Plan Review Details - Permit 13070532
Plan Review Stops For Permit 13070532
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-12-17 Cont ID  
Sent By jwitmer Date 2013-12-17 Time 09:07 Rev Time 0.00
Received By jwitmer Date 2013-12-17 Time 07:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-17 Cont ID  
Sent By jwitmer Date 2013-08-17 Time 14:57 Rev Time 0.00
Received By jwitmer Date 2013-08-17 Time 14:18 Sent To  
Notes
2013-08-17 14:24:31BUILDING PLAN REVIEW
 PERMIT: 13070532
 ADD: 6601 N JOG RD
 CONT: CDM
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: AUGUST 17/ 2013
 ACTION: DENIED
  
 1) THIS OVER-ALL PROJECT WAS CLASSIFIED AS A F3
 OCCUPANCY. WITHIN THE FLY ASH BUILDING THERE WILL BE BY
 PRODUCT OF ASH THAT WILL NOT BE FULLY BURNED AND CAN &
 WILL CREATE 2010 FBC-B CHAPTER 2 DEFINITIONS "
 COMBUSTIBLE DUST". FINELY DIVIDED SOLID MATERIAL THAT
 IS 420 MICRONS OR LESS IN DIAMETER AND WHICH, WHEN
 DISPERSED IN AIR IN THE PROPER PROPORTIONS, COULD BE
 IGNITED BY A FLAME, SPARK OR OTHER SOURCE OF IGNITION.
 COMBUSTIBLE DUST WILL PASS THROUGH A U.S. NO. 40
 STANDARD SIEVE.
  
 2010 FBC-B DEFINITIONS. DEFLAGRATION. AN EXOTHERMIC
 REACTION, SUCH AS THE EXTREMELY RAPID OXIDATION OF A
 FLAMMABLE DUST OR VAPOR IN AIR, IN WHICH THE REACTION
 PROGRESSES THROUGH THE UNBURNED MATERIAL AT A RATE LESS
 THAN THE VELOCITY OF SOUND. A DEFLAGRATION CAN HAVE AN
 EXPLOSIVE EFFECT.
  
 THE CONCERNS ARE THAT THE F-3 OCCUPANCY MAY FIT THE
 MAIN GENERATING BUILDING BUT THE FLY ASH BUILDING MAY
 IN EFFECT BE CLASSIFIED AS A HIGH HAZARD OCCUPANCY.
 2010 FBC-B TABLE 307.1(1) UNDER THE HEADING OF
 COMBUSTIBLE FIBERS LIST ALLOWABLE QUANITIES OF
 HAZARDOUS MATERIALS FOR STORAGE AND FOR CLOSED SYSTEMS,
 ALSO SEE FOOTNOTE A FOR THE USE OF CONTROL AREAS THAT
 MAY APPLY SEE SECTION 414.2.(1-5).
 PLEASE PROVIDE COMMENTS BACK SO BOTH BUILDING & FIRE
 AND REVIEW FOR CODE COMPLIANCE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-09-07 Cont ID  
Sent By dharvey Date 2013-09-07 Time 13:46 Rev Time 0.00
Received By dharvey Date 2013-09-07 Time 12:55 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2013-09-12 Cont ID  
Sent By mgonzale Date 2013-09-12 Time   Rev Time 1.00
Received By mgonzale Date 2013-09-12 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-12-10 Cont ID  
Sent By wjolin Date 2013-12-10 Time 14:34 Rev Time 0.00
Received By wjolin Date 2013-12-10 Time 14:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-08-10 Cont ID  
Sent By wjolin Date 2013-08-10 Time 19:35 Rev Time 0.00
Received By wjolin Date 2013-08-10 Time 16:53 Sent To  
Notes
2013-08-10 19:30:086610 NORTH JOG ROAD - ASH MANAGEMENT BUILDING
 PERMIT #13070532
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLEASE PROVIDE A WRITTEN NARRATIVE SUMMARIZING THE
 ENGINEERING CONTROLS (AUTOMATIC SPRINKLER SYSTEM,
 MAGNETIC SEPARATOR, DUST COLLECTORS, PRESSURE RELIEF
 PANELS, BONDING/GROUNDING, SPARK ARRESTORS, ABORT
 GATES, ETC.) THAT ARE BEING IMPLEMENTED TO MITIGATE
 PROBABILITY AND SEVERITY OF A COMBUSTIBLE DUST FIRE
 AND/OR EXPLOSION.
  
 DESIGN SHALL CONFORM TO THE REQUIREMENTS OF NFPA 1 -
 CHAPTER 40: DUST EXPLOSION AND FIRE PREVENTION. A FEW
 OF THE REQUIREMENTS HAVE BEEN INDICATED BELOW.
  
 PER NFPA 1 SECTION 40.1, EQUIPMENT, PROCESSES, AND
 OPERATIONS THAT INVOLVE THE MANUFACTURE, PROCESSING,
 BLENDING, REPACKAGING, OR HANDLING OF COMBUSTIBLE
 PARTICULATE SOLIDS OR COMBUSTIBLE DUSTS REGARDLESS OF
 CONCENTRATION OR PARTICLE SIZE SHALL BE INSTALLED AND
 MAINTAINED IN ACCORDANCE WITH THIS CHAPTER AND THE
 FOLLOWING STANDARDS AS APPLICABLE: NFPA 69 - STANDARD
 ON EXPLOSION PREVENTION SYSTEMS & NFPA 654 - STANDARD
 FOR THE PREVENTION OF FIRE AND DUST EXPLOSIONS FROM THE
 MANUFACTURING, PROCESSING, AND HANDLING OF COMBUSTIBLE
 PARTICULATE SOLIDS.
  
 PER NFPA 1 SECTION 40.3.2.1.2, REGULAR CLEANING
 FREQUENCIES SHALL BE ESTABLISHED FOR WALLS, FLOORS, AND
 HORIZONTAL SURFACES, SUCH AS EQUIPMENT, DUCTS, PIPES,
 HOODS, LEDGES, BEAMS, AND ABOVE SUSPENDED CEILINGS AND
 OTHER CONCEALED SURFACES, TO MINIMIZE DUST
 ACCUMULATIONS WITHIN OPERATING AREAS OF THE FACILITY.
  
 PER NFPA 1 SECTION 40.3.2.2, SURFACES SHALL BE CLEANED
 IN A MANNER THAT MINIMIZES THE GENERATION OF DUST
 CLOUDS. VIGOROUS SWEEPING OR BLOWING DOWN WITH STEAM OR
 COMPRESSED AIR PRODUCES DUST CLOUDS AND SHALL BE
 PERMITTED ONLY WHERE THE FOLLOWING REQUIREMENTS ARE
 MET:
 (1) AREA AND EQUIPMENT SHALL BE VACUUMED PRIOR TO
 BLOWDOWN.
 (2) ELECTRICAL EQUIPMENT NOT SUITABLE FOR CLASS II
 LOCATIONS AND OTHER SOURCES OF IGNITION SHALL BE SHUT
 DOWN OR REMOVED FROM THE AREA.
 (3) ONLY LOW-PRESSURE STEAM OR COMPRESSED AIR, NOT
 EXCEEDING A GAUGE PRESSURE OF 15 PSI (103 KPA), SHALL
 BE USED.
 (4) NO HOT SURFACES OR FLAMES CAPABLE OF IGNITING A
 DUST CLOUD OR LAYER SHALL EXIST IN THE AREA.
  
 PER NFPA 1 SECTION 40.3.2.3, VACUUM CLEANERS SHALL BE
 LISTED FOR USE IN CLASS II HAZARDOUS LOCATIONS OR SHALL
 BE A FIXED-PIPE SUCTION SYSTEM WITH REMOTELY LOCATED
 EXHAUSTER AND DUST COLLECTOR.
  
 PER NFPA 1 - 40.4.8 INDUSTRIAL TRUCKS. IN AREAS
 CONTAINING A COMBUSTIBLE DUST HAZARD, ONLY INDUSTRIAL
 TRUCKS LISTED OR APPROVED FOR THE ELECTRICAL
 CLASSIFICATION OF THE AREA, AS DETERMINED BY SECTION
 6.6 OF NFPA 654, SHALL BE USED IN ACCORDANCE WITH NFPA
 505, FIRE SAFETY STANDARD FOR POWERED INDUSTRIAL TRUCKS
 INCLUDING TYPE DESIGNATIONS, AREAS OF USE, CONVERSIONS,
 MAINTENANCE, AND OPERATIONS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 (561) 805-6730
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-17 Cont ID  
Sent By jwitmer Date 2013-12-17 Time 09:08 Rev Time 0.00
Received By jwitmer Date 2013-11-08 Time 12:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-13 Cont ID  
Sent By shill Date 2013-09-07 Time 16:42 Rev Time 0.00
Received By shill Date 2013-07-25 Time 12:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-08-29 Cont ID  
Sent By rregueir Date 2013-08-29 Time 12:18 Rev Time 0.00
Received By rregueir Date 2013-08-29 Time 11:27 Sent To  
Notes
2013-08-29 12:12:36**PROVISO**
  
 1. PROVIDE ENGINEERED ATTACHMENT DETAIL FOR EXTERIOR
 WALL MOUNTED EXHAUST FANS FOR WIND RESISTANCE PER FBC-M
 301.12.
  
 2. PROVIDE PRODUCT APPROVAL DOCUMENTATION FOR ALL
 EXTERIOR LOUVERS PER FBC-M 301.12 AND FAC RULE 9N-3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-08-13 Cont ID  
Sent By lwagner Date 2013-08-13 Time 15:53 Rev Time 0.00
Received By lwagner Date 2013-08-13 Time 15:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-11-23 Cont ID  
Sent By rregueir Date 2013-11-18 Time 12:29 Rev Time 0.00
Received By rregueir Date 2013-11-18 Time 12:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-08-21 Cont ID  
Sent By eschnide Date 2013-08-21 Time 20:42 Rev Time 1.00
Received By eschneid Date 2013-08-21 Time 20:42 Sent To  
Notes
2013-08-21 20:43:51PRIOR TO C.O., AS BUILT SITE PLAN AND ELEVATIONS SHALL
 BE SUBMITTED TO THE PLANNING DIVISION AS A MINOR SITE
 PLAN AMENDMENT.