Plan Review Details - Permit 13070537
Plan Review Stops For Permit 13070537
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-02-26 Cont ID  
Sent By jwitmer Date 2014-02-26 Time 08:25 Rev Time 0.00
Received By jwitmer Date 2014-02-26 Time 08:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-12-30 Cont ID  
Sent By jwitmer Date 2013-12-30 Time 16:50 Rev Time 0.00
Received By jwitmer Date 2013-12-30 Time 16:35 Sent To  
Notes
2013-12-30 16:45:05BUILDING PLAN REVIEW
 PERMIT: 13070537 WATER TREATMENT BLDG.
 ADD: 6651 N JOG RD
 CONT: KBR
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: MONDAY DEC. 30/2013
 ACTION: DENIED
  
 1) LETTER FROM HEAVY STURTURES DESCRIBING WHICH PRODUCT
 APPROVALS THEY WERE GOING TO INSTALLDOES NOT MATCH THE
 PRODUCT APPROVAL COVER SHEETS SUBMITTED. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SUBMITTED PRODUCT APPROVAL MIAMI-DADE NOA 10-0901.20
 THE TECHNICAL DRAWINGS WERE NOT LOADED IN LANDSCAPE AND
 1/2 OF THE INFORMATION IS LEFT OFF THE PAGE (6-11)
 THE SUB-SYSTEM IS NOT IDENTIFIED BY CIRCLE OR COULD,
 PLEASE IDENTIFY WHICH SUB-SYSTEM IS BEING INSTALLED AND
 PRESSURES CAN BE VERIFIED.
  
 3) MIAMI-DADE NOA 10-0901.18 WAS NEVER SUBMITTED. NOTE
 THIS PRODUCT APPROVAL WAS NOT PART OF HEAVY STRUCTURES
 APPROVAL LETTER. FLORIDA APPROVAL # FL 12493-R1 BUTLER
 PANELWALL, THE SUB-SYSTEM IS NOT IDENTIFIED BY CIRCLE
 OR CLOUD. THE EVALUATION REPORT FOR LIMITATION & LOAD
 TABLES NOR THE INSTALATION INSTRUCTIONS WERE NOT
 UPLOADED. NO REVIEW CAN TAKE PLACE WITHOUT THIS
 INFORMATION.
  
 4) FLORIDA APPROVAL # FL 12760-R1 BUTLER PANEL WALL/
 LITE PANEL. THE SUB-SYSTEM IS NOT IDENTIFIED BY CIRCLE
 OR CLOUD. THE EVALUATION REPORT FOR LIMITATION & LOAD
 TABLES NOR THE INSTALATION INSTRUCTIONS WERE NOT
 UPLOADED. NO REVIEW CAN TAKE PLACE WITHOUT THIS
 INFORMATION.
  
 5) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. ROLL UP DOORS, SWING DOORS,
 ROOF HATCHES
 (C) WALLS: SIDING , WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES CURBS FOR ROOF TOP
 FANS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-25 Cont ID  
Sent By jwitmer Date 2013-08-25 Time 11:08 Rev Time 0.00
Received By jwitmer Date 2013-08-25 Time 10:08 Sent To  
Notes
2013-08-25 11:08:03BUILDING PLAN REVIEW
 PERMIT:13070531
 ADD: 6651 N JOG RD
 CONT: CDM
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUNDAY AUGUST 25/ 2013
 ACTION: DENIED
  
 1) CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE
 FLORIDA BUILDING CODE (FBC) 2010 CHAPTER 1
 ADMINISTRATION, 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL...
  
 107.3.5.1 COMMERCIAL BUILDINGS:
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503).
 STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS
 FOUNDATION
 STRUCTURAL CCOMPONNENTS
 BUILDING ENVELOPE
  
 SOILS CONDITIONS/ ANALYSIS. 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 MISSING FOUNDATION PLANS!!!!
  
 STRUCTURAL PLANS HAVE NOTE THAT HEAVY STRUCTURES ON
 ROOF FRAMING MEMBERS AND JOIST "NOT BY HEAVY
 STRUCTURES", WHAT ARE THE WALL AND FRAMING MEMBERS
 GOING TO BE AND WHO WILL THE ENGINEER OVER THE COMPLETE
 BUILDING SYSTEM, WHO WILL BE THE ENGINEER OF RECORD?
 SEE 700-S6-650 DETAIL ENCOA1, 700-S6-800 & 700-901-RP6
 ROOF BEAMS NOT BY HEAVY STRURETURES. THE STRUCTURAL
 COMPONENTS ARE THE MWFRS, MAIN WIND FORCE RESISTTING
 SYSTEM 2010 FBC-B 1609.6.4.1.
  
