Plan Review Details - Permit 13070649
Plan Review Stops For Permit 13070649
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-10-29 Cont ID  
Sent By albarran Date 2013-10-29 Time 10:16 Rev Time 0.00
Received By albarran Date 2013-10-29 Time 09:39 Sent To I
Notes
2013-10-29 10:16:38SENT TO SH DESK
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-07-29 Cont ID  
Sent By dharvey Date 2013-07-29 Time 13:46 Rev Time 0.00
Received By dharvey Date 2013-07-29 Time 11:14 Sent To  
Notes
2013-07-29 13:46:14ADDITIONAL HORNS AND/OR STROBES ARE REQUIRED TO PROVIDE
 NOTIFICATION DEVICES IN EACH TENNANT SPACE. PROVIDE
 STROBES IN BATHROOMS. SHOW INTERCONNECTION OF AIR
 HANDLER SMOKE DETECTOR AND/OR UNIT SHUTDOWN. PLANS SHOW
 2007 NEC?
  
 PLACED IN DENIED UNDER "W" DH

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-10-18 Cont ID  
Sent By scaldero Date 2013-10-18 Time 13:06 Rev Time 0.00
Received By scaldero Date 2013-10-18 Time 13:06 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-07-24 Cont ID  
Sent By scaldero Date 2013-07-24 Time 14:38 Rev Time 0.00
Received By scaldero Date 2013-07-24 Time 14:38 Sent To E
Notes
2013-07-24 14:41:35FIRE ALARM
  
 1781 PALM BEACH LAKES BLVD.
 FIRE ALARM - PALM BEACH MALL BUILDING J-9
 PERMIT #130700649
 MASTER #12110064
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS IN THE TITLE BLOCK SHOULD REFLECT ONLY
 1781, NOT 1741-1801. ALSO, BUILDING SHOULD ONLY BE
 IDENTIFIED AS J9.
  
 NO VISUAL NOTIFICATION PROVIDED IN RESTROOMS, EXCEPT
 FOR TENANT SPACE W249. DEVICES NEEDED IN ALL RESTROOMS.
  
 NO NOTIFICATION APPLIANCES LOCATED IN TENANT SPACES
 W209, W213, AND W215.
  
 NOTIFICATION APPLIANCES IN THE FOLLOWING TENANT SPACES
 WILL NOT PROVIDE ADEQUATE COVERAGE FOR ENTIRE SPACE:
 W203, W207, W208, W217, W218, W219, W221, W223, W225,
 W227, W229, W231, W233, W235, W237, W241, W243, W245,
 W247, AND W249.
  
 NOTIFICATION APPLIANCES IN THE CORRIDORS WILL NOT
 PROVIDE ADEQUATE COVERAGE FOR TOTAL LENGTH OF CORRIDOR.
  
 INDICATE ELEVATION FOR CEILING MOUNTED DEVICES.
  
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By jwitmer Date   Time   Rev Time 0.00
Received By jwitmer Date 2013-10-16 Time 18:59 Sent To FIRE
Notes
2013-10-16 19:00:47INCOMING SENT TO FIRE BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-16 Cont ID  
Sent By jwitmer Date 2013-07-29 Time 18:58 Rev Time 0.00
Received By jwitmer Date 2013-07-18 Time 08:08 Sent To  
Notes
2013-07-18 08:08:20ROUTED TO FIRE