Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-06-24 Cont ID  
Sent By mcarsill Date 2013-06-24 Time 15:20 Rev Time 0.00
Received By mcarsill Date 2013-06-24 Time 15:16 Sent To  
Notes
2013-06-24 15:20:29FIRE ALARM SYSTEM ADDITIONS
 TOMMY BAHAMAS
 701 SOUTH ROSEMARY AVENUE
 PERMIT # 13060838
  
 1. FIRE ALARM INSTALLATIONS TO COMPLY WITH NFPA 72, THE
 NATIONAL FIRE ALARM CODE.
  
 2. NOTE # 15 IS INCORRECT. DUCT DETECTORS WHEN
 ACTIVATED SHALL CAUSE A FIRE ALARM SYSTEM ACTIVATION
 NOT A SUPERVISORY SIGNAL AS PER LOCAL REQUIREMENTS.
  
 APPROVED PROVISO
  
  
 MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF
 WEST PALM BEACH FIRE RESCUE