 THIS SAME DETAIL OF THE ROOF CURB FOR THE ROOF HATCH
 STILL INDICATES THE PURLINS CONTINUEING THROUGH, NOT BY
 HEAVY STRUCTURES.
  
 700 S6-900 THE HAND RAIL DETAIL PROVIDES NO INFORMATION
 FOR COMPLIANCE TO 1607.7.1 OR 1013.2 HEIGHT, 1013.3
 OPENINGS, & MISSING THE WHOLE LOCATION IN 1013.6.
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. ROLL UP DOORS, SWING DOORS,
 ROOF HATCHES
 (C) WALLS: SIDING , WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES CURBS FOR ROOF TOP
 FANS
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-09-07 Cont ID  
Sent By dharvey Date 2013-09-07 Time 10:48 Rev Time 0.00
Received By dharvey Date 2013-09-07 Time 10:43 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2013-09-12 Cont ID  
Sent By mgonzale Date 2013-09-12 Time   Rev Time 1.00
Received By mgonzale Date 2013-09-12 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-08-23 Cont ID  
Sent By wjolin Date 2013-08-23 Time 14:12 Rev Time 0.00
Received By wjolin Date 2013-08-23 Time 12:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-02-26 Cont ID  
Sent By jwitmer Date 2014-02-26 Time 08:25 Rev Time 0.00
Received By jwitmer Date 2014-02-18 Time 16:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-30 Cont ID  
Sent By jwitmer Date 2013-12-30 Time 16:50 Rev Time 0.00
Received By jwitmer Date 2013-12-06 Time 14:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-13 Cont ID  
Sent By shill Date 2013-09-12 Time 16:38 Rev Time 0.00
Received By shill Date 2013-07-22 Time 15:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-12-06 Cont ID  
Sent By rregueir Date 2013-12-06 Time 14:06 Rev Time 0.00
Received By rregueir Date 2013-12-06 Time 14:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-08-29 Cont ID  
Sent By rregueir Date 2013-08-29 Time 12:30 Rev Time 0.00
Received By rregueir Date 2013-08-29 Time 12:18 Sent To  
Notes
2013-08-29 12:30:00**PROVISO**
  
 1. PROVIDE ENGINEERED ATTACHMENT DETAIL FOR ROOF
 MOUNTED EXHAUST FANS FOR WIND RESISTANCE PER FBC-M
 301.12.
  
 2. PROVIDE PRODUCT APPROVAL DOCUMENTATION FOR ALL
 EXTERIOR LOUVERS PER FBC-M 301.12 AND FAC RULE 9N-3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-08-29 Cont ID  
Sent By lwagner Date 2013-08-29 Time 15:31 Rev Time 0.00
Received By lwagner Date 2013-08-29 Time 15:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2014-04-07 Cont ID  
Sent By skennedy Date 2014-04-07 Time 10:49 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2014-04-06 Cont ID  
Sent By skennedy Date 2014-04-06 Time 12:28 Rev Time 0.00
Received By skennedy Date 2014-03-28 Time 12:28 Sent To  
Notes
2014-04-06 12:29:27THE SIGNATURE DOCUMENT PROVIDED BY DAVID V. CONNOR
 (700-E4-910.PDF) REFERENCED FILE NO. IS NOT CONTAINED
 IN THE DRAWINGS. THE OTHER 39 OF 40 ARE OK.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 (561) 805-6710
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2013-12-18 Cont ID  
Sent By eschneid Date 2013-12-18 Time 22:10 Rev Time 0.50
Received By eschneid Date 2013-12-18 Time 22:10 Sent To  
Notes
2013-12-18 22:11:03PASSED
  
 THE BUILDING ELEVATIONS, SITE LOCATION AND FOOTPRINT
 HAVE CHANGED FROM THE ORIGINAL SITE PLAN APPROVAL. A
 REVISED SITE PLAN IS REQUIRED TO BE SUBMITTED TO THE
 PLANNING DIVISION SHOWING ALL OF THE AS-BUILT CHANGES
 PRIOR TO THE C.O.
  
2013-12-10 11:25:3512/10/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-09-05 Cont ID  
Sent By eschneid Date 2013-09-05 Time 13:57 Rev Time 0.75
Received By eschneid Date 2013-09-05 Time 13:57 Sent To  
Notes
2013-09-05 13:59:47FAILED
  
 1) A SITE PLAN SHOWING THE LOCATION OF THE WATER
 TREATMENT BUILDING IS REQUIRED WITH THE RESUBMITTAL.
  
 2) THE BUILDING ELEVATIONS HAVE CHANGED FROM THE
 ORIGINAL SITE PLAN APPROVAL. A REVISED SITE PLAN IS
 REQUIRED TO BE SUBMITTED TO THE PLANNING DIVISION
 SHOWING ALL OF THE AS-BUILT CHANGES.
2013-08-21 15:41:058/21/13


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved