Plan Review Details - Permit 13060815
Plan Review Stops For Permit 13060815
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2014-04-26 Cont ID  
Sent By jwitmer Date 2014-04-26 Time 06:44 Rev Time 0.00
Received By jwitmer Date 2014-04-26 Time 06:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2014-04-22 Cont ID  
Sent By jwitmer Date 2014-04-22 Time 08:13 Rev Time 0.00
Received By jwitmer Date 2014-04-22 Time 07:44 Sent To  
Notes
2014-04-22 08:13:07BUILDING PLAN REVIEW
 PERMIT: 13060815
 ADD: 2823 N AUSTRALIAN AVE
 CONT: BLACKBURN BUILDING CO
 TEL: (561)775-5653
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: TUESDAY APRIL 22/2014
 ACTION: DENIED
  
 NOTE SCOPE OF WORK HAS CHANGED, PHASES II & III WERE
 ADDED IN THE SCOPE OF THIS PERMIT.
  
 1) 2ND REQUEST, PLEASE REVIEW SHEETS A1.02 AND THE
 ROOMS 220 & 221, BOTH SHOWING THE USE OF ACCORDIAN
 DOORS. WHEN THE ACCORDIAN DOOR BETWEEN THE 2 ROOMS IS
 PULLED BACK CREATING ONE LARGE ROOM THE OCCUPANT LOAD
 IS 17 COMBINED. THE 2010 FBC-B 1008.1.2 DOOR SWING.
 EGRESS DOORS SHALL BE OF THE PIVOTED OR SIDE-HINGED
 SWINGING TYPE.
 EXCEPTIONS:
 1. PRIVATE GARAGES, OFFICE AREAS, FACTORY AND STORAGE
 AREAS WITH AN OCCUPANT LOAD OF 10 OR LESS.
  
 2) SHEET A2.02 CORRIDOR WALLS ARE DESIGNATED AS A SMOKE
 WALL FP1, P2, & FP6, THERE IS NO DETAIL INDICATING THIS
 WALL GOING TO THE TOP OF THE DECK ABOVE OR TO THE FLOOR
 INDICATING IT TO BE A SMOKE PARTITION. 711.4
 CONTINUITY.
 SMOKE PARTITIONS SHALL EXTEND FROM THE TOP OF THE
 FOUNDATION OR FLOOR BELOW TO THE UNDERSIDE OF THE FLOOR
 OR ROOF SHEATHING, DECK OR SLAB ABOVE OR TO THE
 UNDERSIDE OF THE CEILING ABOVE WHERE THE CEILING
 MEMBRANE IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE.
  
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-04-11 Cont ID  
Sent By JWITMER Date 2014-04-11 Time 12:36 Rev Time 0.00
Received By jwitmer Date 2014-04-11 Time 11:29 Sent To  
Notes
2014-04-11 12:36:33BUILDING PLAN REVIEW
 PERMIT: 13060815
 ADD: 2823 N AUSTRALIAN AVE
 CONT: BLACKBURN BUILDING CO
 TEL: (561)775-5653
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRIDAY APRIL 11/2014
 ACTION: DENIED
  
 NOTE SCOPE OF WORK HAS CHANGED, PHASES II & III WERE
 ADDED IN THE SCOPE OF THIS PERMIT.
  
 1) PLEASE REVIEW SHEETS A1.02 AND THE ROOMS 220 & 221,
 BOTH SHOWING THE USE OF ACCORDIAN DOORS. WHEN THE
 ACCORDIAN DOOR BETWEEN THE 2 ROOMS IS PULLED BACK
 CREATING ONE LARGE ROOM THE OCCUPANT LOAD IS 17
 COMBINED. THE 2010 FBC-B 1008.1.2 DOOR SWING.
 EGRESS DOORS SHALL BE OF THE PIVOTED OR SIDE-HINGED
 SWINGING TYPE.
 EXCEPTIONS:
 1. PRIVATE GARAGES, OFFICE AREAS, FACTORY AND STORAGE
 AREAS WITH AN OCCUPANT LOAD OF 10 OR LESS.
  
 2) SHEET A1.02 CORRIDOR WALLS ARE DESIGNATED AS A SMOKE
 WALL P2, DOES NOT INDICATE THE WALL GOING TO THE TOP OF
 THE DECK ABOVE OR TO THE FLOOR INDICATING IT TO BE A
 SMOKE PARTITION. 711.4 CONTINUITY.
 SMOKE PARTITIONS SHALL EXTEND FROM THE TOP OF THE
 FOUNDATION OR FLOOR BELOW TO THE UNDERSIDE OF THE FLOOR
 OR ROOF SHEATHING, DECK OR SLAB ABOVE OR TO THE
 UNDERSIDE OF THE CEILING ABOVE WHERE THE CEILING
 MEMBRANE IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE.
  
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-08-20 Cont ID  
Sent By jwitmer Date 2013-08-20 Time 11:34 Rev Time 0.00
Received By jwitmer Date 2013-08-20 Time 11:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-05 Cont ID  
Sent By jwitmer Date 2013-07-05 Time 14:47 Rev Time 0.00
Received By jwitmer Date 2013-07-05 Time 14:47 Sent To  
Notes
2013-07-05 15:20:57BUILDING PLAN REVIEW
 PERMIT: 13060815
 ADD: 2823 N AUSTRALIAN AVE
 CONT: BLACKBURN BUILDING CO
 TEL: (561)775-5653
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 07/2013
 ACTION: DENIED
  
 1) THE COVERSHEET A0.00 UNDER THE HEADING PROJECT
 DESCRIPTION INDICATES 2ND FLOOR FROM A FREE CLINIC TO
 AFTER SCHOOL TRAINING & DEVELOPMENT FOR MIDDLE AND HIGH
 SCHOOL YOUTH. THIS IS A CHANGE OF OCCUPANCY FROM A (B)
 BUSINESS OCCUPANCY TO (E) EDUCATIONAL OCCUPANCY. FBC-B
 305.1 EDUCATIONAL GROUP E. EDUCATIONAL GROUP E
 OCCUPANCY INCLUDES, AMONG OTHERS, THE USE OF A BUILDING
 OR STRUCTURE, OR A PORTION THEREOF, BY SIX OR MORE
 PERSONS AT ANY ONE TIME FOR EDUCATIONAL PURPOSES
 THROUGH THE 12TH GRADE.
 2010 FBC-B 901.3.1 PARTIAL CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE A PORTION OF AN EXISTING BUILDING
 IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION
 912 SHALL APPLY.
  
 1A) THE COVER SHEET NEEDS TO UPDATE THE 2010 FBC'S
 FAMILY OF CODES, PLUMBING, MECHANICAL & ACCESSIBILITY
 TO 2010. ALL ADOPTED IN MARCH 15/ 2012. THE 2012
 SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2) THE DESIGNER OF RECORD WILL NEED TO DECLARE EXST
 BLDG 912.1.1 COMPLIANCE WITH CHAPTER 8. THE
 REQUIREMENTS OF CHAPTER 8 SHALL BE APPLICABLE
 THROUGHOUT THE BUILDING FOR THE NEW OCCUPANCY
 CLASSIFICATION BASED ON THE SEPARATION CONDITIONS SET
 FORTH IN SECTIONS 912.1.1.1 AND 912.1.1.2.
  
 3) SHEET A1.02 INDICATES THE CENTRAL STAIR IS NOT A
 REQUIRED EGRESS STAIR PLEASE SHOW COMPLIANCE WITH: 2010
 EXST BLDG CODE 912.4.1 MEANS OF EGRESS FOR CHANGE TO
 HIGHER HAZARD CATEGORY.
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING. PROVIDE MEANS OF EGRESS TO THE PUBLIC
 WAY FOR STAIR 2 & 3 FOR CHANGE OF USE TO A HIGHER
 HAZARD CLASSIFICATION.
  
 4) PLEASE DESIGNATE WALL TYPE FOR THE SECOND FLOOR
 CORRIDOR, SEE 2010 FBC-B TABLE 1018.1 FOOTNOTE "C"
 CORRIDOR WALLS ARE TO BE SMOKE PARTITIONS IN ACCORDANCE
 WITH THE FIRE PREVENTION CODE.
  
 5) PLEASE REVIEW DOOR HARDWARE REQUIREMENTS FOR THE NEW
 EDUCATIONAL OCCUPANCY UNDER 2010 FBC-B 1008.1.10 PANIC
 HARDWARE REQUIREMENTS FOR OCCUPANT LOADS OF 50 OR MORE
 IN (E) OCCUPANCIES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-05-01 Cont ID  
Sent By DHARVEY Date 2014-05-01 Time 11:39 Rev Time 0.00
Received By rlecky Date 2014-05-01 Time 11:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-09-09 Cont ID  
Sent By dharvey Date 2013-09-09 Time 13:34 Rev Time 0.00
Received By dharvey Date 2013-09-09 Time 13:34 Sent To  
Notes
2013-09-09 13:35:04SUPPLEMENTAL REVIEW - 9-25-13
  
 THIS REVIEW WAS DONE WITH CONSIDERATION THAT THIS IS A
 BUSINESS FACILTY AS OPPOSED TO AN EDUCATIONAL FACILTY.
 THE FOLLOWING CORRECTIONS ARE REQUIRED.
  
 1. PLEASE PROVIDE AN ELECRICAL DRAWING SHOWING ALL
 ELECTRICAL BOTH EXISTING AND NEW. PLEASE INCLUDE
 CIRCUIT NUMBERS ON THE FLOOR PLAN AS WELL.
  
 2. PLEASE PROVIDE A PANEL SCHEDULE SHOWING ALL REQUIRED
 INFORMATION PER NEC 408.4
  
 3. PROVIDE GFCI PROTECTION FOR WATER COOLERS PER NEC
 422.52
  
 END REVIEW
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-07-08 Cont ID  
Sent By dharvey Date 2013-07-08 Time 09:54 Rev Time 0.00
Received By dharvey Date 2013-07-08 Time 09:37 Sent To  
Notes
2013-07-08 09:56:5213060815
 2823 N. AUSTRALIAN AVE. BLDG. 2
 NEW EDUCATIONAL FACILITY
  
 THE SCOPE OF THE PROPOSED ELECTRICAL WORK IS NOT CLEAR.
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A PLAN SHOWING THE ELECTRICAL SYSTEM. SHOW ALL
 NEW AND EXISTING ELECTRICAL OUTLETS INCLUDING LIGHTING.
  
 VERIFY THAT THE REQUIRED WORKING CLEARANCES AND
 DEDICATED WORKING SPACE HAS BEEN PROVIDED FOR THE
 ELECTRICAL EQUIPMENT AND PANEL BOARDS. NEC 110.26,
 240.24, 408.17
  
 A FUNCTIONING FIRE ALARM SYSTEM IS REQUIRED FOR THIS
 FACILITY. NFPA 101 15.3.4, FBC 907.2.3
  
 VERIFY COMPLIANCE WITH REQUIRED ILLUMINATION LEVEL,
 UNIFORMITY, BRIGHTNESS AND GLARE IN
 CLASSROOMS/INSTRUCTION SPACES. FBC 443.3.7
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLANS SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. 2010 FBC ENERGY CONSERVATION T505.3
  
 GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS.
 NEC 422.52
  
 VENDING MACHINES IF PROVIDED SHALL BE PROTECTED WITH
 GFCI?S. NEC 422.51
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS MUST
 BE GFCI PROTECTED. NEC 210.8
  
 NOTE:
 SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE,
 DATA, FIRE ALARM, AND SECURITY.
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2014-04-25 Cont ID  
Sent By wjolin Date 2014-04-25 Time 13:54 Rev Time 0.00
Received By wjolin Date 2014-04-25 Time 13:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2014-04-24 Cont ID  
Sent By wjolin Date 2014-04-24 Time 12:39 Rev Time 0.00
Received By wjolin Date 2014-04-24 Time 12:39 Sent To  
Notes
2014-04-24 12:39:20BUILDING REVIEW AND FIRE REVIEW COMMENTS ARE THE SAME;
 PLEASE REFER TO BUILDING REVIEWER COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2014-04-11 Cont ID  
Sent By WJOLIN Date 2014-04-11 Time 15:10 Rev Time 0.00
Received By wjolin Date 2014-04-11 Time 15:10 Sent To  
Notes
2014-04-11 15:11:07BUILDING REVIEW AND FIRE REVIEW COMMENTS ARE THE SAME;
 PLEASE REFER TO BUILDING REVIEWER COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-08-20 Cont ID  
Sent By wjolin Date 2013-08-20 Time 17:15 Rev Time 0.00
Received By wjolin Date 2013-08-20 Time 17:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-07-03 Cont ID  
Sent By wjolin Date 2013-07-03 Time 11:03 Rev Time 0.00
Received By wjolin Date 2013-07-03 Time 09:29 Sent To  
Notes
2013-07-03 11:03:162823 NORTH AUSTRALIAN AVENUE - BUILDING #2
 PERMIT #13060815
 REVIEW COMMENTS - FIRE DEPARTMENT
 *****CHANGE OF OCCUPANCY FROM BUSINESS TO
 EDUCATIONAL*****
  
