Plan Review Details - Permit 13070649
| Plan Review Stops For Permit 13070649 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2013-10-29 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2013-10-29 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2013-10-29 |
Time |
09:39 |
Sent To |
I |
|
| Notes |
| 2013-10-29 10:16:38 | SENT TO SH DESK | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-07-29 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-07-29 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-07-29 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2013-07-29 13:46:14 | ADDITIONAL HORNS AND/OR STROBES ARE REQUIRED TO PROVIDE | | | NOTIFICATION DEVICES IN EACH TENNANT SPACE. PROVIDE | | | STROBES IN BATHROOMS. SHOW INTERCONNECTION OF AIR | | | HANDLER SMOKE DETECTOR AND/OR UNIT SHUTDOWN. PLANS SHOW | | | 2007 NEC? | | | | | | PLACED IN DENIED UNDER "W" DH |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2013-10-18 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2013-10-18 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2013-10-18 |
Time |
13:06 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2013-07-24 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2013-07-24 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2013-07-24 |
Time |
14:38 |
Sent To |
E |
|
| Notes |
| 2013-07-24 14:41:35 | FIRE ALARM | | | | | | 1781 PALM BEACH LAKES BLVD. | | | FIRE ALARM - PALM BEACH MALL BUILDING J-9 | | | PERMIT #130700649 | | | MASTER #12110064 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE ADDRESS IN THE TITLE BLOCK SHOULD REFLECT ONLY | | | 1781, NOT 1741-1801. ALSO, BUILDING SHOULD ONLY BE | | | IDENTIFIED AS J9. | | | | | | NO VISUAL NOTIFICATION PROVIDED IN RESTROOMS, EXCEPT | | | FOR TENANT SPACE W249. DEVICES NEEDED IN ALL RESTROOMS. | | | | | | NO NOTIFICATION APPLIANCES LOCATED IN TENANT SPACES | | | W209, W213, AND W215. | | | | | | NOTIFICATION APPLIANCES IN THE FOLLOWING TENANT SPACES | | | WILL NOT PROVIDE ADEQUATE COVERAGE FOR ENTIRE SPACE: | | | W203, W207, W208, W217, W218, W219, W221, W223, W225, | | | W227, W229, W231, W233, W235, W237, W241, W243, W245, | | | W247, AND W249. | | | | | | NOTIFICATION APPLIANCES IN THE CORRIDORS WILL NOT | | | PROVIDE ADEQUATE COVERAGE FOR TOTAL LENGTH OF CORRIDOR. | | | | | | INDICATE ELEVATION FOR CEILING MOUNTED DEVICES. | | | | | | | | | SUE ELLEN CALDERON | | | FIRE INSPECTOR & INVESTIGATOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-10-16 |
Time |
18:59 |
Sent To |
FIRE |
|
| Notes |
| 2013-10-16 19:00:47 | INCOMING SENT TO FIRE BOX. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-10-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-07-29 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-07-18 |
Time |
08:08 |
Sent To |
|
|
| Notes |
| 2013-07-18 08:08:20 | ROUTED TO FIRE |
|
|
|