Plan Review Details - Permit 13070453
| Plan Review Stops For Permit 13070453 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2013-07-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-07-22 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-07-22 |
Time |
11:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2013-07-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-07-19 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-07-19 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2013-07-19 12:05:52 | 2010 FBC | | | | | | 1) THE RAS 117 CALCULATIONS SPECIFY 1" THICK | | | ENERGYGUARD INSULATION AND A 1:3 SQFT FASTENER DENSITY. | | | THE MINIMUM THICKNESS FOR THIS FASTENER DENSITY IS | | | 1.3". PLEASE CORRECT. | | | | | | 2) IT APPEARS THAT THE ENGINEER USED A FASTENER SPACING | | | OF 1.3 SQFT PER FASTENER RATHER THAN 1 FASTENER PER 3 | | | SQFT. THEREBY SUBSTANTIALLY INCREASING THE NUMBER OF | | | FASTENERS PER BOARD. PLEASE REVIEW CALCULATIONS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-07-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-07-15 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-07-15 |
Time |
11:28 |
Sent To |
|
|
| Notes |
| 2013-07-15 12:22:19 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE. CITY | | | AMENDMENTS 107.2.1 | | | | | | 2) FROM THE GAF NOA NO. 09-0224.01, SPECIFY WHICH ONE | | | OF THE APPROVED SYSTEMS, FASTENING OPTION AND MAXIMUM | | | DESIGN PRESSURE WILL BE USED. FBC 1609.5.2 | | | | | | 3) THE DESIGN PRESSURES THAT ARE LISTED IN THE NOA ARE | | | TOO LOW FOR THE PERIMETER AND CORNER AREAS OF THE ROOF. | | | SUBMIT TWO COPIES OF SIGNED AND SEALED RAS 117 | | | CALCULATIONS FOR ENHANCED FASTENING REQUIREMENTS FOR | | | THE INSULATION AND BASE SHEET AT THE CORNER AND | | | PERIMETER AREAS AS SPECIFIED IN LIMITATION NUMBER 7 ON | | | PAGE 31. FBC 1609.5.2 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-07-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-07-22 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-07-22 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2013-07-20 14:39:53 | INCOMING SENT TO R. MCDOUGALS' DESK . JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-07-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-07-19 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-07-18 |
Time |
17:26 |
Sent To |
|
|
| Notes |
| 2013-07-18 17:26:49 | TO RM DESK | | | |
|
|
|