| Plan Review Stops For Permit 13060934 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2013-07-03 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-07-03 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-07-03 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2013-07-03 11:57:17 | ISSUED WITH A PROVISO. RL |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-06-26 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-06-26 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-06-26 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2013-06-26 11:18:42 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | INDICATE WIRING METHOD. PROVIDE SPECIFICATIONS AND | | | LISTING FOR EQUIPMENT. PROVIDE LAYOUT OR DESCRIPTION OF | | | THE PROPOSED LOCATION OF WIRING FROM SOURCE TO | | | DESTINATION. PROVIDE A TYPICAL FIRE STOP DETAIL FOR ALL | | | PENETRATIONS OF RATED ASSEMBLIES. CABLES AND CONDUIT | | | MAY NOT BE LOCATED WITHIN SHAFTS, OR WITHIN EGRESS | | | STAIR WAYS. WIRING LOCATED IN DAMP OR WET LOCATIONS | | | MUST BE LISTED FOR THE LOCATION. NEC 110.3, 110.12 | | | 110.8, 300.21 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | 561-805-6718 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-06-26 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-06-26 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-06-25 |
Time |
17:58 |
Sent To |
|
|
| Notes |
| 2013-06-25 17:58:45 | ROUTED TO ELECTRICAL |
|
|
|