Plan Review Details - Permit 13070787
Plan Review Stops For Permit 13070787
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-09-18 Cont ID  
Sent By shill Date 2013-09-18 Time 20:14 Rev Time 0.00
Received By shill Date 2013-09-18 Time 20:13 Sent To  
Notes
2013-09-18 20:19:53****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
 ****REVISION REQUIRED BEFORE FIRST INSPECTION****
  
  
 1. SEE PREVIOUS LIST REGARDING DISCREPANCIES IN
 BUILDING TYPE ON SHEET 1 OF PLAN. THE PLANS WERE
 REVISED TO STATE A VA BUILDING TYPE AND ALSO TYPE IIIA,
 BOTH WHICH REQUIRE A FIRE RATING FOR STRUCTURAL
 ELEMENTS. EITHER REVISE BUILDING TYPE OR PROVIDE
 DETAILS AS TO HOW THE FIRE RATED STRUCTURAL ELEMENTS
 ARE OR WILL BE PROTECTED FBC TABLE 601. **REVISE SHEET
 1**
  
 2. SEE PREVIOUS LISTS REGARDING PRODUCT APPROVALS
 REQUIRED TO BE REVIEWED BY DESIGNER OF RECORD. SUBMIT
 PRODUCT APPROVALS ***AS A REVISION*** FOR ALL
 COMPONENTS & CLADDING, ***REVIEWED BY DESIGNER OF
 RECORD*** (SHOP DRAWING REVIEW STAMP OR LETTER) PRIOR
 TO INSTALLATION. ALL WERE SUBMITTED BUT NONE WERE
 REVIEWED BY DESIGNER OF RECORD AS REQUIRED.
 PRODUCT APPROVALS REQUIRED: ROOF, DOORS, SINGLE HUNG
 WINDOWS, STOREFRONT, MECHANICAL STAND
  
 3. ROOF INFORMATION REQUESTED NOT PROVIDED. SEE ITEM 2,
 REVIEW BY DOR REQUIRED. SUBMIT ENGINEERING FOR ROOFING
 PERMIT 13090352 AS A REVISION
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-09-10 Cont ID  
Sent By shill Date 2013-09-10 Time 15:50 Rev Time 0.00
Received By shill Date 2013-08-29 Time 16:33 Sent To  
Notes
2013-08-31 14:10:05****CORRECTIONS****
  
 WHEN RESUBMITTING, PLEASE PROVIDE NEW SHEETS 5 AND 6 IN
 ADDITION TO SHEETS WHICH HAVE CHANGED AS WELL AS
 PRODUCT APPROVALS SUBMITTED FIRST REVIEW
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE PREVIOUS LIST REGARDING DISCREPANCIES IN
 BUILDING TYPE ON SHEET 1 OF PLAN. THE PLANS WERE
 REVISED TO STATE A VA BUILDING TYPE AND ALSO TYPE IIIA,
 BOTH WHICH REQUIRE A FIRE RATING FOR STRUCTURAL
 ELEMENTS. EITHER REVISE BUILDING TYPE OR PROVIDE
 DETAILS AS TO HOW THE FIRE RATED STRUCTURAL ELEMENTS
 ARE OR WILL BE PROTECTED FBC TABLE 601.
  
 2. SEE PREVIOUS LIST REGARDING PRODUCT APPROVALS
 REQUIRED TO BE REVIEWED BY DESIGNER OF RECORD. SUBMIT
 PRODUCT APPROVALS ***AS A REVISION*** FOR ALL
 COMPONENTS & CLADDING, ***REVIEWED BY DESIGNER OF
 RECORD*** (SHOP DRAWING REVIEW STAMP OR LETTER) PRIOR
 TO INSTALLATION.
  
 3. ROOF INFORMATION REQUESTED NOT PROVIDED. SEE ITEM 2,
 REVIEW BY DOR REQUIRED. SEE PREVIOUS LIST REGARDING
 INFORMATION REQUIRED FOR ROOF PERMITS (INDICATE
 ASSEMBLY PROPOSED AND PROVIDE RAS117 CALCULATIONS IF
 REQUIRED, PREPARED BY A DESIGN PROFESSIONAL, IF
 REQUIRED). SUBMIT AS A REVISION.
  
