Plan Review Details - Permit 13070205
Plan Review Stops For Permit 13070205
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2013-07-27 Cont ID  
Sent By shill Date 2013-07-27 Time 09:42 Rev Time 0.00
Received By shill Date 2013-07-27 Time 09:42 Sent To FIRE
Notes
2013-07-27 09:43:08NOT LOCATED IN SPECIAL HAZARD FLOOD ZONE
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2013-07-27 Cont ID  
Sent By wjolin Date 2013-07-27 Time 11:04 Rev Time 0.00
Received By wjolin Date 2013-07-27 Time 10:32 Sent To P
Notes
2013-07-27 11:04:426801 NORTH JOG ROAD - #7 CONSTRUCTION TRAILER
 PERMIT #13070205
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 STAIRS SHALL BE A MINIMUM OF 36 INCHES IN WIDTH. STAIR
 RISERS SHALL BE BETWEEN 4 INCHES AND 7 INCHES IN
 HEIGHT. STAIRS SHALL BE SLIP RESISTANT AND HAVE A
 MINIMUM TREAD DEPTH OF 11 INCHES AND PREVENT THE
 ACCUMULATION OF WATER. GUARDS, AT LEAST 42-INCHES TALL,
 SHALL BE PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS
 (STAIRS, MEZZANINE, ETC.) THAT EXCEED 30-INCHES ABOVE
 THE FLOOR. OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A
 4-INCH DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE
 TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND
 BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE
 PASSAGE OF A 6-INCH DIAMETER SPHERE. HANDRAILS ARE
 REQUIRED ON BOTH SIDES OF THE STAIR. HANDRAILS SHALL BE
 LOCATED NOT LESS THAN 34 INCHES AND NOT MORE THAN 38
 INCHES ABOVE THE SURFACE OF THE TREAD, MEASURED
 VERTICALLY TO THE TOP OF THE RAIL FROM THE LEADING EDGE
 OF THE TREAD. HANDRAIL ENDS SHALL BE RETURNED TO THE
 WALL OR FLOOR OR SHALL TERMINATE AT NEWEL POSTS.
 HANDRAIL CROSS SECTION SHALL HAVE A DIAMETER OF NOT
 LESS THAN 1.25 INCHES AND NOT MORE THAN 2 INCHES.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By wlehnhar Date 2013-07-05 Time 15:18 Sent To Z
Notes
2013-07-05 15:19:10ZONING BOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-07-29 Cont ID  
Sent By lwagner Date 2013-07-29 Time 15:51 Rev Time 0.00
Received By lwagner Date 2013-07-29 Time 15:44 Sent To  
Notes
2013-07-29 15:52:39PLUMBING PERMIT REQUIRED IF CONNECTING TO SANITARY AND
 WATER

Review Stop Z ZONING
Rev No 1 Status P Date 2013-07-24 Cont ID  
Sent By eschneid Date 2013-07-24 Time 10:26 Rev Time 0.25
Received By eschneid Date 2013-07-24 Time 10:26 Sent To B
Notes
***NONE***