Plan Review Details - Permit 13070423
Plan Review Stops For Permit 13070423
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-07-14 Cont ID  
Sent By jwitmer Date 2013-07-14 Time 09:29 Rev Time 0.00
Received By jwitmer Date 2013-07-14 Time 08:16 Sent To  
Notes
2013-07-14 09:29:47BUILDING PLAN REVIEW
 PERMIT: 13070423
 ADD: 701 S ROSEMARY # 127
 CONT: TBD
 TEL: (561)856-6655 NEYITA
  
  
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 14/ 2013
  
 ACTION: BUILDING PROVISO
  
 1) 2010 FBC-B 713.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-07-31 Cont ID  
Sent By dharvey Date 2013-07-31 Time 17:01 Rev Time 0.00
Received By dharvey Date 2013-07-31 Time 16:06 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-07-26 Cont ID  
Sent By rferguso Date 2013-07-26 Time 15:02 Rev Time 0.00
Received By rferguso Date 2013-07-26 Time 15:02 Sent To E
Notes
2013-07-26 15:27:07701 SOUTH ROSEMARY AVE. SUITE #127
 PERMIT #13070423
  
 WEST PALM BEACH FIRE RESCUE PLAN REVIEW COMMENTS.
  
 * WHEN SUBMITTING PLANS FOR PERMIT, FIRE ALARM AND
 SPRINKLRE PLANS SHALL BE SUBMITTED SEPERATELY.
  
  
  
 RONALD E. FERGUSON, ASSISTANT FIRE MARSHAL
 BUREAU OF FIRE PREVENTION
 WEST PALM BEACH FIRE RESCUE
 PHONE #804-4700

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-01 Cont ID  
Sent By jwitmer Date 2013-08-01 Time 07:03 Rev Time 0.00
Received By jwitmer Date 2013-07-11 Time 14:45 Sent To  
Notes
2013-07-12 14:46:11B27

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-07-24 Cont ID  
Sent By hmoser Date 2013-07-24 Time 08:30 Rev Time 0.00
Received By hmoser Date 2013-07-23 Time 14:52 Sent To  
Notes
2013-07-24 08:30:40PASS PROVISO
 1) NOTE #4 CALLS FOR DUCT DUCTDETECTOR TO BE ON RETURN
 AIR DUCT. REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEMS
 2010 FBC (M) .
 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE .
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-07-15 Cont ID  
Sent By lwagner Date 2013-07-15 Time 15:19 Rev Time 0.00
Received By lwagner Date 2013-07-15 Time 14:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-07-23 Cont ID  
Sent By ESCHNIDE Date 2013-07-23 Time 11:33 Rev Time 0.50
Received By eschneid Date 2013-07-23 Time 11:33 Sent To  
Notes
2013-07-23 11:54:03SIGNS REQUIRE SEPARATE PERMITS WITH PLANS.
  
 NOTE: INTERNALLY ILLUMINATED SIGNS ARE NOT PERMITTED
 WITHIN THE ARCADE.
2013-07-16 14:07:167-16-13