Plan Review Details - Permit 13070068
| Plan Review Stops For Permit 13070068 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2013-07-29 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-07-29 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-07-29 |
Time |
10:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-07-05 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-07-05 |
Time |
12:40 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-07-05 |
Time |
12:31 |
Sent To |
|
|
| Notes |
| 2013-07-05 12:41:24 | 13070068 | | | 1427 CENTREPARK BLVD. #140 | | | FIRE ALARM SYSTEM | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE CONDUCTOR TYPE AND SIZE. FBC 907.1.2 | | | VERIFY WIRING METHODS AND WALL PENETRATIONS ARE | | | PROTECTED AND APPROPRIATELY FIRE RATED. NEC 300.21 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2013-07-22 |
|
|
Cont ID |
|
| Sent By |
rferguso |
Date |
2013-07-22 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
rferguso |
Date |
2013-07-22 |
Time |
13:57 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2013-07-05 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2013-07-05 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2013-07-05 |
Time |
11:12 |
Sent To |
E |
|
| Notes |
| 2013-07-05 11:24:22 | 1475 CENTERPARK BOULEVARD - SUITE #140 | | | PERMIT #13070068 | | | MASTER #13060068 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | NO SUITE NUMBER PROVIDED IN PLAN TITLEBLOCK. | | | | | | BREAK ROOM #110 MAY HAVE AN ACCORDIAN DOOR THAT | | | SEPARATES THE ROOM INTO TWO ROOMS WHEREBY AN ADDITIONAL | | | NOTIFICATION WOULD BE NEEDED. | | | | | | SEVERAL NOTIFICATION APPLIANCES APPEAR TO BE LOCATED | | | TOO FAR FROM ADJACENT WALLS INCLUDING ADMIN #103, | | | WORKROOM #107, AND CORRIDOR #109. | | | | | | INSUFFICIENT NOTIFICATION APPLIANCES PROVIDED AT | | | SOUTHWEST AREA OF LARGE OPEN OFFICE #105. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-07-29 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-07-29 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-07-19 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2013-07-19 14:19:16 | INCOMING SENT TO FIRE BOX . JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-07-05 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-07-05 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-07-02 |
Time |
17:10 |
Sent To |
|
|
| Notes |
| 2013-07-02 17:05:20 | TO FIRE |
|
|
|