Plan Review Details - Permit 13060638
Plan Review Stops For Permit 13060638
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2014-04-26 Cont ID  
Sent By J WITMER Date 2014-04-26 Time 13:02 Rev Time 0.00
Received By jwitmer Date 2014-04-26 Time 09:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2014-02-12 Cont ID  
Sent By jwitmer Date 2014-02-12 Time 10:44 Rev Time 0.00
Received By jwitmer Date 2014-02-01 Time 10:14 Sent To  
Notes
2014-02-01 12:29:10BUILDING PLAN REVIEW
 PERMIT:13060638
 ADD: 114 S OLIVE
 CONT: TBD
 TEL: (561)856-6655
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: SAT. FEB. 01/2013
  
  
 ACTION: PENDING
 PENDING REVIEW: OF THRESHOLD DOCUMENTS SUBMITTED
 1/31/2014 TO K. CONRAD
 & RESPONCE TO COMMENT # 2.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING,
 MEETING THE DEFINITION.
 DEFINITION: FL S. S. 553.71(7) " THRESHOLD BUILDING"
 MEANING ANY BUILDING WHICH IS GREATER THAN (3) STORIES
 OR 50 FT IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 1A) COMPLIED 11/22/2013
 1B) 2ND REQUEST, THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 1C) 2ND REQUEST, THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 -------------------------------------------------------
 -----------------------------------
  
 1D) 2ND REQUEST, 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
 -------------------------------------------------------
 -------------------------------------
  
 1E) 2ND REQUEST, A THRESHOLD PLAN REVIEW STOP WILL BE
 PUT ON THIS PROJECT UNTIL THESE ITEMS ARE COMPLETED AS
 REQUESTED BY THE CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 1E)(1) 2ND REQUEST, THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 1E)(2) 2ND REQUEST, FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 2) SEMI-COMPLIED.THE SOILS REPORT INDICATES TO A DEPTH
 OF (9) FEET LOOSE TO VERY LOOSE SOILS, RECOMMONDATIONS
 INCLUDE A (7) BULLET STATEMENT OF SOILS IMPROVEMENTS
 AND THE SOILS RECOMMONDATION TO PERMEATION GROUTING OF
 THE ELEVATOR PIT, THE STRUCTURAL SHEETS DO NOT INCLUDE
 ANY STATEMENTS OTHER THAN THAT OF THE INCREASING THE
 BEARING PRESSURE OF THE INTERNAL BEARING COLUMNS TO
 6,000 PSF.
 2ND REQUEST, SHEET S1.1 THE EXISTING 6 COLUMNS INDICATE
 TO INCREASE THE LOADS ON THESE COLUMNS TO 6,000 PSF, TO
 SEE THE GEOTECHNICAL REPORT FOR REQUIREMENTS. PLEASE
 PROVIDE 3 SIGNED/ SEALED ORIGINAL SOILS REPORTS. 2010
 FBC-B 1803.3 BASIS OF INVESTIGATION. 1803.3.1 SCOPE OF
 INVESTIGATION. THE SCOPE OF THE GEOTECHNICAL
 INVESTIGATION INCLUDING THE NUMBER AND TYPES OF BORINGS
 OR SOUNDINGS, THE EQUIPMENT USED TO DRILL OR SAMPLE,
 THE IN-SITU TESTING EQUIPMENT AND THE LABORATORY
 TESTING PROGRAM SHALL BE DETERMINED BY A REGISTERED
 DESIGN PROFESSIONAL.
  
 FAILED 2/12/2014 THE STRUCTURAL ENGINEER, ARCHITECT &
 SOILS ENGINEER ARE GOING TO DECIDE HOW BEST TO IMPROVE
 THE SOIL BEARING VALUE OF THE 6 EXISTING COLUMNS.
 WAITING ON A DECISSION TO BE MADE.
  
 3) COMPLIED, 11/22/2013.
  
 4-9) COMPLIED.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-11-22 Cont ID  
Sent By jwitmer Date 2013-11-22 Time 15:48 Rev Time 0.00
Received By jwitmer Date 2013-11-22 Time 13:20 Sent To  
Notes
2013-11-22 15:47:57BUILDING PLAN REVIEW
 PERMIT:13060638
 ADD: 114 S OLIVE
 CONT: TBD
 TEL: (561)856-6655
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: NOV. 22/2013
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING,
 MEETING THE DEFINITION.
 DEFINITION: FL S. S. 553.71(7) " THRESHOLD BUILDING"
 MEANING ANY BUILDING WHICH IS GREATER THAN (3) STORIES
 OR 50 FT IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 1A) COMPLIED 11/22/2013
 1B) 2ND REQUEST, THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 1C) 2ND REQUEST, THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 -------------------------------------------------------
 -----------------------------------
  
