| 2013-08-17 11:01:27 | BUILDING PLAN REVIEW |
| | PERMIT: 13061104 |
| | ADD: 5800 S DIXIE |
| | CONT: MIKE MOORE |
| | TEL: (561)301-9468 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: AUGUST 17/2013 |
| | ACTION: DENIED |
| | |
| | FROM 1ST REVIEW, QUESTION WAS ASKED IF THIS BUILDING IS |
| | FIRE SPRINKLERED, NOT PROVIDED, ASSUMED FOR THIS PLAN |
| | REVIEW, NON-SPRINKLERED. |
| | |
| | 1) SHEET A1.1: THE CONTRACTOR WILL NEED TO UPDATE THE |
| | EXISSTING PERMIT APPLICATION AND APPLY FOR A SECOND |
| | PERMIT APPLICATION. THE PLANS INDICATE THE SPLITING OF |
| | A SINGLE TENANT SPACE INTO TWO INDIVUAL TENANT SPECES |
| | BY CREATING A TENANT SEPERATION WALL. THE CURRENT |
| | PERMIT APPLICATION UNDER THE DESCRIPTION OF WORK ONLY |
| | LIST A DEMISSING WALL. THE PLANS REFLECT ALSO THE |
| | CREATION OF TWO RESTROOMS, ONE IN EACH TENANT SPACE. |
| | NOTE THE VALLUE FOR THE NEW TENANT SEPERATION WALL, 2 |
| | NEW RESTROOM WALLS, AND THE OUTFITTING OF RESTROOMS IS |
| | ONLY $1,500.00. |
| | |
| | 1A) ON THE EXISTING PERMIT APPLICATION UPDATE THE |
| | DESCRIPTION OF WORK, ADD A SUITE NUMBER TO THE |
| | APPLICATION AND INCREASE THE VALUE OF WORK TO BE |
| | COMPLETED UNDER THIS PERMIT. |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF |
| | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER |
| | ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, |
| | PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE |
| | WORK (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD |
| | AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION |
| | REFRENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF |
| | NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 1B) SUBMIT A SECOND PERMIT PERMIT APPLICATION UPDATE |
| | THE DESCRIPTION OF WORK, ADD A SUITE NUMBER TO THE |
| | APPLICATION AND INCREASE THE VALUE OF WORK TO BE |
| | COMPLETED UNDER THIS PERMIT. |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF |
| | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER |
| | ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, |
| | PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE |
| | WORK (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD |
| | AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION |
| | REFRENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF |
| | NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 1C) NOTE INDICATES THE CHOICE OF TWO 1 HOUR UL RATINGS |
| | FOR THE 1 HOUR TENANT SEPERATION WALL. PLEASE SUBMIT |
| | ONE UL DESIGN AND PRODUCE THE DESIGN ON THE PLANS, |
| | INSPECTORS DO NOT CARRY A UL BOOK IN THEIR CAR. |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH |
| | DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION, |
| | IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | PLEASE NOTE SOME OF THE UL LISTINGS INDICATE TO TAKE |
| | THE WALL TO THE CEILING LINE. PLEASE REVIEW2010 FBC-B |
| | 709.4 CONTINUITY. |
| | FIRE PARTITIONS SHALL EXTEND FROM THE TOP OF THE |
| | FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW TO THE |
| | UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR DECK |
| | ABOVE OR TO THE FIRE-RESISTANCE-RATED FLOOR/CEILING OR |
| | ROOF/CEILING ASSEMBLY ABOVE, AND SHALL BE SECURELY |
| | ATTACHED THERETO. IF THE PARTITIONS ARE NOT CONTINUOUS |
| | TO THE SHEATHING, DECK OR SLAB, AND WHERE CONSTRUCTED |
| | OF COMBUSTIBLE CONSTRUCTION, THE SPACE BETWEEN THE |
| | CEILING AND THE SHEATHING, DECK OR SLAB ABOVE SHALL BE |
| | FIREBLOCKED OR DRAFTSTOPPED IN ACCORDANCE WITH SECTIONS |
| | 717.2 AND 717.3 AT THE PARTITION LINE. THE SUPPORTING |
| | CONSTRUCTION SHALL BE PROTECTED TO AFFORD THE REQUIRED |
| | FIRE-RESISTANCE RATING OF THE WALL SUPPORTED, EXCEPT |
| | FOR WALLS SEPARATING TENANT SPACES IN COVERED MALL |
| | BUILDINGS, WALLS SEPARATING DWELLING UNITS, WALLS |
| | SEPARATING SLEEPING UNITS AND CORRIDOR WALLS, IN |
| | BUILDINGS OF TYPE IIB, IIIB AND VB CONSTRUCTION. |
| | |
| | 1D) THE PLANS DO NOT INDICATE WHICH WAY THE ROOF |
| | FRAMING MEMBERS ARE DESIGNED, IF THE ROOF FRAMING |
| | MEMBERS PENETRATE THE NEW 1 HOUR FIRE RATED WALL OR |
| | THERE IS ANY OTHER PENETRATIONS OF THE 1 HOUR RATED |
| | WALL COMPLIANCE WITH 2010 FBC-B 709.7 PENETRATIONS. |
| | PENETRATIONS OF FIRE PARTITIONS SHALL COMPLY WITH |
| | SECTION 713. |
| | 713.3.1 THROUGH PENETRATIONS. |
| | THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS |
| | SHALL COMPLY WITH SECTION 713.3.1.1 OR 713.3.1.2. |
| | 713.3.1.1 FIRE-RESISTANCE-RATED ASSEMBLIES. |
| | PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN |
| | APPROVED FIRE-RESISTANCE-RATED ASSEMBLY. |
| | |
| | 713.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. |
| | THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED |
| | PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN |
| | ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM |
| | POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) |
| | OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN |
| | THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL |
| | PENETRATED. |
| | |
| | 1E) 2010 FBC-B 713.6 |
| | FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE |
| | BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL |
| | REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE |
| | AND SMOKE BARRIER ? PROTECT ALL OPENINGS.? |
| | |
| | 1F) PLEASE REVIEW PLUMBING COMMENTS ABOUT THE |
| | ACCESSIBLE RESTROOM THAT IS DESIGNED WITH THE OUTSIDE |
| | DIMENSION OF 7'-2", THE MINIMUM INTERIOR DIMENSION IS |
| | 7'-1". 2010 FL ACC CODE FIGURE 604.8.1.6. |
| | |
| | SUGGEST A MEETING BEFORE PLANS ARE RESUBMITTED TO |
| | REVIEW AND MAKE SURE A PERMIT WILL BE ABLE ISSUED UNDER |
| | THE NEXT REVIEW!!!! |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |