Plan Review Details - Permit 13060962
Plan Review Stops For Permit 13060962
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-07-03 Cont ID  
Sent By dharvey Date 2013-07-03 Time 11:08 Rev Time 0.00
Received By dharvey Date 2013-07-03 Time 11:08 Sent To  
Notes
2013-07-03 11:09:20SEE PROVISO ON PLAN.RL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-06-26 Cont ID  
Sent By dharvey Date 2013-06-26 Time 10:05 Rev Time 0.00
Received By dharvey Date 2013-06-26 Time 10:05 Sent To  
Notes
2013-06-26 10:05:46INDICATE WIRING METHOD. PROVIDE SPECIFICATIONS AND
 LISTING FOR EQUIPMENT. PROVIDE LAYOUT OR DESCRIPTION OF
 THE PROPOSED LOCATION OF WIRING FROM SOURCE TO
 DESTINATION. PROVIDE A TYPICAL FIRE STOP DETAIL FOR ALL
 PENETRATIONS OF RATED ASSEMBLIES. CABLES AND CONDUIT
 MAY NOT BE LOCATED WITHIN SHAFTS, OR WITHIN EGRESS
 STAIR WAYS. WIRING LOCATED IN DAMP OR WET LOCATIONS
 MUST BE LISTED FOR THE LOCATION. NEC 110.3, 110.12
 110.8, 300.21
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
 561-805-6718
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-26 Cont ID  
Sent By dharvey Date 2013-06-26 Time 10:05 Rev Time 0.00
Received By dharvey Date 2013-06-25 Time 17:42 Sent To  
Notes
2013-06-25 17:42:29ROUTED TO ELECTRICAL


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved