| 2013-07-23 15:48:53 | BUILDING PLAN REVIEW |
| | PERMIT: 13070390 |
| | ADD: PALM BEACH LAKES BLVD # W-117 |
| | CONT: TBD (TO BE DETERMINED) |
| | TEL: (###)###-#### |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: JULY 23/ 2013 |
| | ACTION: BUILDING PROVISOS |
| | |
| | 1) PB OUTLET MALLS: |
| | BUILDING PROVISO: |
| | A LETTER FROM THE QUALIFIER OF BOTH THE SHELL |
| | CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT |
| | CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT |
| | PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| | CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK |
| | HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY |
| | WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| | DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND |
| | NOTARIZED. |
| | |
| | 2) PROVISO: SHEET A-03 GENERIC ACCESSABLE STALL PLEASE |
| | REVIEW 2010 FLORIDA ACCESSIBILITY CODE 604.8.1.6 |
| | LAVATORY. FIGURE 604.8.1.6 (GRAY BOX, FLORIDA SPECIFIC |
| | REQUIREMENT). IN NEW CONSTRUCTION, THE WHEELCHAIR |
| | ACCESSIBLE TOILET COMPARTMENT SHALL CONTAIN AN |
| | ACCESSIBLE LAVATORY WITHIN IT, WHICH MUST BE AT LEAST |
| | 19 INCHES WIDE BY 17 INCHES DEEP, NOMINAL SIZE, AND |
| | WALL-MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT |
| | TO OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY |
| | SECTION 604 FOR THE WHEELCHAIR ACCESSIBLE TOILET |
| | COMPARTMENT AND SHALL COMPLY WITH SECTION 606. SUCH |
| | LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED |
| | FIXTURE COUNT FOR THE BUILDING. SEE ALSO SECTION |
| | 213.3.4. |
| | |
| | 3A) PROVISO: SHEET A2-1B ACCESSIBLE DRESSING ROOM THERE |
| | IS NO CLEAR TURNING AREA FOR THE WHEEL CHAIR. 2010 |
| | FLORIDA ACCESSIBILITY CODE 803.2 A TURNING SPACE |
| | COMPLYING WITH 304 SHALL BE PROVIDED WITHIN THE ROOM. |
| | |
| | B) PROVISO: SHEET A2-1B NOR A6-3 DETAIL # 4, PROVIDE |
| | COMPLIANCE WITH 2010 FLORIDA ACCESSIBILITY CODE |
| | DRESSING ROOMS 803.4 BENCHES. A BENCH COMPLYING WITH |
| | 903 SHALL BE PROVIDED WITHIN THE ROOM. 903.4 BACK |
| | SUPPORT. THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR |
| | SHALL BE AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 |
| | INCHES (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A |
| | POINT 2 INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE |
| | TO A POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT |
| | SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM) |
| | MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED |
| | HORIZONTALLY. |
| | |
| | NOTE: SPECIFICATION SHEETS SP01 - SP22 ARE NOT PART OF |
| | THE PLAN REVIEW. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |