Plan Review Details - Permit 13070669
Plan Review Stops For Permit 13070669
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-07-20 Cont ID  
Sent By jwitmer Date 2013-07-20 Time 09:46 Rev Time 0.00
Received By jwitmer Date 2013-07-20 Time 09:05 Sent To  
Notes
2013-07-20 09:46:21BUILDING PLAN REVIEW
 PERMIT: 13070669
 ADD: 400 N FLAGLER # 903
 CONT: WHITTMAN BUILDING CORP
 TEL: (561)366-8187
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 7/20/2013
 ACTION:BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION! THIS PLAN HAS BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND THE ASSESSMENT OF
 RE-INSPECTION FEE(S). REVISIONS REQUIRE ADDITIONAL
 REVIEWS WITH ASSOCIATED FEES.
  
 BUILDING TYPE I & II
  
 1A) FLOOR AREA 1-7 ONLY, NOT AREA 1-3. FBC-B 2010
 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES
 BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A
 PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE
 AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE
 WITH ASTM E 492.
  
 1B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING FLOOR
 AREA 1-7 ONLY FLOOR INSULATION PLACED BETWEEN TWO
 LAYERS OF NONCOMBUSTIBLE MATERIALS WITHOUT AN
 INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 100.
  
 1C) FBC-B 2010 603.2 EXCEPTION 2 WOOD FLOORS, FLOOR
 AREA 1-1. INSULATION INSTALLED BETWEEN A FINISHED FLOOR
 AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 FBC-B 2010
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-08-05 Cont ID  
Sent By dharvey Date 2013-08-05 Time 15:53 Rev Time 0.00
Received By dharvey Date 2013-08-05 Time 15:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-07-24 Cont ID  
Sent By wjolin Date 2013-07-24 Time 11:38 Rev Time 0.00
Received By wjolin Date 2013-07-24 Time 11:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-05 Cont ID  
Sent By dharvey Date 2013-08-05 Time 15:54 Rev Time 0.00
Received By dharvey Date 2013-07-18 Time 13:36 Sent To  
Notes
2013-08-05 15:54:28TO S HILL
2013-07-18 13:45:26B10

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-07-20 Cont ID  
Sent By hmoser Date 2013-07-20 Time 11:03 Rev Time 0.00
Received By hmoser Date 2013-07-20 Time 10:26 Sent To  
Notes
2013-07-20 11:03:52PASS PROVISO
 REFER TO SECTION 601.5 CONTAMINATION PREVENTION
 2010 FBC (M) .
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-07-23 Cont ID  
Sent By lwagner Date 2013-07-23 Time 13:48 Rev Time 0.00
Received By lwagner Date 2013-07-22 Time 15:47 Sent To  
Notes
***NONE***