Plan Review Details - Permit 13060785
Plan Review Stops For Permit 13060785
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-08-08 Cont ID  
Sent By rmcdouga Date 2013-08-08 Time 15:10 Rev Time 0.00
Received By rmcdouga Date 2013-08-08 Time 15:10 Sent To  
Notes
2013-08-08 15:11:53RED-LINED PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-29 Cont ID  
Sent By rmcdouga Date 2013-07-29 Time 11:17 Rev Time 0.00
Received By rmcdouga Date 2013-07-29 Time 07:10 Sent To  
Notes
2013-07-29 10:27:142010 FBC
  
 DENIED BY BUILDING
  
 1) SOME OF THE PROJECT INFORMATION ON SHEET A-1 OF THE
 PLANS FROM ADVANCED DESIGN AND BUILDING IS INCORRECT.
 BASED ON SECTION 310, THE OCCUPANCY TYPE IS R-3.
  
 2) BASED ON SECTION 405 OF THE 2010 FBC EXISTING
 BUILDING, THIS IS A LEVEL 3 ALTERATION AND NOT NEW
 CONSTRUCTION.
  
 3) THE EXPOSURE CATEGORY IS C PER FBC R301.2.1.4.3.
  
 4) THE ROOF DEAD LOAD IS 25 PSF AND THE LIVE LOAD IS 30
 PSF PER TRUSS DRAWINGS AND ORIGINAL PLANS. FBC
 R802.1.6.1
  
 5) THE ARCHITECTS SIGNATURE IS MISSING ON SHEET A-2 OF
 ONE OF THE PLAN SETS. FAC 61G1-16
  
 6) SUBMIT TWO COPIES OF THE PRODUCT EVALUATIONS FOR THE
 ICYNENE SPRAY FOAM INSULATION. FBC R316
  
 7) PLEASE CLARIFY IF THIS WILL NOW BE AN UNVENTED ATTIC
 ASSEMBLY WITH THE SPRAY FOAM IS APPLIED TO THE
 UNDERSIDE OF THE ROOF AND REQUIRING THE ATTIC VENTING
 TO BE SEALED. FBC R806.4
  
 8) PLEASE REVIEW THE NEW DOOR OPENING PRESSURES ON
 SHEET A-1 TO DETERMINE IF THEY ARE CORRECT FOR 170 MPH
 VULT / 132 MPH VASD WIND SPEED, EXPOSURE C WITH A 24.5
 FT MEAN ROOF HEIGHT. FBC R301.2.1
  
 9) PLEASE INDICATE THE REQUIRED OPENING PRESSURES FOR
 ALL OF THE SECOND FLOOR SINGLE HUNG WINDOWS THAT ARE TO
 BE REPLACED, ACCORDING TO THE SCOPE OF WORK FOR THIS
 PROJECT. FBC R301.2.1
  
 10) THE DESIGNER OF RECORD IS REQUIRED TO REVIEW AND
 APPROVE THE PRODUCT APPROVALS IN WRITING PER CITY
 AMENDMENTS 107.3.4.1.
  
 11) THE PRODUCT APPROVALS SUBMITTED INDICATE THAT THE
 REPLACEMENT WINDOWS ARE NOT LARGE MISSILE IMPACT RATED.
 PLEASE INDICATE THAT THERE IS EXISTING STORM PANELS OR
 PROVIDE PRODUCT APPROVALS AND INSTALLATION SCHEDULES
 FOR THEM. FBC EXISTING BUILDING SECTION 606.4 AND DCA
 RULE 9N-3.
  
 12) SPECIFY WHICH OF THE APPROVED METHODS OF ATTACHMENT
 LISTED IN THE HANSON CEMENT ROOF TILE, NOA #12-0917.07,
 WILL BE USED TO INSTALL IT. IF A ROOF TILE ADHESIVE
 WILL BE USED, PROVIDE TWO COPIES OF THE PRODUCT
 APPROVAL PER FBC EXISTING BUILDING SECTION 611 AND DCA
 RULE 9N-3.
  
