| Plan Review Stops For Permit 13060708 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2013-09-13 |
|
|
Cont ID |
|
| Sent By |
JWITMER |
Date |
2013-09-13 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-09-13 |
Time |
10:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2013-08-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-08-22 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-08-22 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2013-08-22 09:41:23 | BUILDING PLAN REVIEW | | | PERMIT: 13060708 | | | ADD: 431 BUNKER RD | | | CONT: GRUBER HALL CORP | | | TEL: (561)697-3401 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE:8/22/13 | | | ACTION: DENIED | | | | | | NOTICE: 2/22/13 TODAY I CALLED THE CONTRACTOR TO REACH | | | OUT TO HIM, A MEETING WITH THE OWNER, CONTRACTOR, FIRE | | | DEPARTMENT & THE BUILDING DEPARTMENT IS GOING TO BE | | | REQUIRED. THE FIRE DEPARTMENT VISITED THE SITE, A FIRE | | | INSPECTOR AND REQUESTED A 2 HOUR WALL BE INSTALLED | | | BECAUSE OF THE TYPE OF USAGE FOR THIS SPACE. SINCE THEN | | | THE PLANS HAVE INDICATED THE BACK HALF AS STORAGE AND | | | NOW IT IS TO BE RETAIL WITH A 2 HR FIRE RATED WALL, | | | INDICATING EXISTING RETAIL. THIS REVIEW WILL BE FOR A | | | MERCANTILE OCCUPANCY. | | | | | | 1) THE BUILDING CONTRACTOR HAS NOT TAKEN RESPONSIBILITY | | | FOR THE BUILDING DRAWING NOR HAS THE PLUMBING | | | CONTRACTOR FOR THE PLUMBING SHEETS, THEY WILL NEED TO | | | PRINT & SIGN THEIR NAME AND PROVIDE THEIR LICENSE | | | NUMBER ON THE PLANS THEY HAVE DESIGNED. WEST PALM BEACH | | | AMENDMENT TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION, 2010 EDITION 107.1. | | | | | | 2) PLEASE PROVIDE THE RATIONAL FOR A NEW 2 HR RATED | | | WALL, THIS WALL IS EITHER A TENANT SEPERTION WALL WHICH | | | WOULD BE A ONE HOUR TENANT SEPERATION WALL, FBC-B | | | 709.1(6) OR A OCCUPANCY SEPERATION WALL PER FBC-B TABLE | | | 508.4. PLEASE PROVIDE FOR WHICH CASE THIS WALL IS BEING | | | BUILT, WITHOUT A CLEAR DEFINITION OF WHAT REASON THIS | | | WALL IS BEING CONSTRUCTED, WE ARE ONLT GUESSING A | | | MEETING IS REQUIRED. | | | | | | 3) WITH THE NEWLY FORM MERCANTILE SPACE OR THE EXISTING | | | MERCANTILE SPACE IN THE REAR PORTION OF THE BUILDING | | | HAVING A 2 HOUR RATED WALL BEING CONSTRUCTED THE BSCK | | | 50'X50' SPACE, 2500 SQ FT/ 30 OCC.= 84 OCCUPANT LOAD. | | | | | | 3A) THERE ARE A PAIR OF DOUBLE DOORS AND A SINGLE SWING | | | DOOR THAT SWING INTO THIS SPACE, SINCE THE OCCUPANT | | | LOAD IS 50 OR MORE, COMPLIANCE WITH FBC-B 1008.1.2 | | | REQUIRES THE SWING OF DOORS IN THE DIRECTION OF EXIT | | | TRAVEL. | | | | | | 3B) THE SECOND ISSUE WITH THE BACK HALF OF THE | | | MERCANTILE OCCUPANCY IS THE DISTANCE THE TWO DOORS ARE | | | APART, SINCE THE OCCUPANT LOAD IS 50 OR MORE TWO MEANS | | | OF EGRESS ARE REQUIRED, FBC-B 1008.1.2 REQUIRES THE | | | EGRESS DOORS TO BE SIDE SWINGING, THE OVERHEAD GARAGE | | | DOOR CAN NOT BE CONSIDERED A EGRESS DOOR. FBC-B | | | 1015.2.1. REQUIRES THE DOORS TO BE A MINIMUM OF 1/2 THE | | | OVER ALL DIAGONAL DISTANCE OF THE ROOM APART, THEY DO | | | NOT MEET THIS REQUIREMENT. | | | | | | 3C) THE THIRD ISSUE WITH THE BACK HALF OF THE | | | MERCANTILE OCCUPANCY, IS THIS A SECOND TENANT, IF SO | | | THEY HAVE NO DIRECT EXIT TO THE EXTERIOR, THEY WOULD | | | HAVE TO GO THROUGH ANOTHER TENANT SPACE NOT UNDER THIER | | | CONTROL, FBC-B 1014.2 (2) LOCKABLE SPACES. | | | | | | 4) THE NEWLY FORMED MERCANTILE SPACE DOES NOT PROVIDE | | | ANY EXIT LIGHTING, EXIT SIGNAGE NOR DIRECTIONALS, PLANS | | | FAIL TO PROVIDE ANY NATURAL LIGHT INTO THE SPACE, FBC-B | | | 1006.3.1. | | | | | | 5) PLANS FAIL TO PROVIDE FOR ANY LIGHTING REQUIREMENTS, | | | FBC-B 1205.2 NATURAL LIGHT, 1205.2.1 ADJOINING LIGHT OR | | | 1205.2.2 EXTERIOR OPENINGS. | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. AMEETING IS REQUESTED WITH THE TENNANT, | | | CONTRACTOR, FIRE AND BUILDING DEPARTMENT TO GO OVER | | | COMMENTS, THIS IS THE THIRD REVIEW. | | | | | | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2013-07-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-07-26 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-07-26 |
Time |
12:33 |
Sent To |
|
|
| Notes |
| 2013-07-29 13:45:05 | BUILDING PROVISO: THE STORAGE OCCUPANCY IS STORAGE | | | ONLY!!! NO MANUFACTURING OF SURF- BOARDS!!!!! |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-07-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-07-05 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-07-05 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2013-07-05 14:37:33 | BUILDING PLAN REVIEW | | | PERMIT: 13060708 | | | ADD: 431 BUNKER RD | | | CONT: GRUBER HALL CORP | | | TEL: (561)697-3401 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: 7/05/13 | | | ACTION: DENIED | | | | | | 1) 2010 WEST PALM BEACH ADMINISTRATIVE CODE, CHAPTER 1 | | | FBC-B 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION | | | DOCUMENTS SHALL BE IN ACCORDANCE WITH SECTIONS | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS | | | SHALL BE | | | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN | | | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS | | | CODE AND RELEVANT LAWS, ORDINANCES, RULES AND | | | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. | | | PROVIDE DIMENSIONED PLANS. | | | | | | 1A) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | THE EXAMINATION OF THE DOCUMENTS BY THE | | | BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM | | | CRITERIA AND DOCUMENTS: A FLOOR PLAN; SITE | | | PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS | | | LAYOUT; ALL FENESTRATION PENETRATIONS; | | | FLASHING; AND ROUGH OPENING DIMENSIONS; AND ALL | | | EXTERIOR ELEVATIONS: | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | 107.3.5.1.1 BUILDING | | | 1B) OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS | | | SHALL BE DETERMINED FOR EACH SECTION OF BUILDING, WHY A | | | 2 HOUR WALL. | | | 1C) 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED | | | (SEE TABLE 503). SPRINKLERED? | | | 1D) 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL | | | INCLUDE: | | | COMMON PATH OF TRAVEL | | | OCCUPANCY LOAD | | | GROSS | | | NET | | | MEANS OF EGRESS | | | EXIT ACCESS | | | EXIT | | | 2) ACCESSIBILITY PROVIDE DIMENSIONED PLANS, SHOW | | | COMPLIANCE WITH; | | | 2A) 2010 ACCESSIBILTY CODE 604.3.2 FIGURE 604.8.1.6. | | | 2B) 2010 ACCESSIBILITY CODE 608.3.2 OR 608.3.3. | | | ACCESSIBLE SHOWERS | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | EXIT DISCHARGE |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2013-09-23 |
|
|
Cont ID |
|
| Sent By |
DHARVEY |
Date |
2013-09-23 |
Time |
17:52 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-09-23 |
Time |
17:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2013-08-12 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-08-12 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-08-12 |
Time |
08:21 |
Sent To |
|
|
| Notes |
| 2013-08-12 08:26:52 | NO ELECTRIC SHOWN. NO ELECTRIC WORK ANTICIPATED. | | | PROVIDE PERMIT AND PLANS IF ELECTRIC IS TO BE DONE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-07-05 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-07-05 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-07-05 |
Time |
14:59 |
Sent To |
|
|
| Notes |
| 2013-07-05 15:01:41 | REQUIRES AN ELECTRIC PERMIT AND PPAN FOR ANY PROPOSED | | | ELECTRIC CHANGES OR IMPROVEMENTS. NO ELECRIC SHOWN ON | | | PLANS. | | | | | | RL |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2013-09-13 |
|
|
Cont ID |
|
| Sent By |
LPHILMOR |
Date |
2013-09-13 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2013-09-13 |
Time |
10:45 |
Sent To |
E |
|
| Notes |
| 2013-09-13 10:46:05 | CLASS "B" MERCANTILE: NEED EMERGENCY LIGHTING. | | | EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM | | | OF 1.5 HOURS IN THE EVENT OF FAILURE OF NORMAL | | | LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE | | | ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT | | | LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, | | | NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF | | | EGRESS AT FLOOR LEVEL. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2013-08-21 |
|
|
Cont ID |
|
| Sent By |
lphilmor |
Date |
2013-08-21 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
lphilmor |
Date |
2013-08-21 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2013-08-21 15:53:08 | 431 BUNKER RD | | | PERMIT # 13060708 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 1. PLEASE PROVIDE INTENT OF 2HR RATED WALL AS PREVIOUS | | | REVISION INDICATES WAREHOUSING/STORAGE AND NOW STATES | | | EXISTING RETAIL SPACE. ARE MULTIPLE TENANTS INTENDED | | | FOR THIS LAYOUT? | | | 2. DOORS LOCATED WITHIN THE 2HR RATED WALL NEED TO | | | SWING IN THE FLOW OF TRAFFIC DUE TO SPACE BEING | | | INDICATED AS MERCANTILE AT 30 SQFT/PERSON. | | | 3. EXTERIOR DOORS DO NOT MEET DISTANCE REQUIREMENTS NOW | | | THAT THE WAREHOUSING/STORAGE AREA HAS BEEN CHANGED TO | | | EXISTING RETAIL. TWO REMOTE EXITS AT LEAST HALF THE | | | DISTANCE OF THE SPACE IS REQUIRED DUE TO THE LOCATION | | | CHANGING FROM A CLASS C MERCANTILE TO A CLASS B | | | MERCANTILE. IN THIS CASE, TRAVEL DISTANCE EXCEEDS 75FT. | | | | | | LAUREN PHILMORE | | | FIRE INSPECTOR II / INVESTIGATOR I | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4783 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2013-07-30 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2013-07-30 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2013-07-30 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2013-07-30 15:47:43 | 431 BUNKER ROAD | | | PERMIT #13060708 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE ILLUMINATED EXIT SIGN(S) AND EMERGENCY LIGHTING | | | FOR STORAGE AREA. | | | | | | EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH | | | SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL | | | OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN | | | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE | | | SPACED NOT MORE THAN 15 FEET ON CENTER. | | | | | | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL | | | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2013-07-03 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2013-07-03 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2013-07-03 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2013-07-03 09:27:57 | 431 BUNKER ROAD | | | PERMIT #13060708 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE PLAN INDICATES ONE TENANT HAS TO ACCESS THE | | | ADJACENT TENANT SPACE IN ORDER TO EXIT THE BUILDING. | | | PROVIDE A LIFE SAFETY PLAN SHOWING ALL EXIT DOORS, | | | OCCUPANCY TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT | | | SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON | | | PATH OF TRAVEL ETC. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH | | | SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL | | | OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN | | | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE | | | SPACED NOT MORE THAN 15 FEET ON CENTER. | | | | | | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL | | | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. | | | | | | 90-MINUTE FIRE RATED DOORS ARE REQUIRED IN THE 2-HOUR | | | FIRE RATED WALL AND DOORS SHALL BE POSITIVE LATCHING. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2013-09-23 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-09-23 |
Time |
17:52 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-09-23 |
Time |
17:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2013-08-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-08-22 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-08-14 |
Time |
18:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-08-14 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-08-14 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-07-22 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2013-07-23 14:35:23 | SENT TO B23 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-07-05 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-07-05 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-06-20 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2013-06-20 15:27:32 | INCOMING SENT TO B-14 BOX. JW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2013-08-14 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-08-14 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-08-14 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2013-08-14 13:21:17 | NO MECHANICAL AT THIS TIME. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2013-09-18 |
|
|
Cont ID |
|
| Sent By |
LWAGNER |
Date |
2013-09-18 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-09-18 |
Time |
15:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2013-08-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-08-22 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-08-22 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2013-08-22 10:28:47 | PLUMBING PLAN REVIEW | | | PERMIT: 13060708 | | | ADD: 431 BUNKER RD | | | CONT: GRUBER HALL CORP | | | TEL: (561)697-3401 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE:8/22/13 | | | ACTION: DENIED | | | | | | NOTICE: 2/22/13 TODAY I CALLED THE CONTRACTOR TO REACH | | | OUT TO HIM, A MEETING WITH THE OWNER, CONTRACTOR, FIRE | | | DEPARTMENT & THE BUILDING DEPARTMENT IS GOING TO BE | | | REQUIRED. THE FIRE DEPARTMENT VISITED THE SITE, A FIRE | | | INSPECTOR AND REQUESTED A 2 HOUR WALL BE INSTALLED | | | BECAUSE OF THE TYPE OF USAGE FOR THIS SPACE. SINCE THEN | | | THE PLANS HAVE INDICATED THE BACK HALF AS STORAGE AND | | | NOW IT IS TO BE RETAIL WITH A 2 HR FIRE RATED WALL, | | | INDICATING EXISTING RETAIL. THIS REVIEW WILL BE FOR A | | | MERCANTILE OCCUPANCY. | | | | | | 1) ISSUES SSTAND WITH THE PLUMBING DRAWINGS, THE | | | PLUMBING CONTRACTOR HAS NOT TAKEN RESPONSIBILITY FOR | | | THE PLUMBING CONTRACTOR FOR THE PLUMBING SHEETS, THEY | | | WILL NEED TO PRINT & SIGN THEIR NAME AND PROVIDE THEIR | | | LICENSE NUMBER ON THE PLANS THEY HAVE DESIGNED. WEST | | | PALM BEACH AMENDMENT TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.1. | | | | | | 2) AS IN THE BUILDING REVIEW, THE PLANS DO NOT INDICATE | | | IF THIS IS GOING TO BE A SINGLE TENANT OR IF THIS WILL | | | BE TWO TENANTS, WORST CASE A SINGLE MERCANTILE | | | OCCUPANCY, SINGLE TENANT, 5000 SQ FT/ 30 SQ/ OCC EQUALS | | | 167 OCCUPANTS. THE 2010 FBC-P TABLE 403.1(6) WILL | | | REQUIRE ONE RESTROOM FOR BOTH MEN AND WOMEN. PLEASE NOT | | | SINCE THERE IS A SHOWER, ONE WOULD HAVE TO BE PROVIDED | | | FOR EACH SEX. | | | | | | THE SINGLE UNISEX RESTROOM WAS FOR ONLY FOR MERCANTILE | | | OCCUPANCIES UNDER 3,000 SQ FT. IF THIS IS TO BE | | | CONSIDERED TWO MERCANTILE OCCUPANCIES EACH 2,500 SQ FT | | | THEN EACH TENANT SPACE WILL REQUIRE A UNISEX RESTROOM. | | | NOTE THE TENANT SPACE NOT REQUIRING A SHOWER IN IT WILL | | | ONLY NEED THE SINGLE UNISEX RESTROOM. | | | | | | 3) PLEASE ALSO REVIEW THE 2010 FBC-P TABLE 403.1(6) | | | WILL REQUIRE A DRINKING FOUNTAIN PLEASE REVIEW 2010 FL | | | ACCESSIBILITY CODE 211, | | | 211.2 MINIMUM NUMBER. | | | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. | | | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH | | | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH | | | 602.7. | | | | | | 4) THE RESTROOMS DESIGN ACCESSIBLITY NOR THE DRAINAGE | | | AND VENT SYSTEMS WILL BE REVIEWED UNDER THIS REVIEW | | | SINCE THEY WILL BE DRASTICALLY REVISED. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2013-07-29 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2013-07-29 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-07-29 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2013-07-29 11:10:22 | FBC 2010 EXISTING BUILDING CODE | | | FBC 2010 ACCESSIBILITY CODE | | | FBC 2010 PLUMBING REVIEW #2 | | | DENIED: | | | | | | 1. SHEET A-1 & P-1 ACCESS FOR THE PUBLIC TO THE | | | RESTROOM IS SHOWN THROUGH THE STORAGE AREA. | | | FBC PLUMBING 403.3.1 ACCESS. | | | THE ROUTE TO THE PUBLIC TOILET FACILITIES REQUIRED BY | | | SECTION 403.3 SHALL NOT PASS THROUGH KITCHENS, STORAGE | | | ROOMS OR CLOSETS. ACCESS TO THE REQUIRED FACILITIES | | | SHALL BE FROM WITHIN THE BUILDING OR FROM THE EXTERIOR | | | OF THE BUILDING. ALL ROUTES SHALL COMPLY WITH THE | | | ACCESSIBILITY REQUIREMENTS OF THE FLORIDA BUILDING | | | CODE, ACCESSIBILITY. THE PUBLIC SHALL HAVE ACCESS TO | | | THE REQUIRED TOILET FACILITIES AT ALL TIMES THAT THE | | | BUILDING IS OCCUPIED. | | | | | | 2. SHEET P-2 WATER FOR THE SHOWER IS SHOWN AS COLD | | | WATER ONLY. | | | FBC PLUMBING 607.1 WHERE REQUIRED. | | | IN OCCUPIED STRUCTURES, HOT WATER SHALL BE SUPPLIED TO | | | ALL PLUMBING FIXTURES AND EQUIPMENT UTILIZED FOR | | | BATHING, WASHING, CULINARY PURPOSES, CLEANSING, LAUNDRY | | | OR BUILDING MAINTENANCE. | | | | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2013-06-24 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2013-06-24 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-06-24 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2013-06-24 10:15:30 | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | NO PLUMBING DRAWINGS WERE INCLUDED WITH PLANS. | | | FBC 2010 107.3.5.1.3 IF THE RESTROOM IS NEW, PLUMBING | | | DRAWINGS ARE REQUIRED FOR SANITARY RISER DIAGRAM, | | | WATER, WATER HEATER, ETC. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2013-06-24 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2013-06-24 |
Time |
18:53 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2013-06-24 |
Time |
18:53 |
Sent To |
|
|
| Notes |
|
|