| Plan Review Stops For Permit 13070386 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2013-07-15 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-07-13 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-07-13 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2013-07-15 16:47:24 | NEW INFORMATION AND DRAWINGS PROVIDED BY CONTRACTOR | | | 7/15/13. ALL WORK SUBJECT TO FIELD EVALUATION AND | | | INSPECTION. ALL EQUIPMENT TO BE UL LISTED OR MEET THE | | | NEC AND APPLICABLE SAFETY CODES. PERMIT APPROVED | | | SUBJECT TO FIELD INSPECTOR APPROVAL. DH | | 2013-07-13 11:28:53 | PLACED IN DENIED UNDER "C" CAMOFLAUGE ELECTRIC | | | | | | USE 75 DEGREE RATING OR PROVIDE DOCUMENTATION OF 90 | | | RATING FOR ALL COMPONENTS | | | PROVIDE LISTING DATA FOR M-TEC PANELS | | | CONDUCTORS NOT RATED FOR LOADS OR OCP BASED ON | | | DOCUMENTATION PROVIDED | | | PROVIDE ONE LINE DRAWING SHOWING OCP AND AIC | | | PROVIDE NOTES ON DRAWINGS PER CONVERSATIONS, INCLUDING | | | ENT PROTECTION AND MOUNTING DETAILS OF CONDUCTORS | | | PLAN NOT CLEAR TO DETERMINE ALL NEEDED DETAILS FOR | | | PROPER EVALUATION | | | PROVIDE DETAILS OF TEMPORARY LIGHTING AND COMPLIANCE | | | WITH NEC 590 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-07-15 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-07-15 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-07-11 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2013-07-11 11:00:19 | ROUTED TO ELECTRICAL |
|
|
|