Plan Review Details - Permit 13070786
Plan Review Stops For Permit 13070786
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-24 Cont ID  
Sent By jwitmer Date 2013-07-24 Time 11:42 Rev Time 0.00
Received By jwitmer Date 2013-07-24 Time 11:42 Sent To  
Notes
2013-07-24 11:43:32ROOFING COMENTS INCLUDED IN BLDG REVIEW UNDER PERMIT #
 13070719, LOW VALUE CALCULATED VALUE IS $10,700.00

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2013-07-24 Cont ID  
Sent By wjolin Date 2013-07-24 Time 12:39 Rev Time 0.00
Received By wjolin Date 2013-07-24 Time 12:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-07-26 Cont ID  
Sent By hmoser Date 2013-07-26 Time 08:17 Rev Time 0.00
Received By hmoser Date 2013-07-25 Time 15:13 Sent To  
Notes
2013-07-26 08:17:38PLANS DENIED
 1) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROL'S.
 SHOW THE LOCATION AND THE SIZE OF THE FRESH AIR DUCT
 ON THE PLANS 2010 FLORIDA ENERGY CODE.
 2) DOORS ON AIR HANDLER CLOSET SHOW WOOD ON THE
 DOOR SCHEDULE. REFER TO SECTION 602.2.1 MATERIALS
 WITHIN
 PLENUM'S 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  