Plan Review Details - Permit 13060657
Plan Review Stops For Permit 13060657
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-09-27 Cont ID  
Sent By shill Date 2013-09-27 Time 12:07 Rev Time 0.00
Received By shill Date 2013-09-27 Time 12:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-08-22 Cont ID  
Sent By shill Date 2013-08-22 Time 20:54 Rev Time 0.00
Received By shill Date 2013-08-22 Time 20:54 Sent To  
Notes
2013-08-22 20:56:46****PROVISO****
 ****SEPARATE PERMIT REQUIRED FOR SHUTTERS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF)
  
 INSTALLATION SCHEDULE WAS NOT PROVIDED AT TIME OF
 RESUBMITTAL. SUBMIT PRODUCT APPROVAL AND INSTALLATION
 SCHEDULE WITH PERMIT APPLICATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-07-26 Cont ID  
Sent By shill Date 2013-07-26 Time 14:38 Rev Time 0.00
Received By shill Date 2013-07-26 Time 14:38 Sent To  
Notes
2013-07-26 14:51:28****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%.
  
 2ND REVIEW -
  
 MASTER BEDROOM SHOWS A "BLOCKED EXISTING DOOR." WHAT
 DOES THIS MEAN? IF THIS WAS AN EXISTING DOOR WHICH WAS
 REMOVED AND BLOCKED, THIS WAS THE EMERGENCY MEANS OF
 ESCAPE FOR THE BEDROOM. OTHER WINDOW IS SHOWN AS 48"
 HIGH, WHICH DOES NOT COMPLY. REVISE PLAN TO INSTALL A
 DOOR IN PREVIOUS LOCATION OR PROVIDE AN INFILL DETAIL
 AND COMPLIANT MEANS OF EMERGENCY ESCAPE AND RESCUE OR
 CLARIFY CONDITIONS PRIOR TO CONSTRUCTION PERFORMED
 WITHOUT PERMIT.
  
 PROVIDE THE ADDITIONAL INFORMATION REQUESTED - TYPE OF
 EXISTING (PRIOR TO CHANGE) OF WINDOW IN THE BEDROOMS,
 CLEAR OPENING THAT WAS EXISTING, NEW CLEAR OPENING.
  
 2. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF)
  
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4,
 PROVIDE CALCULATIONS.
  
 NOT ADDRESSED. PLAN STATES THAT THERE ARE EXISTING
 ACCORDION SHUTTERS, BUT NO PERMIT ON FILE FOR THIS
 WORK. PLEASE ADDRESS.
  
 3. PROVIDE A STRUCTURAL DETAIL FOR THE NEW WALL INFILL,
 FBC 107, FBC R 301.
  
 NOT ADDRESSED. INCLUDE WIND DESIGN CRITERIA AND THE
 PRINTED NAME AND SIGNATURE OF THE INDIVIDUAL TAKING
 RESPONSIBILITY FOR THE PLAN.
  
 4. OK
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-27 Cont ID  
Sent By shill Date 2013-06-27 Time 08:50 Rev Time 0.00
Received By shill Date 2013-06-27 Time 08:50 Sent To  
Notes
2013-06-27 08:52:13****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%.
  
 2. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF)
  
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4,
 PROVIDE CALCULATIONS.
  
 3. PROVIDE A STRUCTURAL DETAIL FOR THE NEW WALL INFILL,
 FBC 107, FBC R 301.
  
 4. TWO COMPLETE COLLATED SETS OF PLANS AND DOCUMENTS
 REQUIRED FOR PERMIT ISSUANCE. FAILURE TO PROVIDE TWO
 SETS MAY RESULT IN ADMINISTRATIVE FEES.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-09-27 Cont ID  
Sent By shill Date 2013-09-27 Time 12:07 Rev Time 0.00
Received By shill Date 2013-09-17 Time 14:11 Sent To  
Notes
2013-09-17 14:12:05RESUBMITTAL SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-08-22 Cont ID  
Sent By shill Date 2013-08-22 Time 20:57 Rev Time 0.00
Received By shill Date 2013-08-13 Time 10:13 Sent To  
Notes
2013-08-13 10:14:20SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-26 Cont ID  
Sent By shill Date 2013-07-26 Time 14:51 Rev Time 0.00
Received By shill Date 2013-07-18 Time 15:24 Sent To  
Notes
2013-07-18 15:24:37TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-27 Cont ID  
Sent By shill Date 2013-06-27 Time 08:52 Rev Time 0.00
Received By shill Date 2013-06-18 Time 17:25 Sent To  
Notes
2013-06-18 17:25:45TO BLDG < $5K