 1D) 2ND REQUEST, 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
 -------------------------------------------------------
 -------------------------------------
  
 1E) 2ND REQUEST, A THRESHOLD PLAN REVIEW STOP WILL BE
 PUT ON THIS PROJECT UNTIL THESE ITEMS ARE COMPLETED AS
 REQUESTED BY THE CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 1E)(1) 2ND REQUEST, THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 1E)(2) 2ND REQUEST, FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 2) 2ND REQUEST, SHEET S1.1 THE EXISTING 6 COLUMNS
 INDICATE TO INCREASE THE LOADS ON THESE COLUMNS TO
 6,000 PSF, TO SEE THE GEOTECHNICAL REPORT FOR
 REQUIREMENTS. PLEASE PROVIDE 3 SIGNED/ SEALED ORIGINAL
 SOILS REPORTS. 2010 FBC-B 1803.3 BASIS OF
 INVESTIGATION. 1803.3.1 SCOPE OF INVESTIGATION. THE
 SCOPE OF THE GEOTECHNICAL INVESTIGATION INCLUDING THE
 NUMBER AND TYPES OF BORINGS OR SOUNDINGS, THE EQUIPMENT
 USED TO DRILL OR SAMPLE, THE IN-SITU TESTING EQUIPMENT
 AND THE LABORATORY TESTING PROGRAM SHALL BE DETERMINED
 BY A REGISTERED DESIGN PROFESSIONAL.
  
 3) COMPLIED, 11/22/2013.
  
 4) 2ND REQUEST PRODUCT APPROVALS:
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
 THE PRODUCT APPROVAL NOA 13-0606.02 CETCO STRATASEAL HR
 HOT APPLIED LIQUID MEMBRANE WILL NEED TO SHOW ITS: (
 GENERAL LIMITATIONS)
 FIRE CLASSIFICATION FOR A TYPE II-A BUILDING.
 THIS PRODUCT IS NOT TO BE EXPOSED TO TRAFFIC, HOW WILL
 IT BE PROTECTED.
 NOT TO BE INSTALLED ON LIGHTWEIGHT CONCRETE, WHERE AS
 THE OTHER ROOFING APPROVAL NOA 12-0703.09 IS TO BE
 INSTALLED ON LIGHT WEIGHT CONCRETE.
 FLASHINGS TO COMPLY WITH THE MANUFACTURERS STANDARDS
 COMPLY WITH RAS 111
 MAXIMUM DESIGN PRESSURE OF -75, LIMITATION # 9
 THE SECOND ROOFING APPROVAL SUBMITTED IS NOA 12-0703.09
 PLEASE CIRCLE WHICH SUB-SYSTEM IS TO BE INSTALLED UNDER
 THIS PERMIT.
  
 5) 2ND REQUEST. SHEET S2.1 UNDER THE WIND LOAD SCHEDULE
 NOTE # 1 INDICATES THE USE OF THE WORD EITHER SHUTTERS
 OR LARGE MISSILE IMPACT TESTED ...
 SHEET S2.1 THE WORD ?OR? IN THE WIND DESIGN SCHEDULE,
 IMPACT GLASS OR SHUTTERS, SPECIFY ONE OR THE OTHER.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH
 DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 6) SHEET LS 1.1, BUILDING CLASSIFICATION;
 6A-C) COMPLIED.
 6D) 2ND REQUEST. PLEASE UPDATE PLANS, THEY INDICATE A
 LEVEL III ALTERATION THIS IS ALSO A CHANGE OF OCCUPANCY
 AND THE 2010 EXST BLDG CODE CHANGE OF OCCUPANCY 901.3.
  
 6E) 2ND REQUEST. OCCUPANT LOADS & EGRESS CAPACITY CHART
 IS OFF WITH ONLY LOOKING AT THE REQUIRED WIDTH OF THE
 STAIR, THE WORST CASE SCENARIO SHOULD BE THE DOOR, YOU
 CAN?T BOTTLE NECK THE MEANS OF EGRESS, THE CHART SHOULD
 BE REWORKED.
  
 6F) SUBSTITUTION NOTE: 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 7) COMPLIED.
  
 8) 2ND REQUEST. LS1.1, INDICATES 1 HR. GLASS WALL AT
 STAIR # 1. ID 1.2 SI-9 APPEARS TO BE FOR WIRE GLASS
 DETAIL AT STAIR # 1. PLEASE REVIEW THE MAXIMUM AREA
 ALLOWED IN EXIT DOORS FBC-B 715.4.4, 715.4.4.1 715.4.5
 AS WELL AS TABLE 715.5.4 FOR WIRE GLASS PANELS AND
 TABLE 715.5 FIRE WINDOW ASSEMBLIES IN FIRE BARRIERS (1
 HR. VERTICAL EXITS.)
  