 4. SEPARATE PLANS AND PERMIT REQUIRED FOR MECHANICAL.
 NO MECHANICAL PLANS SUBMITTED.
  
 5. SEPARATE ROOF PERMIT REQUIRED. THE ROOF SUB PERMIT
 CANNOT BE ISSUED UNTIL THE ROOFING INFORMATION IS
 SUBMITTED/REVIEWED (REVISION).
  
 6. WHEN RESUBMITTING, PLEASE PROVIDE SHEETS 5 AND 6 IN
 ADDITION TO ANY OTHER SHEETS WHICH HAVE CHANGED AS WELL
 AS PRODUCT APPROVALS SUBMITTED FIRST REVIEW (UNABLE TO
 LOCATE AT THIS TIME).
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-24 Cont ID  
Sent By jwitmer Date 2013-07-24 Time 11:40 Rev Time 0.00
Received By jwitmer Date 2013-07-24 Time 07:30 Sent To  
Notes
2013-07-24 08:58:30BUILDING PLAN REVIEW
 PERMIT: 13070787
 ADD: 2003 N TAMARIND AVE # SUITE A & B
 CONT: NYC CONSTRUCTION
 TEL: (561) 283-3333
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 24/ 2013
 ACTION: DENIED
  
 1) PLEASE PROVIDE ADDITIONAL INFORMATION TO CLEAR UP
 DISCREPANCIES IN THE PLANS. 2010 WPB ADMINISTRATIVE
 CODE CHAPTER 1 2010 FBC. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
 1A) THE COVERSHEET INDICATES THE TYPE OF OCCUPANCY AS A
 BUSINESS OCCUPANCY BUT UNDER THE HEADING DESIGN
 CRITERIA THE PLANS INDICATE A R-3 OCCUPANCY?
 1B) THE COVERSHEET ALSO INDICATES THIS BUILDING TO BE A
 BUILDING TYPE V(A) BUT THERE IS NO DETAILED INFORMATION
 AS TO COMPLIANCE WITH 2010 FBC-B TABLE 601: 1 HR FIRE
 RATING ON PRIMARY STRUCTURAL MEMBERS, BEARING WALLS,
 FLOOR CONSTRUCTION, & ROOF CONSTRUCTION AND SECONDARY
 MEMBRS.
  
 1C) WIND DESIGN CRITERIA, PLEASE REVIEW 2010 FBC-B WIND
 CONTOUR MAP RISK CATEGORY II BUILDINGS, THE 170 MPH
 CONTOUR LINE IS THROUGH THE INTERCOASTAL AND THE 160
 MPH CONTOUR LINE IS APPROXIMATELY 15 MILES WEST OF
 CITIES FURTHEST MOST COMMUNITY IBIS, IBIS WHEN INTER
 PLATING BETWEEN CONTOUR LINES IS A 165 MPH WIND ZONE.
 SEE PALM BEACH COUNTY CONTOUR MAPS AND CONTOUR LINES.
 FIGURE 1609A.
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. NO PRODUCT APPROVALS FOR
 STOREFRONT DOORS WAS SUBMITTED.
 (B) WINDOWS SINGLE HUNG NOT REVIEWED BY THE DESIGNER OF
 RECORD
 (C) STOREFRONTS, , NOT REVIEWED BY THE DESIGNER OF
 RECORD
 (D) ROOFING PRODUCTS AND ASSEMBLIES DISCREPANCIES SEE
 COMMENT BELOW, NOT REVIEWED BY THE DESIGNER OF RECORD.
 (E) PRE-ENGINEERED A/C STANDS NO PRODUCT APPROVALS
 SUBMITTED FOR ROOF TOP UNITS
  
 4) SHEET # 3 THE ROOF RAFTER REPAIR INDICATES A FLAT
 ROOF WITH A PARPET, PARAPET HEIGHT NOT PROVIDED, DOES
 IT SURROUND THE TOTAL BUILDING? THE PRODUCT APPROVAL
 SUBMITTED IS FOR A FLAT DECK, NOA 07-1219.09 NO
 SUB-SYSTEM WAS HIGHLIGHTED INDICATING WHICH SYSTEM IS
 TO BE INSTALLED. THE ONLY NON-INSULATED SUB-SYSTEM
 STARTS ON SHEET 17 CONTINUES TO 18, PLEASE IDENTIFY
 WHICH OF THE OPTIONS ARE TO BE INSTALLED NOTE THE
 MAXIMUM DESIGN PRESSURES AND GENERAL LIMITATION # 7
 WHICH ALLOWS FOR ENHANCED FASTENING. RAS 117
 CALCULATIONS BY EITHER A ARCHITECT OR ENGINEER.
  
  
  
 5A) THE VALUE FOR THE BUILDING PERMIT APPEARS TO BE
 LOW, VALUES FOR THE SCOPE OF WORK UNDER THE NOVA
 ENGINEERING WORK SHEETS ARE BLANK. WILL CONTACT
 THE HOUSING & COMMUNITY DEVELOPMENT PROGRAM COORDINATOR
 MS. MCCRAY FOR FURTHER INFORMATION, (1266) 822-1250.
  
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 5B) THE VALUE OF THE ROOFING PERMIT IS ALSO LOW, VALUE
 STATED IS $4,500.00. THE MASHAL SWIFT PRICE, AVERAGE
 VALUE IS $5.30 PER SQ FT, THIS ROOF SQ FT IS 1900 SQ FT
 WHICH EQUALS A VALUE OF $10,070 THE PERMIT WLL BE
 UPDATED TO REFLECT THIS VALUE.
  
 6) SHEET 2 PLEASE PROVIDE A DETAIL OF THE NEW
 RESTROOMS, SHEET 3 DETAIL MISSING FL ACC CODE 604.3.2
 OCER LAP, 2010 EXISTING BUILDING CODE 706.1 A BUILDING,
 FACILITY, OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2010 FL ACCESS CODE 604.3.2 OVERLAP.
 THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE
 PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB
 BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT
 HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE
 AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE
 TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL
 BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
 SEE FIGURE 604.3.2 & FIGURE 604.8.1.6, THE MINIMUM WALL
 LENGTH OF 7'-1" IS REQUIRED.
  
 7) SHEET 2 INDICATES THE REMOVAL OF WINDOW WALL A/C
 UNITS, SHEET 6 INDICATES NEW CENTRAL A/C UNITS AND AIR
 CONDITIONING BEING INTRODUCED. ALSO THE NOVA WORK
 SHEETS INDICATE REMOVAL AND REPLACEMENT OF ALL
 CEILINGS, HOW WILL CODE COMPLIANCE BE MADE FOR EXISTING
 BUILDING CODE 711.1 MINIMUM REQUIREMENTS. ALTERATIONS
 SUBJECT TO THIS CHAPTER SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, ENERGY
 CONSERVATION. PLEASE PROVIDE ENERGY CALCULATIONS.
  
 8) SHEET 2 INDICATES A EXISTING ONE-HOUR TENANT
 SEPERATION WALL, (NON-SPRINKLERED) ASSUMED TO GO
 THROUGH TO THE UNDER NEATH SIDE OF THE ROOF DECK. PLANS
 DO NOT INDICATE THE FIRE RATING OFTHE PLANS FOR THE
 DOOR, PLEASE REVIEW OPENING PROTECTIVES 2010 FBC-B
 TABLE 715.4 REQUIRING A 3/4 HOUR FIRE RATING.
  
 9) SHEET A3 INDICATES A NEW EXTERIOR STAIR, FOOTER,
 HAND RAIL & GAURD RAIL BY OTHERS ,SHOP DRAWINGS TO BE
 SUBMITED. PLEASE PROVIDE ENOUGH INFORMATION ON THE
 STAIRS SHOWING CODE COMPLIANCE. PROVIDE COMPLIANCE FOR
 2010 FBC-B LIVE LOADS TABLE 1607.1, 1607.7.1,
 1607.7.1.1 & 1607.7.1.2.
  
