| 2013-09-30 16:07:22 | BUILDING PLAN REVIEW |
| | PERMIT: 13070610 |
| | ADD: 720 S SAPODILLA AV- ROOFTOP |
| | CONT: HAYDEN PROFESSIONAL SERVICES |
| | TEL: (772)781-1512 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE:9/ 30/2012 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. PLANS BEING SUBMITTED FOR CITY REVIEW |
| | REQUIRES CITY PLACE STAMP OF REVIEW AND APPROVAL. |
| | |
| | 2A) 3RD REVIEW. SUBMITTED IS A PRE-MANUFACTURED |
| | BUILDING, THIS STATE APPROVED PLAN, HAS VARIOUS OPTIONS |
| | AS TO VARIOUS OPTIONS TO 1 OR 2 HOUR FIRE RATINGS, |
| | PLEASE CIRCLE WHICH OPTION WILL BE EXERCISED IN |
| | BUILDING THIS UNIT. |
| | THE ISSUE IS THIS MODULAR BUILDING IS GOING TO BE |
| | LOCATED ON TOP OF AN EXISTING 5 STORY III-A FULLY |
| | SPRINKLERED BUILDING. THE STATE APPROVED PLAN INDICATES |
| | THIS TO BE A BUILDING TYPE V-B BUT WITH THE VARIOUS |
| | OPTIONS IT CAN BE UPGRADED TO THE REQUIREMENTS OF A |
| | BUILDING TYPE IIIA. |
| | THE ORIGINAL BUILDING BEING BUILT AS A MIXED USE |
| | MERCANTILE 1ST FLOOR AND R2 THE SECOND THRU 5TH FLOOR |
| | WHICH ALLOWED FOR 4 STORIES, IT IS FULLY SPRINKLERED |
| | WITH A FULL NFPA 13 SPRINKLER THAT GACE THEM A ONE |
| | STORY INCREASE, THE NEW MODULAR STRUCTURE WOULD ALSO BE |
| | REQUIRED TO BE FULLY SPRINKLERED AND A MINIMUM BUILDING |
| | TYPE OF IIIA. |
| | |
| | 2B) WE WILL STILL NEED DOCUMENTATION THAT THIS BUILDING |
| | WILL BE EITHER FIRE SPRINKLERED OR MEET THE REQUIREMENT |
| | THROUGH AN ALTERNATE METHOD. |
| | |
| | 3) COMPLIED. 2ND REQUEST.SHEET S2 DETAIL # 5 INDICATES |
| | A SPECIAL PLATE DETAIL OF THE STEEL FRAME BEING |
| | ATTACHED TO THE EXISTING ELEVATOR SHAFT, BUT THERE IS |
| | NO INFORMATION AS TO HOW THE MANUFACTURED BUILDING IS |
| | TRANSFERRING THE LOADS TO THE STRUCTURAL STEEL |
| | FRAMEWORK, PART OF THE MAIN WIND FORCE RESISTING |
| | SYSTEM. 2010 1609.4.1. |
| | |
| | 4) 3RD REQUEST. SHEET C4 THE ELEVATIONS INDICATE WHAT |
| | APPEARS TO BE TRIM ON THE CONCEALMENT SCREENS AND |
| | ARCHITECTURAL DECOR TO MATCH THE BUILDING ON THE |
| | MODULAR BUILDING, PLEASE PROVIDE COMPLIANCE WITH: |
| | |
| | 2010 FBC-B 1406.2.2 TYPE I, II, III AND IV |
| | CONSTRUCTION. |
| | ON BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION, |
| | EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE |
| | CONSTRUCTED OF WOOD IN ACCORDANCE WITH SECTION 1405.5, |
| | OR OTHER EQUIVALENT COMBUSTIBLE MATERIAL, COMPLYING |
| | WITH THE FOLLOWING LIMITATIONS: (2.) COMBUSTIBLE |
| | ARCHITECTURAL TRIM SHALL BE LIMITED TO 40 FEET (12 192 |
| | MM) IN HEIGHT ABOVE GRADE. |
| | |
| | SUBMITTED REPORTS:STEALTHSKIN V (FR-ESSV) CONSEALMENT |
| | PANEL- OK MEETS THE REQUIREMENT |
| | GLASTEEL FIRE RETARDANT LINER PANEL -OK MEETS THE |
| | REQUIREMENT |
| | 3" HARDCOAT FOAM, 60 MIL THICKNESS FAILS TO MEET THE |
| | REQUIREMENT OF E84 COMPOSITE MATERIALS FLAME SPREAD NOT |
| | GREATER THAN 50, TESTED THE FLAME SPREAD |
| | WAS 140. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |