Plan Review Details - Permit 13061115
Plan Review Stops For Permit 13061115
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-07-12 Cont ID  
Sent By rmcdouga Date 2013-07-12 Time 07:52 Rev Time 0.00
Received By rmcdouga Date 2013-07-12 Time 07:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-07-15 Cont ID  
Sent By dharvey Date 2013-07-15 Time 17:32 Rev Time 0.00
Received By dharvey Date 2013-07-15 Time 17:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-07-08 Cont ID  
Sent By dharvey Date 2013-07-08 Time 12:49 Rev Time 0.00
Received By dharvey Date 2013-07-08 Time 12:28 Sent To  
Notes
2013-07-08 12:50:1813061115
 3080 ARLINGTON ROAD
 SFD REMODEL
  
 THE SCOPE OF THE PROPOSED ELECTRICAL WORK IS NOT CLEAR.
 PROVIDE A DETAILED ELECTRICAL PLAN FOR ALL
 IMPROVEMENTS.
  
 INDICATE THE SIZE, RATING, LOCATION OF THE EXISTING
 SERVICE, MAIN DISCONNECT AND PANEL BOARD. SHOW SERVICE
 AND PANEL BOARD LOCATIONS. SHOW NEW AND EXISTING
 OUTLETS. INCLUDE A PANEL SCHEDULE. NEC 215.5
  
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI PROTECTED.
 NEC 210.12
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
  
 SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI
 PROTECTED. NEC 210.8
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND
 REAR ELEVATIONS. NEC 210.8
  
 PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE BRANCH
 CIRCUITS. NEC 210.52
  
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS.
 NEC 210.11 (C)(3)
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-16 Cont ID  
Sent By shill Date 2013-07-16 Time 08:00 Rev Time 0.00
Received By shill Date 2013-07-15 Time 16:51 Sent To  
Notes
2013-07-15 16:51:56INCOMING SENT TO D. HARVEYS' DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-12 Cont ID  
Sent By rmcdouga Date 2013-07-12 Time 08:09 Rev Time 0.00
Received By rmcdouga Date 2013-06-28 Time 05:32 Sent To  
Notes
2013-06-29 05:34:32R03
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-07-12 Cont ID  
Sent By rmcdouga Date 2013-07-12 Time 08:09 Rev Time 0.00
Received By rmcdouga Date 2013-07-12 Time 08:08 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved