Plan Review Details - Permit 13061035
Plan Review Stops For Permit 13061035
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-07-16 Cont ID  
Sent By shill Date 2013-07-16 Time 07:34 Rev Time 0.00
Received By shill Date 2013-07-16 Time 07:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-29 Cont ID  
Sent By shill Date 2013-06-29 Time 08:43 Rev Time 0.00
Received By shill Date 2013-06-29 Time 08:43 Sent To  
Notes
2013-06-29 08:43:49****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-07-02 Cont ID  
Sent By dharvey Date 2013-07-02 Time 10:07 Rev Time 0.00
Received By dharvey Date 2013-07-02 Time 09:37 Sent To  
Notes
2013-07-02 10:07:31BY RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-06-29 Cont ID  
Sent By wjolin Date 2013-06-29 Time 16:10 Rev Time 0.00
Received By wjolin Date 2013-06-29 Time 16:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-02 Cont ID  
Sent By hmoser Date 2013-07-02 Time 10:28 Rev Time 0.00
Received By hmoser Date 2013-06-27 Time 10:54 Sent To  
Notes
2013-06-28 10:54:33SENT TO B4 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2013-07-02 Cont ID  
Sent By hmoser Date 2013-07-02 Time 10:22 Rev Time 0.00
Received By hmoser Date 2013-07-02 Time 10:21 Sent To  
Notes
2013-07-02 10:25:50CALLED CONTRACTOR HE TOLD ME THERE IS NO AIR
 CONDITIONING
 OR VENTILATION ON THIS REMODEL.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-07-01 Cont ID  
Sent By lwagner Date 2013-07-01 Time 15:05 Rev Time 0.00
Received By lwagner Date 2013-07-01 Time 14:58 Sent To  
Notes
***NONE***