Plan Review Details - Permit 13060868
Plan Review Stops For Permit 13060868
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-12-17 Cont ID  
Sent By shill Date 2013-12-17 Time 18:19 Rev Time 0.00
Received By shill Date 2013-12-17 Time 18:19 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-11-25 Cont ID  
Sent By S Hill Date 2013-11-25 Time 16:41 Rev Time 0.00
Received By shill Date 2013-11-25 Time 12:44 Sent To  
Notes
2013-11-25 16:49:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. OK.
  
 2. FBC 2010 EXISTING BUILDING 912.4.1, FBC 2010
 BUILDING 1031.2, PANIC AND FIRE EXIT HARDWARE REQUIRED
 WHERE THE MEANS OF EGRESS DOOR SERVES AN OCCUPANT LOAD
 GREATER THAN 100. SEE ALSO COMMENT 3; OCCUPANT LOAD.
 REVISE PLAN TO SHOW LOCATIONS REQUIRED, IF ANY.
  
 2ND REVIEW, REQUIREMENTS CANNOT BE DETERMINED DUE TO
 LACK OF INFORMATION, SEE ITEM 3.
  
 3RD REVIEW, PLANS INDICATE THAT ALL DOORS WILL HAVE
 PANIC DEVICES. PLANS ALSO HAVE A STATEMENT THAT ALL
 INFORMATION WAS PROVIDED BY OWNER. DESIGNER OF RECORD
 TO DETERMINE WHETHER EXTERIOR DOORS HAVE PANIC DEVICES
 AND TO INCLUDE IN SCOPE OF WORK IF THEY ARE NEEDED. AS
 THEY ARE COMPONENTS AND CLADDING, PRODUCT APPROVALS
 REQUIRED.
  
 3. OK
  
 4. OK
  
 5. FBC 2010 EXISTING BUILDING 912.5, HEIGHT AND AREA TO
 COMPLY WITH FBC 2010 BUILDING TABLE 503 FOR BUILDING
 HEIGHT & AREA.
  
 2ND REVIEW, RESPONSE LETTER STATES THIS IS COMPLETED.
 IT IS NOT CLEAR HOW THIS WAS ADDRESSED AS NO
 INFORMATION ABOUT THE EXISTING BUILDING WAS PROVIDED.
  
 3RD REVIEW, PLEASE ADDRESS.
  
 6. OK
  
 NEW COMMENT:
  
 PLEASE NOTE THAT THIS IS A CHANGE OF OCCUPANCY AS WELL
 AS A LEVEL 2 ALTERATION. PLEASE INCLUDE THIS
 INFORMATION ON THE PLAN.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-08-12 Cont ID  
Sent By shill Date 2013-08-12 Time 11:40 Rev Time 0.00
Received By shill Date 2013-08-12 Time 11:33 Sent To  
Notes
2013-08-12 11:40:05****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 2010 EXISTING BUILDING 912.2.2, FBC 2010
 BUILDING 907.2.3, FIRE ALARM REQUIRED.
  
 2ND REVIEW, PLEASE ADVISE WHEN THIS IS ISSUED.
  
 2. FBC 2010 EXISTING BUILDING 912.4.1, FBC 2010
 BUILDING 1031.2, PANIC AND FIRE EXIT HARDWARE REQUIRED
 WHERE THE MEANS OF EGRESS DOOR SERVES AN OCCUPANT LOAD
 GREATER THAN 100. SEE ALSO COMMENT 3; OCCUPANT LOAD.
 REVISE PLAN TO SHOW LOCATIONS REQUIRED, IF ANY.
  
 2ND REVIEW, REQUIREMENTS CANNOT BE DETERMINED DUE TO
 LACK OF INFORMATION, SEE ITEM 3.
  
 3. FBC 2010 EXISTING BUILDING 912.4.1, FBC 2010
 BUILDING 1004.1.1, LABEL EACH ROOM WITH OCCUPANCY
 CLASSIFICATION AND OCCUPANT LOAD FOR EACH ROOM.
 ALTHOUGH THE SCHOOL BOARD HAS DETERMINED THAT YOU CAN
 HAVE A MAXIMUM OF 150 STUDENTS, THE FLORIDA BUILDING
 CODE REQUIRES EXITING IN COMPLIANCE WITH FBC 2010 TABLE
 1004.
  
 NOT ADDRESSED. RESPONSE LETTER STATES THAT PLAN WAS
 REVISED. PLAN SHOWS RATIOS SUCH AS 1:10, 1:18. THIS IS
 NOT AN OCCUPANT LOAD. SEE FBC TABLE 1004. EACH ROOM
 SHOULD STATE OCCUPANT LOAD (EITHER DESIGN LOAD OR
 OCCUPANT LOAD FROM TABLE 1004, WHICHEVER IS GREATER).
  
 4. OK
  
 5. FBC 2010 EXISTING BUILDING 912.5, HEIGHT AND AREA TO
 COMPLY WITH FBC 2010 BUILDING TABLE 503 FOR BUILDING
 HEIGHT & AREA.
  
 2ND REVIEW, RESPONSE LETTER STATES THIS IS COMPLETED.
 IT IS NOT CLEAR HOW THIS WAS ADDRESSED AS NO
 INFORMATION ABOUT THE EXISTING BUILDING WAS PROVIDED.
  
 6. IMPACT FEE ASSESSMENT REQUIRED BY PALM BEACH COUNTY.
 561-233-5025 FOR MORE INFORMATION. PROVIDE STAMPED PLAN
 AND RECEIPT, IF APPLICABLE.
  
 2ND REVIEW, NOT ADDRESSED. THIS MAY BE DONE AT THE END
 OF PLAN REVIEW PROCESS BUT MUST BE DONE PRIOR TO
 ISSUANCE OF A PERMIT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-01 Cont ID  
Sent By shill Date 2013-07-01 Time 11:56 Rev Time 0.00
Received By shill Date 2013-07-01 Time 11:56 Sent To  
Notes
2013-07-01 12:39:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 2010 EXISTING BUILDING 912.2.2, FBC 2010
 BUILDING 907.2.3, FIRE ALARM REQUIRED.
  
 2. FBC 2010 EXISTING BUILDING 912.4.1, FBC 2010
 BUILDING 1031.2, PANIC AND FIRE EXIT HARDWARE REQUIRED
 WHERE THE MEANS OF EGRESS DOOR SERVES AN OCCUPANT LOAD
 GREATER THAN 100. SEE ALSO COMMENT 3; OCCUPANT LOAD.
 REVISE PLAN TO SHOW LOCATIONS REQUIRED, IF ANY.
  
 3. FBC 2010 EXISTING BUILDING 912.4.1, FBC 2010
 BUILDING 1004.1.1, LABEL EACH ROOM WITH OCCUPANCY
 CLASSIFICATION AND OCCUPANT LOAD FOR EACH ROOM.
 ALTHOUGH THE SCHOOL BOARD HAS DETERMINED THAT YOU CAN
 HAVE A MAXIMUM OF 150 STUDENTS, THE FLORIDA BUILDING
 CODE REQUIRES EXITING IN COMPLIANCE WITH FBC 2010 TABLE
 1004.
  
 4. PLEASE REVISE PLAN TO NOTE WHETHER THIS WILL BE USED
 FOR CLASSROOM/SCHOOL ONLY, OR ALSO FOR DAY CARE FBC
 2010 BUILDING 1037.
  
 5. FBC 2010 EXISTING BUILDING 912.5, HEIGHT AND AREA TO
 COMPLY WITH FBC 2010 BUILDING TABLE 503 FOR BUILDING
 HEIGHT & AREA.
  
 6. IMPACT FEE ASSESSMENT REQUIRED BY PALM BEACH COUNTY.
 561-233-5025 FOR MORE INFORMATION. PROVIDE STAMPED PLAN
 AND RECEIPT, IF APPLICABLE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-12-02 Cont ID  
Sent By dharvey Date 2013-12-02 Time 13:48 Rev Time 0.00
Received By dharvey Date 2013-12-02 Time 13:48 Sent To  
Notes
2013-12-02 13:49:41ILLUMINATION LEVEL VERIFICATION NOT REQUIRED PER ROBERT
 BROWN. REQUIREMENT APPLIES TO PUBLIC SCHOOLS AND
 CHARTER SCHOOLS DO NOT NEED TO COMPLY. DH
2013-10-29 11:34:17NEW PLANS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-08-06 Cont ID  
Sent By dharvey Date 2013-08-05 Time 15:33 Rev Time 0.00
Received By dharvey Date 2013-08-05 Time 15:22 Sent To  
Notes
2013-08-05 15:33:27SEPERATE FIRE ALARM PERMIT IS REQUIRED
 SEPARATE PERMITS ARE REQUIRE FOR DATA, LOW VOLTAGE,
 AUDIO, ACCESS AND OTHER SYSTEMS
 ALL PREVIOUS ITEMS HAVE BEEN ADDRESSED EXCEPT
 ILLUMINATION LEVEL VERIFICATION
 PROVIDE CERTIFICATION OF ILLUMANATION LEVEL AND
 PHOTOMETRIC CHART FOR RECORD PRIOR TO FINAL INSPECTION

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-06-27 Cont ID  
Sent By dharvey Date 2013-06-27 Time 11:07 Rev Time 0.00
Received By dharvey Date 2013-06-27 Time 11:07 Sent To FIRE
Notes
2013-06-27 11:10:3313060868
 901 NORTH POINT PKWY
 CHANGE OF USE TO EDUCATIONAL
  
 VERIFY THAT THE REQUIRED WORKING CLEARANCES AND
 DEDICATED WORKING SPACE HAS BEEN PROVIDED FOR THE
 ELECTRICAL EQUIPMENT AND PANEL BOARDS. NEC 110.26,
 240.24, 408.17
  
 A FIRE ALARM SYSTEM IS REQUIRED FOR THIS FACILITY. A
 SEPARATE PERMIT WITH PLAN AND SHOP DRAWINGS IS
 REQUIRED. NFPA 101 15.3.4, FBC 907.2.3
  
 VERIFY THE MEANS OF EGRESS HAS EMERGENCY ILLUMINATION
 AND EXIT SIGNS. FBC 1006.2 1011.1
  
 VERIFY COMPLIANCE WITH REQUIRED ILLUMINATION LEVEL,
 UNIFORMITY, BRIGHTNESS AND GLARE IN
 CLASSROOMS/INSTRUCTION SPACES. FBC 443.3.7
  
 GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS.
 NEC 422.52
  
 VENDING MACHINES IF PROVIDED SHALL BE PROTECTED WITH
 GFCI?S. NEC 422.51
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS MUST
 BE GFCI PROTECTED. NEC 210.8
  
 NOTE:
 SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE,
 DATA, FIRE ALARM, AND SECURITY.
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
 561-805-6718
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2013-12-18 Cont ID  
Sent By rferguso Date 2013-12-18 Time 09:34 Rev Time 0.00
Received By rferguso Date 2013-12-18 Time 09:33 Sent To  
Notes
2013-12-18 10:09:36901 NORTHPOINT PARKWAY SUITE #400-404
 PERMIT #13060868
  
 WEST PALM BEACH FIRE RESCUE PLAN REVIEW COMMENTS.
  
 * PLAN (APPROVED, PROVISO), ALL ITEMS LISTED ON
 12/12/2013'S REVIEW IS ADDRESSED.
  
 RONALD E. FERGUSON, ASSISTANT FIRE MARSHAL
 BUREAU OF FIRE PREVENTION
 WEST PALM BEACH FIRE RESCUE
 PHONE #(561) 804-4700

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2013-12-12 Cont ID  
Sent By rferguso Date 2013-12-12 Time 11:29 Rev Time 0.00
Received By rferguso Date 2013-12-12 Time 11:29 Sent To M
Notes
2013-12-12 11:45:30901 NORTHPOINT PARKWAY, SUITE 400-404
 PERMIT #13060868
  
 WEST PALM BEACH FIRE RESCUE PLAN REVIEW COMMENTS.
  
 ** BE SPECIFIC ON THE PLAN OF WHAT DOORS ARE TO BE
 OUTFITTED WITH PANIC HARDWEAR.
 ** NO EMERGENCY LIGHTS ARE BEING SHOWN ON THE PLANS.
 ** SUBMIT SEPERATE PLANS FOR THE FIRE ALARM SYSTEM.
  
  
 RONALD E. FERGUSON, ASSISTANT FIRE MARSHAL
 BUREAU OF FIRE PREVENTION
 WEST PALM BEACH FIRE RESCUE
 PHONE #(561) 804-4700

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-08-09 Cont ID  
Sent By rfergso Date 2013-08-09 Time 15:12 Rev Time 0.00
Received By scaldero Date 2013-08-09 Time 15:12 Sent To  
Notes
2013-08-09 15:27:09PERMIT #13060868
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A SCALABLE PLAN.
  
 STORAGE ROOMS SHALL BE SEPERATED FROM THE OTHER ROOMS
 WITH A 1-HOUR RATED FIRE WALL AND 45-MINUTE FIRE RATED
 DOOR.
  
 EXIT ACCESS CORRIDORS SHALL BE AT LEAST 6 FEET IN
 WIDTH.
  
 CORRIDORS SHALL BE SEPERATED FROM OTHER AREAS WITH A
 1-HOUR RATED BARRIER AND A 45-MINUTE DOOR.
  
 AN ACCURATE AND DETAILED FURNITURE PLAN MUST BE
 SUBMITTED.
  
 CLUSTER OF OFFICES EXCEEDS 10 PERCENT OF THE OVERALL
 SPACE USED, CLASSIFYING IT AS A NON-SEPERATED MIXED USE
 OCCUPANCY.
 THE LARGE CLASSROOM AREA (LABELED "CAFETERIA" IN THE
 ORIGINAL PLANS) HAS AN AREA WHICH RESULTS IN AN
 OCCUPANT LOAD GREATER THAN 50 PERSONS, CLASSIFYING IT
 AS AN ASSEMBLY OCCUPANCY.
 FOR NON-SEPARATED MIXED USE OCCUPANCIES, THE MOST
 STRINGENT FIRE AND LIFE SAFETY REQUIREMENTS OF EACH
 OCCUPANCY SHALL APPLY TO THE BUILDING.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY
 LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
 THE LOCATIONS OF THE EXIT SIGNS AND EMERGENCY LIGHTS
 MUST BE CLEARLY IDENTIFIED.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 ALL ROOMS SHOULD BE DESIGNATED WITH A NAME OR FUNCTION.
  
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-06-28 Cont ID  
Sent By rferguso Date 2013-06-28 Time 15:28 Rev Time 0.00
Received By rferguso Date 2013-06-28 Time 15:28 Sent To B
Notes
2013-06-28 15:59:02901 NORTHPOINT PARKWAY #400-401
 PERMIT #13060868
  
 WEST PALM BEACH FIRE RESCUE PLAN REVIEW COMMENTS.
  
 1) STORAGE ROOMS SHALL BE SEPERATED FROM THE OTHER
 ROOMS WITH A 1- HOUR FIRE - RATED WALL AND 45 - MIN.
 FIRE RATED DOORS.
  
 2) EXIT ACCESS CORRIDORS SHALL BE AT LEAST 6 - FEET IN
 WIDTH.
  
 3) CORRIDORS SHALL BE SEPERATED FROM OTHER AREAS WITH A
 1 - HOUR FIRE RATED BARRIER AND 45 - MIN. FIRE RATED
 DOORS.
  
 4) FURNITURE PLANS MUST BE SUBMITTED.
  
 5) THE PLAN INDICATES NON - FILES SEPERATED, MIXED USE
 OCCUPANCIES, (EDUCATION AND ASSEMBLY). THE MOST
 STRINGENT OCCUPANTCY REQUIRMENTS APPLY. FOR EXAMPLE, AN
 ASSEMBLY OCCUPANCY WITH 300 + PERSONS IS REQUIERED TO
 BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM WHEREAS
 EDUCATIONAL OCCUPANCIES REQUIRE A SPRINKLER SYSTEM IF
 THE FLOOR AREA EXCEED 12,000 SQ. FT.
  
 6) A LIFE SAFETY PLAN IS NEEDED SHOWING FIRE RATED
 WALLS, EXIT SIGNS, EMERGENCY LIGHTING, FIRE ALARM
 DEVICES, PANIC HARDWARE LOCATIONS, ETC.
  
  
  
 RONALD E. FERGUSON, ASSISTANT FIRE MARSHAL
 BUREAU OF FIRE PREVENTIO
 WEST PALM BEACH FIRE RESCUE
 PHONE #(561) 804-4700

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-12-19 Cont ID  
Sent By jlmitch Date 2013-12-19 Time 08:15 Rev Time 0.00
Received By jlmitch Date 2013-12-19 Time 08:15 Sent To  
Notes
2013-12-17 18:19:55TO RF DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-12-14 Cont ID  
Sent By hmoser Date 2013-12-14 Time 07:30 Rev Time 0.00
Received By hmoser Date 2013-10-28 Time 11:36 Sent To  
Notes
2013-10-29 11:37:17SENT TO B2 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-12 Cont ID  
Sent By shill Date 2013-08-12 Time 11:40 Rev Time 0.00
Received By shill Date 2013-08-05 Time 12:09 Sent To  
Notes
2013-08-05 12:09:54B12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-01 Cont ID  
Sent By shill Date 2013-07-01 Time 12:40 Rev Time 0.00
Received By shill Date 2013-06-25 Time 08:53 Sent To  
Notes
2013-06-25 08:53:12TO LEW DESK
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-11-25 Cont ID  
Sent By shill Date 2013-11-25 Time 12:46 Rev Time 0.00
Received By shill Date 2013-11-25 Time 12:46 Sent To  
Notes
2013-11-25 12:47:10NO FEES DUE (CHARTER SCHOOL)
 PALM BEACH COUNTY STAMP SHOWS 8825 SF AND $0 DUE
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-07-01 Cont ID  
Sent By shill Date 2013-07-01 Time 12:39 Rev Time 0.00
Received By shill Date 2013-07-01 Time 12:39 Sent To  
Notes
2013-07-01 12:40:25SEE BUILDING COMMENTS
  
 561-233-5025 FOR IMPACT FEE INFORMATOIN

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-12-14 Cont ID  
Sent By hmoser Date 2013-12-14 Time 07:30 Rev Time 0.00
Received By hmoser Date 2013-12-14 Time 06:59 Sent To  
Notes
2013-12-14 07:30:35PASS PROVISO
 REVISION REQUIRED WITH FRESH AIR CALCULATIONS.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-08-05 Cont ID  
Sent By hmoser Date 2013-08-05 Time 14:17 Rev Time 0.00
Received By hmoser Date 2013-08-05 Time 14:14 Sent To  
Notes
2013-08-05 14:17:30PLANS DENIED
 PROVIDE FRESH AIR CALCULATIONS ON THE PLANS.
 PER TABLE 403.3 FBC (M) 2010
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-06-25 Cont ID  
Sent By hmoser Date 2013-06-25 Time 16:25 Rev Time 0.00
Received By hmoser Date 2013-06-25 Time 15:58 Sent To  
Notes
2013-06-25 16:25:14PASS PROVISO
 PROVIDE A REVISION SHOWING FRESH AIR
 CALCULATIONS PER TABLE 403.3 MINIMUM
 VENTILATION RATES 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2013-11-04 Cont ID  
Sent By lwagner Date 2013-11-04 Time 09:08 Rev Time 0.00
Received By lwagner Date 2013-11-04 Time 08:58 Sent To  
Notes
2013-10-29 11:34:49NEW SHEETS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-08-09 Cont ID  
Sent By lwagner Date 2013-08-09 Time 07:30 Rev Time 0.00
Received By lwagner Date 2013-08-09 Time 07:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-06-27 Cont ID  
Sent By lwagner Date 2013-06-27 Time 08:56 Rev Time 0.00
Received By lwagner Date 2013-06-27 Time 08:36 Sent To  
Notes
2013-06-27 09:11:01***PROVISO***
  
 HIGH / LOW DRINKING FOUNTAIN REQUIRED

Review Stop Z ZONING
Rev No 1 Status P Date 2013-06-27 Cont ID  
Sent By ajones Date 2013-06-27 Time 09:24 Rev Time 0.00
Received By ajones Date 2013-06-27 Time 09:24 Sent To  
Notes
2013-06-27 09:25:486/27/13- APPROVED. SCHOOLS ARE PERMITTED IN BY RIGHT IN
 NORTHPOINT.
  
 ANGELLA VANN
 561-822-1441
 [email protected]