Plan Review Details - Permit 13060882
Plan Review Stops For Permit 13060882
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-29 Cont ID  
Sent By shill Date 2013-06-29 Time 06:09 Rev Time 0.00
Received By shill Date 2013-06-29 Time 06:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-25 Cont ID  
Sent By shill Date 2013-06-25 Time 09:07 Rev Time 0.00
Received By shill Date 2013-06-25 Time 09:07 Sent To  
Notes
2013-06-25 09:09:43****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. WHEN SUBMITTING FOR ROOF PERMIT, MEAN ROOF HEIGHT
 REQUIRED SO DESIGN PRESSURES CAN BE DETERMINED, FBC R
 301.
  
 2. ASSEMBLY SELECTED DOES NOT MEET DESIGN PRESSURE
 REQUIREMENTS FOR ZONES 2 AND 3. SEE LAST PAGE OF NOA,
 GENERAL LIMITATION #7, CALCULATIONS BY AN ARCHITECT OR
 ENGINEER REQUIRED, FBC R 301.
  