 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A MANUAL PULL STATION NEAR THE MAIN ENTRANCE
 SETS OF DOUBLE DOORS.
  
 THE MANUAL PULL STATION SYMBOL IN THE LEGEND IS
 DIFFERENT FROM THE SYMBOL USED ON THE PLANS.
  
 PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  