Plan Review Details - Permit 13061001
Plan Review Stops For Permit 13061001
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-08-31 Cont ID  
Sent By shill Date 2013-08-31 Time 14:28 Rev Time 0.00
Received By shill Date 2013-08-31 Time 14:28 Sent To  
Notes
2013-08-31 14:29:26***COURTESY REVIEWS WERE PERFORMED VIA EMAIL**
  
 EMAIL FROM 8/31:
  
 BEFORE I DO ANOTHER COURTESY REVIEW, PLEASE REFER TO MY
 COMMENT LIST, AND THEN CIRCLE OR HIGHLIGHT ON THE TEST
 YOU WISH FOR ME TO REVIEW THE TEST STANDARD USED. THERE
 SHOULD BE A TOTAL OF 3 (IIC, STC, FLAME SPREAD).
  
 IF YOU CANNOT FIND THE TEST CIRCLED REFERENCED IN THE
 COMMENT LIST, THEY'D NEED TO SUBMIT A REQUEST FOR
 ALTERNATIVE MATERIALS AND METHODS TO PROVIDE DATA TO
 JUSTIFY WHY THEY ELECTED TO USE A DIFFERENT TEST, OR A
 DIFFERENT METHOD, OR PROVIDE DATA/ENGINEERING TO SHOW
 WHY THEY DO NOT NEED TO PERFORM THE TEST PRESCRIBED BY
 THE FBC AND IBC (THEREFORE A NATIONAL REQUIREMENT
 ANYWHERE THAT USES THE ICC AS BASE CODE). ALSO CHECK
 THAT NONE OF THE TESTS INCLUDE A SUSPENDED DRYWALL
 CEILING.
  
 I STARTED TO LOOK AT THE DOCUMENTS - THE FIRST HAD A
 SUSPENDED CEILING. THE SECOND DID NOT MEET THE
 REQUIREMENTS OF THE STANDARDS OF THE TEST. PLEASE TAKE
 THE TIME TO READ THE TEST REPORTS BEFORE SENDING. BY
 NOW YOU SHOULD BE AN EXPERT!
  
 AFTER YOU CONFIRM THAT, TO THE BEST OF YOUR KNOWLEDGE,
 THE PRODUCT MEETS THE REQUIREMENTS OF THE FBC, PLEASE
 FEEL FREE TO SEND TO ME.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-05 Cont ID  
Sent By shill Date 2013-07-05 Time 15:19 Rev Time 0.00
Received By shill Date 2013-07-05 Time 15:19 Sent To  
Notes
2013-07-05 15:28:05****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED. PROVIDE COPIES OF TEST REPORT.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED. PROVIDE COPY OF TEST REPORT.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 4. THIS WORK IS NOT WITHIN THE SCOPE OF A RESIDENTIAL
 CONTRACTOR LICENSE.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-05 Cont ID  
Sent By shill Date 2013-07-05 Time 15:28 Rev Time 0.00
Received By shill Date 2013-06-26 Time 07:15 Sent To  
Notes
2013-06-27 07:16:23SENT TO BLDG. UNDER $5000 BOX.