 THE SCOPE OF WORK APPEARS TO BE A CHANGE OF OCCUPANCY
 FROM BUSINESS (ADULT OUTPATIENT CLINIC) TO AN
 EDUCATIONAL OCCUPANCY OF TRAINING AND SKILLS
 DEVELOPMENT OF MIDDLE SCHOOL AND HIGH SCHOOL AGE
 CHILDREN. NFPA 101 - THE LIFE SAFETY CODE DEFINES
 EDUCATIONAL OCCUPANCY AS AN OCCUPANCY USED FOR
 EDUCATIONAL PURPOSES THROUGH THE TWELFTH GRADE BY SIX
 OR MORE PERSONS FOR 4 OR MORE HOURS PER DAY OR MORE
 THAN 12 HOURS PER WEEK. WHEREAS A BUSINESS OCCUPANCY IS
 DEFINED AS AN OCCUPANCY USED FOR THE TRANSACTION OF
 BUSINESS OTHER THAN MERCANTILE.
  
 CORRIDOR WALLS SHALL BE CONSTRUCTED TO FORM SMOKE
 PARTITIONS IN A FULLY SPRINKLERED BUILDING PER SECTION
 14.3.6(2)(A) OF NFPA 101.
  
 FOR EDUCATIONAL OCCUPANCIES WITH AN OCCUPANT LOAD OF
 100 OR MORE PERSONS (50 PERSONS PER THE FLORIDA
 BUILDING CODE), PANIC/FIRE EXIT HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE.
  
 THE CENTRAL STAIR IS INDICATED AS "NOT A RQUIRED EXIT."
 IF THIS STAIR WILL NOT BE UTILIZED AS AN EXIT, THE
 STAIR DOORS SHALL BE PERMANENTLY AND OBVIOUSLY
 IDENTIFIED WITH SIGNAGE INDICATING "NO EXIT."
  
 PROVIDE A PLAN SHOWING THE EXIT DISCHARGE FOR STAIR #2
 AND #3.
  
 ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 50 PERCENT OF THE INDIVIDUAL WALL
 AREA.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-05-01 Cont ID  
Sent By rlecky Date 2014-05-01 Time 11:40 Rev Time 0.00
Received By rlecky Date 2014-04-04 Time 14:33 Sent To  
Notes
2014-04-08 14:34:35B16
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-05-01 Cont ID  
Sent By rlecky Date 2014-05-01 Time 11:40 Rev Time 0.00
Received By rlecky Date 2014-03-26 Time 08:15 Sent To  
Notes
2014-03-27 08:15:32B16

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-09-09 Cont ID  
Sent By dharvey Date 2013-09-09 Time 13:35 Rev Time 0.00
Received By dharvey Date 2013-09-09 Time 13:35 Sent To  
Notes
2013-08-14 13:32:16SENT TO B16 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-15 Cont ID  
Sent By hmoser Date 2013-07-15 Time 09:44 Rev Time 0.00
Received By hmoser Date 2013-06-21 Time 14:36 Sent To  
Notes
2013-06-24 14:37:21SENT TO B10 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-04-24 Cont ID  
Sent By hmoser Date 2014-04-24 Time 14:13 Rev Time 0.00
Received By hmoser Date 2014-04-24 Time 13:35 Sent To  
Notes
2014-04-24 14:12:29PASS PROVISO
 REFER TO SECTION 503.2.4.4
 SHUTOFF DAMPER CONTROLS
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-9805-6676
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-07-15 Cont ID  
Sent By hmoser Date 2013-07-15 Time 09:43 Rev Time 0.00
Received By hmoser Date 2013-07-15 Time 09:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-06-27 Cont ID  
Sent By lwagner Date 2013-06-27 Time 14:39 Rev Time 0.00
Received By lwagner Date 2013-06-27 Time 14:13 Sent To  
Notes
2013-06-27 14:40:01NO PLUMBING SHOWN AT THIS TIME.

Review Stop Z ZONING
Rev No 1 Status N Date 2013-07-10 Cont ID  
Sent By ajones Date 2013-07-10 Time 15:01 Rev Time 0.00
Received By ajones Date 2013-07-10 Time 15:01 Sent To  
Notes
***NONE***