent To  
Notes
2013-10-07 11:24:26PERMIT # 13070818
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS PROVIDED ON THE PLANS FOR THE FIRE ALARM
 SYSTEM AND FIRE SPRINKLER SYSTEM DO NOT MATCH THE
 ADDRESS PROVIDED ON THE PERMIT APPLICATION.
  
 SEPARATE PLANS AND PERMITS WILL BE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM. ALL SHOP DRAWINGS NEED
 TO INDICATE THE CORRECT ADDRESS.
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-07-30 Cont ID  
Sent By wjolin Date 2013-07-30 Time 17:42 Rev Time 0.00
Received By wjolin Date 2013-07-30 Time 16:45 Sent To  
Notes
2013-07-30 17:42:431801 PALM BEACH LAKES BOULEVARD
 PERMIT #13070818
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: THE ADDRESS OF 1721 PALM BEACH LAKES BOULEVARD
 APPEARS TO HAVE ALREADY BEEN ASSIGNED ANOTHER MALL
 BUILDING (BLDG J-6) LOCATED AT THE FAR EAST OF THE
 PARKING LOT.
  
 SHEET LP-1: ENSURE TREES AND SHRUBS WILL NOT (OR IN
 FUTURE) OBSTRUCT ACCESS TO FIRE PROTECTION EQUIPMENT.
 PER SECTION 18.3.4.1 (NFPA 1), FIRE HYDRANTS AND FIRE
 PROTECTION EQUIPMENT SHALL BE PROVIDED WITH CLEARANCES
 OF 7'-6" TO THE FRONT AND SIDES AND 4' TO THE BACKSIDE.
  
 SHEET A2.0: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE
 BUILDING ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL
 BE ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES
 IN HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER
 FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. PER FBC
 SECTION 907.1.1 CONSTRUCTION DOCUMENTS - "CONSTRUCTION
 DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE, THE FLORIDA
 FIRE PREVENTION CODE, AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL." PER SECTION 12.3.4.3.3, PROVIDE
 SPEAKER/STROBE NOTIFICATION APPLIANCES AS ASSEMBLY
 OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING 300
 OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY
 VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS. PROVIDE A
 PRE-RECORDED FIRE ALARM EVACUATION MESSAGE NOTIFYING
 OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN THE
 BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION WORK
 SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH
 AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2013-10-04 Cont ID  
Sent By lwagner Date 2013-10-04 Time 15:40 Rev Time 0.00
Received By lwagner Date 2013-10-04 Time 15:19 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-08-13 Cont ID  
Sent By lwagner Date 2013-08-13 Time 14:16 Rev Time 0.00
Received By lwagner Date 2013-08-13 Time 13:28 Sent To  
Notes
2013-08-13 14:16:24***PROVISO***
 EMERGENCY GAS VALVE IS TO BE ACCESSIBLE BELOW CEILING.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-17 Cont ID  
Sent By jwitmer Date 2013-10-17 Time 18:51 Rev Time 0.00
Received By jwitmer Date 2013-09-25 Time 13:16 Sent To  
Notes
2013-09-25 13:17:19C35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-05 Cont ID  
Sent By shill Date 2013-09-05 Time 13:48 Rev Time 0.00
Received By shill Date 2013-07-23 Time 16:09 Sent To  
Notes
2013-09-05 13:49:12RETURNED SET - MG WILL ENTER "P" FOR ENGINEERING
  