 13) PRODUCT APPROVALS WERE SUBMITTED FOR AN OUTSWING
 DOOR WITH A MAXIMUM HEIGHT OF 6' 8", AS WELL AS, ONE
 WITH AN 8' DOOR HEIGHT. THE PLANS SPECIFY A DOOR WITH
 AN 8' HEIGHT. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1
  
 14) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. THIS WILL
 HELP CUT DOWN ON PLAN REVIEW TIME.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-07-26 Cont ID  
Sent By rmcdouga Date 2013-07-26 Time 16:56 Rev Time 0.00
Received By rmcdouga Date 2013-07-26 Time 16:56 Sent To  
Notes
2013-07-26 16:56:252010 FBC / 2008 NEC
  
 1) ALL ELECTRICAL WORK TO COMPLY WITH 2008 NEC.
  
 2) ELECTRICAL PLANS HAVE BEEN RED-LINED. SEE REVIEW
 NOTES ON PLANS.
  
 3) REVISED ELECTRICAL PLANS MAY BE REQUIRED TO CLARIFY
 FIELD CONDITIONS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-08 Cont ID  
Sent By rmcdouga Date 2013-08-08 Time 15:10 Rev Time 0.00
Received By rmcdouga Date 2013-08-01 Time 16:03 Sent To  
Notes
2013-08-02 16:04:05SENT TO MCDOUGAL'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-29 Cont ID  
Sent By rmcdouga Date 2013-07-29 Time 11:21 Rev Time 0.00
Received By rmcdouga Date 2013-06-20 Time 17:29 Sent To  
Notes
2013-06-20 17:31:06SENT TO R-11 BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-08-08 Cont ID  
Sent By rmcdouga Date 2013-08-08 Time 15:10 Rev Time 0.00
Received By rmcdouga Date 2013-08-08 Time 15:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-07-26 Cont ID  
Sent By rmcdouga Date 2013-07-26 Time 13:01 Rev Time 0.00
Received By rmcdouga Date 2013-07-26 Time 10:32 Sent To  
Notes
2013-07-26 16:24:212010 FBC
  
 DENIED BY MECHANICAL
  
 1) THE MECHANICAL PLANS FOR THE SECOND FLOOR FROM CEE
 DEE A/C DO NOT COMPLY WITH FBCR M1602.4 FOR BALANCED
 RETURN AIR. TRANSFER DUCTS ARE REQUIRED TO BE 1.5 TIMES
 THE CROSS SECTIONAL AREA OF SUPPLY DUCT ENTERING THE
 ROOM OR SPACE IT IS SERVING AND THE DOOR HAVING AT
 LEAST A ONE INCH UNDERCUT. ALSO, ALL OF THE SUPPLY AIR
 ENTERING THE MASTER SUITE HAS TO BE INCLUDED IN SIZING
 THE TRANSFER DUCT FROM THAT AREA. PLEASE CORRECT
 DRAWINGS.
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-07-26 Cont ID  
Sent By rmcdouga Date 2013-07-26 Time 09:55 Rev Time 0.00
Received By rmcdouga Date 2013-07-26 Time 08:18 Sent To  
Notes
2013-07-26 09:59:31RED-LINED PLUMBING RISER PLAN ON SHEET P-1. A REVISED
 PLUMBING RISER DIAGRAM IS REQUIRED TO BE SUBMITTED FOR
 REVIEW AND APPROVED PRIOR TO FINAL PLUMBING INSPECTION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2013-07-29 Cont ID  
Sent By rmcdouga Date 2013-07-29 Time 11:18 Rev Time 0.00
Received By rmcdouga Date 2013-07-29 Time 11:18 Sent To  
Notes
2013-07-29 11:21:35ROOFING PRODUCT APPROVALS SUBMITTED.
  
 1) BORAL TILESEAL (UNDERLAYMENT) NOA NO. 12-0417.06
  
 2) HANSON HACIENDA DOUBLE ROLL ROOF TILE 12-0917.07

Review Stop Z ZONING
Rev No 1 Status N Date 2013-06-27 Cont ID  
Sent By avann Date 2013-06-27 Time 10:34 Rev Time 0.00
Received By ajones Date 2013-06-27 Time 10:34 Sent To  
Notes
2013-06-24 18:55:016/25/13