| Plan Review Stops For Permit 13060815 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2014-04-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-04-26 |
Time |
06:44 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-04-26 |
Time |
06:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2014-04-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-04-22 |
Time |
08:13 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-04-22 |
Time |
07:44 |
Sent To |
|
|
| Notes |
| 2014-04-22 08:13:07 | BUILDING PLAN REVIEW | | | PERMIT: 13060815 | | | ADD: 2823 N AUSTRALIAN AVE | | | CONT: BLACKBURN BUILDING CO | | | TEL: (561)775-5653 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 4TH REVIEW | | | DATE: TUESDAY APRIL 22/2014 | | | ACTION: DENIED | | | | | | NOTE SCOPE OF WORK HAS CHANGED, PHASES II & III WERE | | | ADDED IN THE SCOPE OF THIS PERMIT. | | | | | | 1) 2ND REQUEST, PLEASE REVIEW SHEETS A1.02 AND THE | | | ROOMS 220 & 221, BOTH SHOWING THE USE OF ACCORDIAN | | | DOORS. WHEN THE ACCORDIAN DOOR BETWEEN THE 2 ROOMS IS | | | PULLED BACK CREATING ONE LARGE ROOM THE OCCUPANT LOAD | | | IS 17 COMBINED. THE 2010 FBC-B 1008.1.2 DOOR SWING. | | | EGRESS DOORS SHALL BE OF THE PIVOTED OR SIDE-HINGED | | | SWINGING TYPE. | | | EXCEPTIONS: | | | 1. PRIVATE GARAGES, OFFICE AREAS, FACTORY AND STORAGE | | | AREAS WITH AN OCCUPANT LOAD OF 10 OR LESS. | | | | | | 2) SHEET A2.02 CORRIDOR WALLS ARE DESIGNATED AS A SMOKE | | | WALL FP1, P2, & FP6, THERE IS NO DETAIL INDICATING THIS | | | WALL GOING TO THE TOP OF THE DECK ABOVE OR TO THE FLOOR | | | INDICATING IT TO BE A SMOKE PARTITION. 711.4 | | | CONTINUITY. | | | SMOKE PARTITIONS SHALL EXTEND FROM THE TOP OF THE | | | FOUNDATION OR FLOOR BELOW TO THE UNDERSIDE OF THE FLOOR | | | OR ROOF SHEATHING, DECK OR SLAB ABOVE OR TO THE | | | UNDERSIDE OF THE CEILING ABOVE WHERE THE CEILING | | | MEMBRANE IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE. | | | | | | | | | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2014-04-11 |
|
|
Cont ID |
|
| Sent By |
JWITMER |
Date |
2014-04-11 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-04-11 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2014-04-11 12:36:33 | BUILDING PLAN REVIEW | | | PERMIT: 13060815 | | | ADD: 2823 N AUSTRALIAN AVE | | | CONT: BLACKBURN BUILDING CO | | | TEL: (561)775-5653 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: FRIDAY APRIL 11/2014 | | | ACTION: DENIED | | | | | | NOTE SCOPE OF WORK HAS CHANGED, PHASES II & III WERE | | | ADDED IN THE SCOPE OF THIS PERMIT. | | | | | | 1) PLEASE REVIEW SHEETS A1.02 AND THE ROOMS 220 & 221, | | | BOTH SHOWING THE USE OF ACCORDIAN DOORS. WHEN THE | | | ACCORDIAN DOOR BETWEEN THE 2 ROOMS IS PULLED BACK | | | CREATING ONE LARGE ROOM THE OCCUPANT LOAD IS 17 | | | COMBINED. THE 2010 FBC-B 1008.1.2 DOOR SWING. | | | EGRESS DOORS SHALL BE OF THE PIVOTED OR SIDE-HINGED | | | SWINGING TYPE. | | | EXCEPTIONS: | | | 1. PRIVATE GARAGES, OFFICE AREAS, FACTORY AND STORAGE | | | AREAS WITH AN OCCUPANT LOAD OF 10 OR LESS. | | | | | | 2) SHEET A1.02 CORRIDOR WALLS ARE DESIGNATED AS A SMOKE | | | WALL P2, DOES NOT INDICATE THE WALL GOING TO THE TOP OF | | | THE DECK ABOVE OR TO THE FLOOR INDICATING IT TO BE A | | | SMOKE PARTITION. 711.4 CONTINUITY. | | | SMOKE PARTITIONS SHALL EXTEND FROM THE TOP OF THE | | | FOUNDATION OR FLOOR BELOW TO THE UNDERSIDE OF THE FLOOR | | | OR ROOF SHEATHING, DECK OR SLAB ABOVE OR TO THE | | | UNDERSIDE OF THE CEILING ABOVE WHERE THE CEILING | | | MEMBRANE IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE. | | | | | | | | | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2013-08-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-08-20 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-08-20 |
Time |
11:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-07-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-07-05 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-07-05 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2013-07-05 15:20:57 | BUILDING PLAN REVIEW | | | PERMIT: 13060815 | | | ADD: 2823 N AUSTRALIAN AVE | | | CONT: BLACKBURN BUILDING CO | | | TEL: (561)775-5653 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: JULY 07/2013 | | | ACTION: DENIED | | | | | | 1) THE COVERSHEET A0.00 UNDER THE HEADING PROJECT | | | DESCRIPTION INDICATES 2ND FLOOR FROM A FREE CLINIC TO | | | AFTER SCHOOL TRAINING & DEVELOPMENT FOR MIDDLE AND HIGH | | | SCHOOL YOUTH. THIS IS A CHANGE OF OCCUPANCY FROM A (B) | | | BUSINESS OCCUPANCY TO (E) EDUCATIONAL OCCUPANCY. FBC-B | | | 305.1 EDUCATIONAL GROUP E. EDUCATIONAL GROUP E | | | OCCUPANCY INCLUDES, AMONG OTHERS, THE USE OF A BUILDING | | | OR STRUCTURE, OR A PORTION THEREOF, BY SIX OR MORE | | | PERSONS AT ANY ONE TIME FOR EDUCATIONAL PURPOSES | | | THROUGH THE 12TH GRADE. | | | 2010 FBC-B 901.3.1 PARTIAL CHANGE OF OCCUPANCY | | | CLASSIFICATION. WHERE A PORTION OF AN EXISTING BUILDING | | | IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION | | | 912 SHALL APPLY. | | | | | | 1A) THE COVER SHEET NEEDS TO UPDATE THE 2010 FBC'S | | | FAMILY OF CODES, PLUMBING, MECHANICAL & ACCESSIBILITY | | | TO 2010. ALL ADOPTED IN MARCH 15/ 2012. THE 2012 | | | SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2) THE DESIGNER OF RECORD WILL NEED TO DECLARE EXST | | | BLDG 912.1.1 COMPLIANCE WITH CHAPTER 8. THE | | | REQUIREMENTS OF CHAPTER 8 SHALL BE APPLICABLE | | | THROUGHOUT THE BUILDING FOR THE NEW OCCUPANCY | | | CLASSIFICATION BASED ON THE SEPARATION CONDITIONS SET | | | FORTH IN SECTIONS 912.1.1.1 AND 912.1.1.2. | | | | | | 3) SHEET A1.02 INDICATES THE CENTRAL STAIR IS NOT A | | | REQUIRED EGRESS STAIR PLEASE SHOW COMPLIANCE WITH: 2010 | | | EXST BLDG CODE 912.4.1 MEANS OF EGRESS FOR CHANGE TO | | | HIGHER HAZARD CATEGORY. | | | WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A | | | HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE | | | 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE | | | REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING | | | CODE, BUILDING. PROVIDE MEANS OF EGRESS TO THE PUBLIC | | | WAY FOR STAIR 2 & 3 FOR CHANGE OF USE TO A HIGHER | | | HAZARD CLASSIFICATION. | | | | | | 4) PLEASE DESIGNATE WALL TYPE FOR THE SECOND FLOOR | | | CORRIDOR, SEE 2010 FBC-B TABLE 1018.1 FOOTNOTE "C" | | | CORRIDOR WALLS ARE TO BE SMOKE PARTITIONS IN ACCORDANCE | | | WITH THE FIRE PREVENTION CODE. | | | | | | 5) PLEASE REVIEW DOOR HARDWARE REQUIREMENTS FOR THE NEW | | | EDUCATIONAL OCCUPANCY UNDER 2010 FBC-B 1008.1.10 PANIC | | | HARDWARE REQUIREMENTS FOR OCCUPANT LOADS OF 50 OR MORE | | | IN (E) OCCUPANCIES. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2014-05-01 |
|
|
Cont ID |
|
| Sent By |
DHARVEY |
Date |
2014-05-01 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2014-05-01 |
Time |
11:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2013-09-09 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-09-09 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-09-09 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2013-09-09 13:35:04 | SUPPLEMENTAL REVIEW - 9-25-13 | | | | | | THIS REVIEW WAS DONE WITH CONSIDERATION THAT THIS IS A | | | BUSINESS FACILTY AS OPPOSED TO AN EDUCATIONAL FACILTY. | | | THE FOLLOWING CORRECTIONS ARE REQUIRED. | | | | | | 1. PLEASE PROVIDE AN ELECRICAL DRAWING SHOWING ALL | | | ELECTRICAL BOTH EXISTING AND NEW. PLEASE INCLUDE | | | CIRCUIT NUMBERS ON THE FLOOR PLAN AS WELL. | | | | | | 2. PLEASE PROVIDE A PANEL SCHEDULE SHOWING ALL REQUIRED | | | INFORMATION PER NEC 408.4 | | | | | | 3. PROVIDE GFCI PROTECTION FOR WATER COOLERS PER NEC | | | 422.52 | | | | | | END REVIEW | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-07-08 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-07-08 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-07-08 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2013-07-08 09:56:52 | 13060815 | | | 2823 N. AUSTRALIAN AVE. BLDG. 2 | | | NEW EDUCATIONAL FACILITY | | | | | | THE SCOPE OF THE PROPOSED ELECTRICAL WORK IS NOT CLEAR. | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE A PLAN SHOWING THE ELECTRICAL SYSTEM. SHOW ALL | | | NEW AND EXISTING ELECTRICAL OUTLETS INCLUDING LIGHTING. | | | | | | VERIFY THAT THE REQUIRED WORKING CLEARANCES AND | | | DEDICATED WORKING SPACE HAS BEEN PROVIDED FOR THE | | | ELECTRICAL EQUIPMENT AND PANEL BOARDS. NEC 110.26, | | | 240.24, 408.17 | | | | | | A FUNCTIONING FIRE ALARM SYSTEM IS REQUIRED FOR THIS | | | FACILITY. NFPA 101 15.3.4, FBC 907.2.3 | | | | | | VERIFY COMPLIANCE WITH REQUIRED ILLUMINATION LEVEL, | | | UNIFORMITY, BRIGHTNESS AND GLARE IN | | | CLASSROOMS/INSTRUCTION SPACES. FBC 443.3.7 | | | | | | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLANS SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. 2010 FBC ENERGY CONSERVATION T505.3 | | | | | | GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS. | | | NEC 422.52 | | | | | | VENDING MACHINES IF PROVIDED SHALL BE PROTECTED WITH | | | GFCI?S. NEC 422.51 | | | | | | ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS MUST | | | BE GFCI PROTECTED. NEC 210.8 | | | | | | NOTE: | | | SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE, | | | DATA, FIRE ALARM, AND SECURITY. | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2014-04-25 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-04-25 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-04-25 |
Time |
13:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2014-04-24 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-04-24 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-04-24 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2014-04-24 12:39:20 | BUILDING REVIEW AND FIRE REVIEW COMMENTS ARE THE SAME; | | | PLEASE REFER TO BUILDING REVIEWER COMMENTS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2014-04-11 |
|
|
Cont ID |
|
| Sent By |
WJOLIN |
Date |
2014-04-11 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-04-11 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2014-04-11 15:11:07 | BUILDING REVIEW AND FIRE REVIEW COMMENTS ARE THE SAME; | | | PLEASE REFER TO BUILDING REVIEWER COMMENTS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2013-08-20 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2013-08-20 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2013-08-20 |
Time |
17:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2013-07-03 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2013-07-03 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2013-07-03 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2013-07-03 11:03:16 | 2823 NORTH AUSTRALIAN AVENUE - BUILDING #2 | | | PERMIT #13060815 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | *****CHANGE OF OCCUPANCY FROM BUSINESS TO | | | EDUCATIONAL***** | | | | | | THE SCOPE OF WORK APPEARS TO BE A CHANGE OF OCCUPANCY | | | FROM BUSINESS (ADULT OUTPATIENT CLINIC) TO AN | | | EDUCATIONAL OCCUPANCY OF TRAINING AND SKILLS | | | DEVELOPMENT OF MIDDLE SCHOOL AND HIGH SCHOOL AGE | | | CHILDREN. NFPA 101 - THE LIFE SAFETY CODE DEFINES | | | EDUCATIONAL OCCUPANCY AS AN OCCUPANCY USED FOR | | | EDUCATIONAL PURPOSES THROUGH THE TWELFTH GRADE BY SIX | | | OR MORE PERSONS FOR 4 OR MORE HOURS PER DAY OR MORE | | | THAN 12 HOURS PER WEEK. WHEREAS A BUSINESS OCCUPANCY IS | | | DEFINED AS AN OCCUPANCY USED FOR THE TRANSACTION OF | | | BUSINESS OTHER THAN MERCANTILE. | | | | | | CORRIDOR WALLS SHALL BE CONSTRUCTED TO FORM SMOKE | | | PARTITIONS IN A FULLY SPRINKLERED BUILDING PER SECTION | | | 14.3.6(2)(A) OF NFPA 101. | | | | | | FOR EDUCATIONAL OCCUPANCIES WITH AN OCCUPANT LOAD OF | | | 100 OR MORE PERSONS (50 PERSONS PER THE FLORIDA | | | BUILDING CODE), PANIC/FIRE EXIT HARDWARE SHALL BE | | | PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER | | | LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE | | | RELEASED BY THE PANIC HARDWARE. | | | | | | THE CENTRAL STAIR IS INDICATED AS "NOT A RQUIRED EXIT." | | | IF THIS STAIR WILL NOT BE UTILIZED AS AN EXIT, THE | | | STAIR DOORS SHALL BE PERMANENTLY AND OBVIOUSLY | | | IDENTIFIED WITH SIGNAGE INDICATING "NO EXIT." | | | | | | PROVIDE A PLAN SHOWING THE EXIT DISCHARGE FOR STAIR #2 | | | AND #3. | | | | | | ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS | | | SHALL NOT EXCEED 50 PERCENT OF THE INDIVIDUAL WALL | | | AREA. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2014-05-01 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2014-05-01 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2014-04-04 |
Time |
14:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-05-01 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2014-05-01 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2014-03-26 |
Time |
08:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-09-09 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-09-09 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-09-09 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2013-08-14 13:32:16 | SENT TO B16 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-07-15 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-07-15 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-06-21 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2013-06-24 14:37:21 | SENT TO B10 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2014-04-24 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-04-24 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-04-24 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2014-04-24 14:12:29 | PASS PROVISO | | | REFER TO SECTION 503.2.4.4 | | | SHUTOFF DAMPER CONTROLS | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-9805-6676 | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2013-07-15 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-07-15 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-07-15 |
Time |
09:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2013-06-27 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2013-06-27 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-06-27 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2013-06-27 14:40:01 | NO PLUMBING SHOWN AT THIS TIME. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2013-07-10 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2013-07-10 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2013-07-10 |
Time |
15:01 |
Sent To |
|
|
| Notes |
|
|