2013-09-05 11:42:041 SET TO MG 9/5
  
2013-07-23 16:10:00C35

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-10-17 Cont ID  
Sent By jwitmer Date 2013-10-17 Time 18:50 Rev Time 0.00
Received By jwitmer Date 2013-10-17 Time 18:50 Sent To  
Notes
2013-10-17 18:51:14IMPACT FEE ASSESSMENT:
 PLANS STAMPED NO FEES DUE. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-08-05 Cont ID  
Sent By jwitmer Date 2013-08-05 Time 16:15 Rev Time 0.00
Received By jwitmer Date 2013-08-05 Time 16:15 Sent To  
Notes
2013-08-05 16:15:33BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-10-11 Cont ID  
Sent By hmoser Date 2013-10-11 Time 10:26 Rev Time 0.00
Received By hmoser Date 2013-10-11 Time 09:54 Sent To  
Notes
2013-10-11 10:26:37THE FOLLOWING ITEMS ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW
 HOOD , FIRE SUPPRESSION FOR HOOD AND COOLERS
 ALL REQUIRE SEPARATE APPLICATION, PLANS AND PERMIT
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-09-03 Cont ID  
Sent By hmoser Date 2013-09-03 Time 15:17 Rev Time 0.00
Received By hmoser Date 2013-09-03 Time 13:10 Sent To  
Notes
2013-09-03 15:17:04PLANS DENIED
 REFER TO SECTION 301.12 WIND RESISTANCE .
 1) PROVIDE A DETAIL ON THE PLAN BY THE ENGINEER
 ON CURB TO ROOF TIEDOWN AND RTU TO CURB
 TIEDOWN. 2010 FBC (M)
 2) SEPARATE APPLICATION PLANS AND PERMIT REQUIRED FOR
 HOODS WALK IN COOLERS AND FREEZERS
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-10-04 Cont ID  
Sent By lwagner Date 2013-10-04 Time 15:50 Rev Time 0.00
Received By lwagner Date 2013-10-03 Time 13:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-08-13 Cont ID  
Sent By lwagner Date 2013-08-13 Time 15:27 Rev Time 0.00
Received By lwagner Date 2013-08-12 Time 15:42 Sent To  
Notes
2013-08-12 15:57:01FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. WITH AN AGGREGATE OF 6 OR MORE WATER CLOSETS A
 UNISEX RESTROOM WILL BE REQUIRED. THE FIXTURES IN THE
 UNISEX RESTROOM CAN BE USED IN THE FIXTURE COUNT FOR
 MEN OR WOMEN.
 403.5 UNISEX TOILET AND BATHING ROOMS.
 IN ASSEMBLY AND MERCANTILE OCCUPANCIES, AN ACCESSIBLE
 UNISEX TOILET ROOM SHALL BE PROVIDED WHERE AN AGGREGATE
 OF SIX OR MORE MALE AND FEMALE WATER CLOSETS IS
 REQUIRED. IN BUILDINGS OF MIXED OCCUPANCY, ONLY THOSE
 WATER CLOSETS REQUIRED FOR THE ASSEMBLY OR MERCANTILE
 OCCUPANCY SHALL BE USED TO DETERMINE THE UNISEX TOILET
 ROOM REQUIREMENT. IN RECREATIONAL FACILITIES WHERE
 SEPARATE-SEX BATHING ROOMS ARE PROVIDED, AN ACCESSIBLE
 UNISEX BATHING ROOM SHALL BE PROVIDED. FIXTURES LOCATED
 WITHIN UNISEX TOILET AND BATHING ROOMS SHALL BE
 INCLUDED IN DETERMINING THE NUMBER OF FIXTURES PROVIDED
 IN AN OCCUPANCY.
  
 2. SHEET P1.2 & P2.1 ALL HOSE BIBBS REQUIRE SEPARATE
 SHUTOFF VALVES.
 606.2 LOCATION OF SHUTOFF VALVES.
 SHUTOFF VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 2. ON THE WATER SUPPLY PIPE TO EACH SILLCOCK IN OTHER
 THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
 3. SHEET 4.0 DETAIL #11 SHOWS AC CONDENSATE CONNECTED
 TO A LAVATORY. AC CONDENSATE IS NOT PERMITTED IN THE
 CITY OF WEST PALM BEACH SEWER SYSTEM.
 CITY ORD.SEC. 90-126. - PROHIBITIONS AND LIMITATIONS OF
 DISCHARGE. (5)
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop POLICE POLICE
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2013-09-05 Time   Rev Time 0.00
Received By ktucker Date 2013-09-05 Time 10:45 Sent To  
Notes
2013-09-05 10:46:13ADDITIONAL CAMERA COVERAGE NEEDED TO COVER THE RESTROOM
 VESTIBULE, ADDITIONAL CAMERAS TO THE OUT DOOR SEATING
 AREAS
  
 WHERE IS THE SAFE LOCATIONS AND SHOW THAT THEY WILL BE
 BOLTED DOWN
  
 VIEW FINDERS IN ALL EXITING DOORS
  
 PANIC ALARM AT THE BAR LOCATION
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2013-10-27 Cont ID  
Sent By jwitmer Date 2013-10-27 Time 10:57 Rev Time 0.00
Received By jwitmer Date 2013-10-27 Time 10:57 Sent To  
Notes
2013-10-27 10:59:25BUILDING PLAN REVIEW
 PERMIT: 13070818
 ADD: 1807 PALM BEACH LAKES
 CONT: HALEY CONSTRUCTION, INC
 TEL: (386)566-7437
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SUNDAY OCT. 27/ 2012
 ACTION: BUILDING PROVISO:
  
 1) ROOF PRODUCT APPROVAL:
 FL 10128-R4
 FIRESTONE SINGLE PLY SYSTEM
 SUB-SYSTEMS NOT IDENTIFIED, WILL REQUIRE A SEPARATE
 ROOFING PERMIT, REVIEW & ASSOCIATED FEES!!!
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2013-10-16 Cont ID  
Sent By eschneid Date 2013-10-15 Time 16:39 Rev Time 2.00
Received By eschneid Date 2013-10-15 Time 16:39 Sent To  
Notes
2013-10-15 17:23:13PASSED
  
 THE FOLLOWING SEPARATE PERMITS ARE STILL REQUIRED
  
 1. STRIPING OF THE PARKING SHOWN ON THIS PLAN. THE
 CIVIL PLANS SHALL BE INCLUDED WITH THAT PERMIT.
 2. SEPARATE SIGN PERMITS ARE REQUIRED, TO INCLUDE
 PLANS, FOR THE FOLLOWING.
  