 10) SHEET 4 INDICATES A DROPPED CEILING PLEASE INDICATE
 HEIGHT OF THE DROP CEILING AND COMPLIANCE WITH 2010
 FBC-B 1208.2. WILL THE A/C DUCTS BE IN THE ATTIC OR
 UNDER THE DRYWALL CEILING? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-09-12 Cont ID  
Sent By dharvey Date 2013-09-12 Time 16:01 Rev Time 0.00
Received By dharvey Date 2013-09-12 Time 16:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-08-29 Cont ID  
Sent By dharvey Date 2013-08-29 Time 15:30 Rev Time 0.00
Received By dharvey Date 2013-09-12 Time 15:15 Sent To  
Notes
2013-08-29 15:33:239/12/13 DH
 PROVIDED PLANS BY S HILL FOR REVIEW
 NOTES PLACED ON PLANS AND SIGNED
  
  
  
 8-29-13
 ADD SERVICE RISER DIAGRAM PER NEC 215.5
 ADD PANEL SCHEDULE PER NEC 408.4
 ARE THERE ANY ELECTRICAL FIXTURES OR DEVICES? PLEASE
 SHOW THEM WITH CIRCUIRTY ON DRAWINGS
 ADD A DEMO NOTE TO REMOVE ALL ABANDONED ELECTRIC BACK
 TO ITS SOURCE. (NOTHING LEFT IN CEILING)
 VB
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-08-27 Cont ID  
Sent By wjolin Date 2013-08-27 Time 14:40 Rev Time 0.00
Received By wjolin Date 2013-08-27 Time 14:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-09-18 Cont ID  
Sent By shill Date 2013-09-18 Time 20:59 Rev Time 0.00
Received By shill Date 2013-09-12 Time 15:31 Sent To  
Notes
2013-09-14 07:25:289/14 TO RB DESK
  
2013-09-13 08:01:319/13 TO RM DESK
  
2013-09-12 15:31:30TO DOUG HARVEY'S DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-29 Cont ID  
Sent By jwitmer Date 2013-08-29 Time 07:17 Rev Time 0.00
Received By jwitmer Date 2013-07-22 Time 16:08 Sent To  
Notes
2013-08-22 08:37:51B20
  
 ADDED NEW SHEETS ADDRESSING BUILDING AND PLUMBING
 COMMENTS, OK PER RB
  
2013-07-22 16:08:53SENT TO B20 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-09-18 Cont ID  
Sent By rregueir Date 2013-09-18 Time 14:55 Rev Time 0.00
Received By rregueir Date 2013-09-18 Time 14:54 Sent To  
Notes
2013-09-18 14:55:43**PROVISO**
  
 NEED SIGNED AND SEALED PLANS PRIOR TO INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-08-28 Cont ID  
Sent By hmoser Date 2013-08-28 Time 08:19 Rev Time 0.00
Received By hmoser Date 2013-08-28 Time 07:40 Sent To  
Notes
2013-08-28 08:19:02NO MECHANICAL PLANS
 HAROLD MOSER
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-08-28 Cont ID  
Sent By lwagner Date 2013-08-28 Time 14:21 Rev Time 0.00
Received By lwagner Date 2013-08-28 Time 14:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-07-25 Cont ID  
Sent By lwagner Date 2013-07-25 Time 13:45 Rev Time 0.00
Received By lwagner Date 2013-07-25 Time 09:09 Sent To  
Notes
2013-07-25 13:44:46FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. PLEASE SEE BUILDING REVIEW NOTES FOR 7'-1" MINIMUM
 REQUIRED WIDTH IN THE TOILET ROOM.
 FBC ACCESSIBILITY
 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
 604.3.2 OVERLAP.
 THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE
 PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB
 BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT
 HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE
 AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE
 TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL
 BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
  
 2. WHILE DRINKING FOUNTAINS ARE NOT REQUIRED FOR 15 OR
 LESS OCCUPANTS, FBC PLUMBING TABLE 403.1(E, F), IF
 DRINKING FOUNTAINS ARE PROVIDED THE ACCESSIBILITY CODE
 REQUIRES TWO (HI/ LOW).
 FBC ACCESSIBILITY 2010 211.1 GENERAL.
 WHERE DRINKING FOUNTAINS ARE PROVIDED ON AN EXTERIOR
 SITE, ON A FLOOR, OR WITHIN A SECURED AREA THEY SHALL
 BE PROVIDED IN ACCORDANCE WITH 211.
 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2013-07-30 Cont ID  
Sent By ajones Date 2013-07-30 Time 13:44 Rev Time 0.00
Received By ajones Date 2013-07-30 Time 13:44 Sent To  
Notes
***NONE***