Plan Review Details - Permit 13070117
Plan Review Stops For Permit 13070117
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-07-22 Cont ID  
Sent By jwitmer Date 2013-07-22 Time 16:51 Rev Time 0.00
Received By jwitmer Date 2013-07-22 Time 15:26 Sent To  
Notes
2013-07-22 16:51:31BUILDING PLAN REVIEW
 PERMIT: 13070117
 ADD: 1781 PALM BEACH LAKES BLVD #W253
 CONT: TO BE DETERMINED
 TEL:
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 22/ 2013
 ACTION: PROVISO
  
 PB OUTLET MALLS:
 BUILDING PROVISO:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-08-05 Cont ID  
Sent By dharvey Date 2013-08-05 Time 12:13 Rev Time 0.00
Received By dharvey Date 2013-08-05 Time 11:51 Sent To  
Notes
2013-08-05 12:13:40LIGHTING CONTROLS TO COMPLY WITH FBC-EC 505.2
 SIGN TO BE IN COMPLIANCE WITH 505.2.4
 INSULATED GROUND RECEPTACLES TO COMPLY WITH 250.146 (D)

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-07-23 Cont ID  
Sent By scaldero Date 2013-07-23 Time 15:35 Rev Time 0.00
Received By scaldero Date 2013-07-23 Time 15:35 Sent To  
Notes
2013-07-23 15:35:51PERMIT #13070117
 TRACKING #
 MASTER #
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 SUE ELLEN CALDERON
 INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2013-08-16 Time   Rev Time 0.00
Received By rregueir Date 2013-07-09 Time 13:41 Sent To  
Notes
2013-07-18 13:42:08DIGITAL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-08-16 Cont ID  
Sent By rregueir Date 2013-08-16 Time 08:51 Rev Time 0.00
Received By rregueir Date 2013-08-16 Time 08:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-07-22 Cont ID  
Sent By lwagner Date 2013-07-22 Time 14:42 Rev Time 0.00
Received By lwagner Date 2013-07-22 Time 14:42 Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 2 Status N Date 2013-10-04 Cont ID  
Sent By rregueir Date 2013-10-04 Time 12:21 Rev Time 0.00
Received By rregueir Date 2013-10-04 Time 12:21 Sent To  
Notes
2013-10-04 12:21:59OK PER ROBERT BROWN

Review Stop POLICE POLICE
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2013-08-22 Time   Rev Time 0.00
Received By ktucker Date 2013-08-22 Time 11:12 Sent To  
Notes
2013-08-22 11:13:02(1) A FULLY FUNCTIONING AND OPERATIONAL CCTV SYSTEM
 CAPABLE OF RECORDING AND RETRIEVING AN IDENTIFIABLE
 IMAGE TO ASSIST IN OFFENDER IDENTIFICATION AND
 APPREHENSION.
 (2) CAMERAS TO BE LOCATED BEHIND THE REGISTER LOW
 ENOUGH FOR FACIAL VIEW, COVERAGE OF: THE FRONT ENTRY
 DOOR, STORE ROOM DOOR, AND THE RETAIL FLOOR.
 (3) A MONITOR FOR THE SYSTEM SHOULD BE PLACED AT THE
 MANAGER?S DESK, AND ONE BY THE POS AREA.
 (4) SILENT PANIC ALARM UNDER THE REGISTER AND ONE IN
 THE BACK STORAGE AREA
 (5) ACCESS CONTROL TO THE STORAGE AREA DOOR WITH A VIEW
 FINDER IN THE DOOR.
 (6) A SECURED DROP SAFE OR CASH MANAGEMENT DEVICE FOR
 RESTRICTED ACCESS TO MONEY/CASH RECEIPTS AT THE
 REGISTER AND A SECURED DROP SAFE OR CASH MANAGEMENT
 DEVICE IN THE STORAGE AREA.
 (7) SECURE THE REGISTER TO THE COUNTER
 (8) HEIGHT MARKERS AT THE ENTRANCE AND EXITS WHICH
 DISPLAY HEIGHT MEASURES.
 (9) WHERE WINDOW(S) ARE PRESENT, A CLEAR AND
 UNOBSTRUCTED VIEW FROM OUTSIDE THE STORE AND IN A
 NORMAL LINE OF SIGHT OF THE CASH REGISTER AND SALES
 TRANSACTION AREA
 (10) GATE DOORS (SWING GATE) SHOULD HAVE ACCESS
 CONTROL. ON THE PLAN ONLY 3 GATES ARE SHOWN RESTRICTING
 ACCESS BEHIND THE COUNTER, ONE EXTRA GATE IS NEEDED
 CONNECTING THE THREE SHOWCASES ON THE SIDE TO THE
 SHOWCASES ALONG THE BACK WALL.
 (11) ALL SHOWCASES SHOULD HAVE LOCKS AND IN THE
 EXPENSIVE SHOWCASES, CONSIDER AN ALARM.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-10-04 Cont ID  
Sent By rregueir Date 2013-10-04 Time 12:20 Rev Time 0.00
Received By rregueir Date 2013-10-04 Time 12:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-07-24 Cont ID  
Sent By eschneid Date 2013-07-24 Time 16:00 Rev Time 0.75
Received By eschneid Date 2013-07-24 Time 15:35 Sent To  
Notes
2013-07-24 15:59:26SIGNS AND THE AWNING REQUIRE SEPARATE PERMITS.
2013-07-22 10:47:547/22/13