 A. THE TEMPORARY CONSTRUCTION SIGN REQUIRES A PERMIT IN
 ACCORDANCE WITH SECTION 94-407(7) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS. PLEASE NOTE THAT ONLY ONE
 SUCH SIGN IS PERMITTED FOR THE BJ'S RESTAURANT.
 B. THE WALL SIGNS REQUIRE PERMITS.
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2013-08-19 Cont ID  
Sent By esnhid Date 2013-08-19 Time 14:11 Rev Time 2.00
Received By eschneid Date 2013-08-14 Time 17:13 Sent To  
Notes
2013-08-19 15:31:03FAILED
  
 1) PRIOR TO THE ISSUANCE OF THE PERMIT, THE DEVELOPER
 SHALL SUBMIT AND HAVE APPROVED AN UPDATED CONSTRUCTION
 SITE SECURITY PLAN BY THE CITY'S CRIME PERVENTION
 OFFICER WHICH INCLUDES THE BJ'S RESTAURANT SITE.
  
 2) THE SITE PLAN SHALL SHOW THE LOADING SPACE IN FRONT
 OF THE DUMPSTER ENCLOSURE IN ACCORDANCE WITH THE
 APPROVED URBAN DESIGN KILDAY STUDIOS SITE PLAN.
  
 3) THE PLANS ARE REQUIRED TO INCLUDE THE EXTENSION OF
 THE SERVICE AREA WALL TO SCREEN THE LOADING SPACE IN
 ACCORDANCE WITH THE APPROVED URBAN DESIGN KILDAY
 STUDIOS SITE PLAN.
  
 4) THE LANDSCAPE PLANS REQUIRES A SEPARATE PERMIT. THE
 LANDSCAPE PLANS SHALL BE INCLUDED WITH THE NEW PERMIT
 AND NOT WITH THIS PERMIT RESUBMITTAL. CURSORY COMMENTS
 FOR THE LANDSCAPE PLAN.
  
 A. PROVIDE A COST ESTIMATE FOR THE VALUE OF THE
 LANDSCAPE AND INSTALLATION WITH THE LANDSCAPE PERMIT.
 B. THE PLANT SPECIFICATIONS ON THE LANDSCAPE PLAN
 SUBMITTED WITH THE LANDSCAPE PERMIT SHALL MATCH THE
 SPECIFICATIONS ON THE APPROVED URBAN DESIGN KILDAY
 STUDIOS LANDSCAPE PLAN.
 C. THE HEDGE ALONG THE REAR SIDE OF THE BUILDING SHALL
 EXTEND THE FULL LENGTH OF THE EXTENDED LOADING SPACE
 WALL AND BE SHOWN SCREENING THE BACKFLOW PREVENTERS IN
 ACCORDANCE WITH THE APPROVED URBAN DESIGN KILDAY
 STUDIOS SITE PLAN.
 D. THE LANDSCAPE PLAN SHOWS LESS GLAPHIMIA GLAUCA
 SHRUBS THAN THE THE APPROVED URBAN DESIGN KILDAY
 STUDIOS SITE PLAN.
  
 5) A SEPARATE PERMIT IS REQUIRED FOR THE STRIPING OF
 THE PARKING SHOWN ON THIS PLAN. THE CIVIL PLANS SHALL
 BE INCLUDED WITH THAT PERMIT. PLEASE NOTE THAT THE
 ZONING AND LAND DEVELOPMENT REGULATIONS REQUIRE THAT
 THE WHEEL STOPS HAVE A SINGLE FACE, NOT DOUBLE FACE AS
 SHOWN ON SHEET C-4.
  
 6) THE BICYCLE RACK DIMENSIONS SHALL BE INCLUDED ON THE
 SITE PLAN - 11.5 FEET X 6 FEET.
  
 7) SEPARATE SIGN PERMITS ARE REQUIRED, TO INCLUDE
 PLANS, FOR THE FOLLOWING.
  
 A. THE MURAL REQUIRES ITS OWN SIGN PERMIT IN ACCORDANCE
 WITH SECTION 94-410 OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
 B. THE TEMPORARY CONSTRUCTION SIGN REQUIRES A PERMIT IN
 ACCORDANCE WITH SECTION 94-407(7) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS. PLEASE NOTE THAT ONLY ONE
 SUCH SIGN IS PERMITTED FOR THE BJ'S RESTAURANT.
 C. THE WALL SIGNS REQUIRE PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2013-08-16 16:24:49IN REVIEW