Plan Review Details - Permit 13060687
Plan Review Stops For Permit 13060687
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-07-10 Cont ID  
Sent By shill Date 2013-07-10 Time 17:10 Rev Time 0.00
Received By shill Date 2013-07-10 Time 17:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-27 Cont ID  
Sent By shill Date 2013-06-27 Time 09:10 Rev Time 0.00
Received By shill Date 2013-06-27 Time 09:10 Sent To  
Notes
2013-06-27 09:14:14****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SUBSTRATE NOTED AS FILLED BLOCK. FILLED CELLS MUST
 USE THE CONCRETE BLOCK SUBSTRATE ANCHOR SPACING, NOT
 CONCRETE.
  
 2. SEE SHEET 14, A 2" EDGE DISTANCE TO USE A FACTOR OF
 .35 APPLIED TO ANCHOR SPACING.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-27 Cont ID  
Sent By shill Date 2013-06-27 Time 09:14 Rev Time 0.00
Received By shill Date 2013-06-18 Time 17:00 Sent To  
Notes
2013-06-18 17:00:28TO BLDG < $5K