Plan Review Details - Permit 13070641
Plan Review Stops For Permit 13070641
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-08-17 Cont ID  
Sent By jwitmer Date 2013-08-17 Time 13:34 Rev Time 0.00
Received By jwitmer Date 2013-08-17 Time 13:04 Sent To  
Notes
2013-08-17 13:34:15BUILDING PROVISO:
  
 1) 2010 FL ACCESSIBILITY CODE AT DRINKING FOUNTAIN THE
 UPPER DRINKING FOUNTAIN WILL TO COMPLY WITH
 2010 FL ACCESSIBILITY CODE 307.2 OBJECTS WITH LEADING
 EDGES MORE THAN 27 INCHES (685 MM) AND NOT MORE THAN 80
 INCHES (2030 MM) ABOVE THE FINISH FLOOR OR GROUND SHALL
 PROTRUDE 4 INCHES (100 MM) MAXIMUM HORIZONTALLY INTO
 THE CIRCULATION PATH.
  
 ADVISORY 307.2 PROTRUSION LIMITS.
 WHEN A CANE IS USED AND THE ELEMENT IS IN THE
 DETECTABLE RANGE, IT GIVES A PERSON SUFFICIENT TIME TO
 DETECT THE ELEMENT WITH THE CANE BEFORE THERE IS BODY
 CONTACT. ELEMENTS LOCATED ON CIRCULATION PATHS,
 INCLUDING OPERABLE ELEMENTS, MUST COMPLY WITH
 REQUIREMENTS FOR PROTRUDING OBJECTS.
  
 2) PB OUTLET MALLS:
 BUILDING PROVISO:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-09-07 Cont ID  
Sent By dharvey Date 2013-09-07 Time 14:07 Rev Time 0.00
Received By dharvey Date 2013-09-07 Time 13:47 Sent To  
Notes
2013-09-07 14:08:05WITH PROVISOS

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-07-25 Cont ID  
Sent By scaldero Date 2013-07-25 Time 15:43 Rev Time 0.00
Received By scaldero Date 2013-07-25 Time 15:43 Sent To  
Notes
2013-07-25 15:44:12PERMIT #13070641
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2013-09-10 Time   Rev Time 0.00
Received By rregueir Date 2013-07-26 Time 14:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-09-10 Cont ID  
Sent By rregueir Date 2013-09-10 Time 16:14 Rev Time 0.00
Received By rregueir Date 2013-09-10 Time 16:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-08-15 Cont ID  
Sent By lwagner Date 2013-08-15 Time 15:37 Rev Time 0.00
Received By lwagner Date 2013-08-15 Time 15:27 Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 2 Status N Date 2013-10-08 Cont ID  
Sent By rregueir Date 2013-10-08 Time 13:28 Rev Time 0.00
Received By rregueir Date 2013-10-08 Time 13:28 Sent To  
Notes
2013-10-08 13:29:18NOT REQUIRED PER ROBERT BROWN.

Review Stop POLICE POLICE
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2013-08-22 Time   Rev Time 0.00
Received By ktucker Date 2013-08-22 Time 15:08 Sent To  
Notes
2013-08-22 15:10:21(1) A FULLY FUNCTIONING AND OPERATIONAL CCTV SYSTEM
 CAPABLE OF RECORDING AND RETRIEVING ON SITE, AN
 IDENTIFIABLE IMAGE TO ASSIST IN OFFENDER IDENTIFICATION
 AND APPREHENSION.
 (2) CAMERA COVERAGE: (A) DOOR THAT LEADS TO THE BACK OF
 HOUSE (B) HALLWAY THAT LEADS TO REAR EXIT (C) SALES
 FLOOR (D) REGISTERS (LOW FOR FACIAL RECOGNITION) (E)
 FRONT ENTRY (F) HALLWAY TO THE PUBLIC RESTROOM
 (3) EXITING REAR DOOR NEEDS ALARM, SENSOR AND VIEW
 FINDER
 (4) DOOR THAT LEADS TO THE BACK OF HOUSE NEEDS SENSORS,
 ACCESS CONTROL AND VIEW FINDER
 (5) SILENT PANIC ALARM UNDER EACH REGISTER, ONE IN THE
 BACK OF HOUSE WORK AREA
 (6) A SECURED DROP SAFE OR CASH MANAGEMENT DEVICE FOR
 RESTRICTED ACCESS TO MONEY/CASH RECEIPTS AT THE
 REGISTER AND A SECURED DROP SAFE OR CASH MANAGEMENT
 DEVICE IN THE STORAGE AREA.
 (7) SECURE THE REGISTER TO THE COUNTER
 (8) HEIGHT MARKERS AT THE ENTRANCE AND EXIT.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-10-08 Cont ID  
Sent By rregueir Date 2013-10-08 Time 13:25 Rev Time 0.00
Received By rregueir Date 2013-10-08 Time 13:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-09-05 Cont ID  
Sent By eschnide Date 2013-09-05 Time 15:01 Rev Time 1.00
Received By eschneid Date 2013-09-05 Time 15:01 Sent To  
Notes
2013-09-05 15:02:19SIGNS REQUIRE SEPARATE PERMITS WITH PLANS.
2013-08-21 15:31:508/21/13