Plan Review Details - Permit 13060970
Plan Review Stops For Permit 13060970
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2014-03-27 Cont ID  
Sent By shill Date 2014-03-27 Time 13:16 Rev Time 0.00
Received By shill Date 2014-03-27 Time 13:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2014-03-11 Cont ID  
Sent By shill Date 2014-03-11 Time 17:00 Rev Time 0.00
Received By shill Date 2014-02-26 Time 10:02 Sent To  
Notes
2014-03-11 17:06:27****CORRECTIONS****
 2/26 SUBMITTAL
  
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 2. ENGINEER SPECIFIES -100PSF ROOF PRESSURES ZONE 2.
 PRODUCT APPROVAL SUBMITTED HAS A LIMITATION OF -80.9.
 PLEASE ADDRESS.
  
 3/11/14 - ENGINEER RESPONSE IS THAT THE UPLIFT
 (ULTIMATE) ON THE PLAN IS 100PSF, WHICH CONVERTS TO
 60PSF. PROVIDE CALCULATIONS/EXPLANATION. THE NOA
 SPECIFIES FASTENING 3" APART IN THE 3" RIBS. SEE FBC
 2010 RESIDENTIAL TABLES 301.2(2) AND (3). ZONE 3, 10SF
 OR LESS, EXPOSURE C, IS -131.8PSF ULTIMATE AND -95.7
 ASD. IT IS NOT CLEAR HOW ENGINEER HAS ARRIVED AT A
 PRESSURE OF -60PSF ASD, -135 ULTIMATE.
  
  
2014-02-27 10:10:56SENT S HILL

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2014-02-03 Cont ID  
Sent By shill Date 2014-02-03 Time 18:34 Rev Time 0.00
Received By shill Date 2014-02-03 Time 18:34 Sent To  
Notes
2014-02-03 18:38:03****CORRECTIONS****
 SUBMITTALS 1/21 AND 1/24 WERE THE SAME
  
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. ENGINEER OF RECORD IS TO REVIEW PRODUCT APPROVAL,
 FBC 107, FBC 2010 RESIDENTIAL 301.
  
 2ND REVIEW -
  
 ENGINEER OF RECORD IS TO REVIEW PRODUCT APPROVAL, FBC
 107, FBC 2010 RESIDENTIAL 301. HAVE THIS DONE PRIOR TO
 SUBMITTAL.
  
 NEW COMMENT:
  
 2. ENGINEER SPECIFIES -100PSF ROOF PRESSURES ZONE 2.
 PRODUCT APPROVAL SUBMITTED HAS A LIMITATION OF -80.9.
 PLEASE ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2014-02-03 Cont ID  
Sent By shill Date 2014-02-03 Time 18:39 Rev Time 0.00
Received By shill Date 2014-02-03 Time 18:39 Sent To  
Notes
2014-02-03 18:39:30****CORRECTIONS****
 SUBMITTALS 1/21 AND 1/24 WERE THE SAME
  
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. ENGINEER OF RECORD IS TO REVIEW PRODUCT APPROVAL,
 FBC 107, FBC 2010 RESIDENTIAL 301.
  
 2ND REVIEW -
  
 ENGINEER OF RECORD IS TO REVIEW PRODUCT APPROVAL, FBC
 107, FBC 2010 RESIDENTIAL 301. HAVE THIS DONE PRIOR TO
 SUBMITTAL.
  
 NEW COMMENT:
  
 2. ENGINEER SPECIFIES -100PSF ROOF PRESSURES ZONE 2.
 PRODUCT APPROVAL SUBMITTED HAS A LIMITATION OF -80.9.
 PLEASE ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-08-29 Cont ID  
Sent By shill Date 2013-08-29 Time 13:29 Rev Time 0.00
Received By shill Date 2013-08-29 Time 13:29 Sent To  
Notes
2013-08-29 13:31:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. THE PRODUCT APPROVAL FOR THE ROOF PANELS DOES NOT
 INCLUDE A FASTENING DETAIL OR INFORMATION REGARDING
 RESISTANCE TO WIND LOADS. EITHER REVISE THE PLAN TO
 INCLUDE THIS INFORMATION OR PROVIDE FASTENING
 SPECIFICATION. ENGINEER OF RECORD IS TO REVIEW PRODUCT
 APPROVAL, FBC 107, FBC 2010 RESIDENTIAL 301.
  
 2ND REVIEW - A DIFFERENT PRODUCT APPROVAL APPROVAL WAS
 SUBMITTED. ON THE PRODUCT APPROVAL, INDICATE METHOD OF
 ATTACHMENT.
  
 ENGINEER OF RECORD IS TO REVIEW PRODUCT APPROVAL, FBC
 107, FBC 2010 RESIDENTIAL 301. HAVE THIS DONE PRIOR TO
 SUBMITTAL.
  
 ENGINEER OF RECORD MAY EMAIL CORRECTIONS TO
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-08-19 Cont ID  
Sent By shill Date 2013-08-19 Time 11:16 Rev Time 0.00
Received By shill Date 2013-08-19 Time 11:16 Sent To  
Notes
2013-08-19 11:17:56****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE PRODUCT APPROVAL FOR THE ROOF PANELS DOES NOT
 INCLUDE A FASTENING DETAIL OR INFORMATION REGARDING
 RESISTANCE TO WIND LOADS. EITHER REVISE THE PLAN TO
 INCLUDE THIS INFORMATION OR PROVIDE FASTENING
 SPECIFICATION. ENGINEER OF RECORD IS TO REVIEW PRODUCT
 APPROVAL, FBC 107, FBC 2010 RESIDENTIAL 301.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-07-18 Cont ID  
Sent By shill Date 2013-07-18 Time 16:55 Rev Time 0.00
Received By shill Date 2013-07-18 Time 16:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2014-03-27 Cont ID  
Sent By shill Date 2014-03-27 Time 13:16 Rev Time 0.00
Received By shill Date 2014-03-18 Time 08:44 Sent To  
Notes
2014-03-19 08:45:19RESUB SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2014-03-11 Cont ID  
Sent By shill Date 2014-03-11 Time 17:06 Rev Time 0.00
Received By shill Date 2014-03-11 Time 17:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-02-03 Cont ID  
Sent By shill Date 2014-02-03 Time 18:38 Rev Time 0.00
Received By shill Date 2014-01-25 Time 07:06 Sent To  
Notes
2014-01-25 07:06:25INCOMING SENT TO S. HILL DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-02-03 Cont ID  
Sent By shill Date 2014-02-03 Time 18:39 Rev Time 0.00
Received By shill Date 2014-01-21 Time 14:09 Sent To  
Notes
2014-01-22 14:09:28RESUBMITTAL SENT TO S. HILL'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-08-29 Cont ID  
Sent By shill Date 2013-08-29 Time 13:31 Rev Time 0.00
Received By shill Date 2013-08-21 Time 18:03 Sent To  
Notes
2013-08-21 18:03:35TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-19 Cont ID  
Sent By shill Date 2013-08-19 Time 11:18 Rev Time 0.00
Received By shill Date 2013-08-05 Time 08:32 Sent To  
Notes
2013-08-06 08:33:19SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-18 Cont ID  
Sent By shill Date 2013-07-18 Time 16:55 Rev Time 0.00
Received By shill Date 2013-06-26 Time 07:20 Sent To  
Notes
2013-06-27 07:20:55SENT TO MISC 2 BOX.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2013-07-18 Cont ID  
Sent By shill Date 2013-07-18 Time 16:56 Rev Time 0.00
Received By shill Date 2013-07-18 Time 16:56 Sent To  
Notes
2013-07-18 17:03:29NO ROOF APPLICATION OR PLANS/PRODUCT APPROVAL SUBMITTED
 SEPARATE ROOF PERMIT REQUIRED WITH APPLICATION, PRODUCT
 APPROVAL, AND ENHANCED FASTENING SPECIFICATION
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-07-16 Cont ID  
Sent By ajones Date 2013-07-16 Time 13:29 Rev Time 0.00
Received By ajones Date 2013-07-16 Time 13:29 Sent To B
Notes
***NONE***