 9) 2ND REQUEST. SHEET LS1.1 INDICATES THE DOORS TO
 STAIRWELL # 1 TO BE HELD OPEN. SHEET A10.1 THE DOORS
 SCHEDULE TO STAIRWELL 1 ( 102.01) DO NOT INDICATE HOW
 THEY ARE GOING TO STAY OPEN OR COMPLIANCE WITH FBC-B
 715.4.8. DOOR CLOSING, THIS REQUIREMENT WILL NEED TO BE
 INDICATED FOR ALL STAIRWELL DOORS. NEITHER THE ELECTRIC
 SHEETS OR FIRE ALARM SHOW ANY ELECTRIC TO THESE DOOR
 FOR ELECTROMAGNETS AND RELEASE WHEN THE FIRE ALARM OR
 FIRE SPRINKLERS ARE ACTIVATED.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-07-17 Cont ID  
Sent By jwitmer Date 2013-07-17 Time 11:53 Rev Time 0.00
Received By jwitmer Date 2013-07-16 Time 13:17 Sent To  
Notes
2013-07-16 16:52:11BUILDING PLAN REVIEW
 PERMIT:13060638
 ADD: 114 S OLIVE
 CONT: TBD
 TEL: (561)856-6655
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 16/2013
 ACTION: DENIED
  
 1) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING,
 MEETING THE DEFINITION.
 DEFINITION: FL S. S. 553.71(7) " THRESHOLD BUILDING"
 MEANING ANY BUILDING WHICH IS GREATER THAN (3) STORIES
 OR 50 FT IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 1A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL
 INSPECTION PLAN (THRESHOLD INSPECTION PLAN) PREPARED BY
 THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 1B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 1C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 -------------------------------------------------------
 -----------------------------------
  
 1D) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
 -------------------------------------------------------
 -------------------------------------
  
 1E) A THRESHOLD PLAN REVIEW STOP WILL BE PUT ON THIS
 PROJECT UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY
 THE CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 1E)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 1E)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 2) SHEET S1.1 THE EXISTING 6 COLUMNS INDICATE TO
 INCREASE THE LOADS ON THESE COLUMNS TO 6,000 PSF, TO
 SEE THE GEOTECHNICAL REPORT FOR REQUIREMENTS. PLEASE
 PROVIDE 3 SIGNED/ SEALED ORIGINAL SOILS REPORTS. 2010
 FBC-B 1803.3 BASIS OF INVESTIGATION. 1803.3.1 SCOPE OF
 INVESTIGATION. THE SCOPE OF THE GEOTECHNICAL
 INVESTIGATION INCLUDING THE NUMBER AND TYPES OF BORINGS
 OR SOUNDINGS, THE EQUIPMENT USED TO DRILL OR SAMPLE,
 THE IN-SITU TESTING EQUIPMENT AND THE LABORATORY
 TESTING PROGRAM SHALL BE DETERMINED BY A REGISTERED
 DESIGN PROFESSIONAL.
  
 3) SHEET S2.1 THE WIND DESIGN CRITERIA IS GIVEN AND
 ASSOCIATED PRESSURES, BUT THE CHART DOES NOT INDICATE
 IF THEY ARE IN VASD OR VULT. THE OTHER ISSUE IS THE
 CHART DOES NOT INDICATE AT WHAT SQ FT IT IS CALCULATED
 FOR, 10 SQ FT, 20SQ FT 50 SQ FT OR 100 SQ FT? PLEASE
 PROVIDE ADDITIONAL INFORMATION FOR REVIEW. 107.2.1.3.
  
 4) PRODUCT APPROVALS:
 4A) 08-0125.02 EXPIRED 6/15/13 CETCO STRATASEAL
 4B) 08-0501.01 EXPIRED 6/19/13 AIROLITE ALUM. PENTHOUSE
 LOUVER
 4C) 08-0520.04 EXPIRES 9/04/13 PLEASE UPDATE TO THE
 NEWEST NOA
 4D) 11-0722.10 BILCO ROOF HATCH LOW PRESSURES AT +/- 70
  
 5) SHEET S2.1 UNDER THE WIND LOAD SCHEDULE NOTE # 1
 INDICATES THE USE OF THE WORD EITHER SHUTTERS OR LARGE
 MISSILE IMPACT TESTED ...
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.SUCH
 DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 6) SHEET LS 1.1, BUILDING CLASSIFICATION;
 6A) A-2 COMMON PATH OF TRAVEL W/ SPRINKLERS 100 FT.
 PLEASE SEE 2010 FBC-B 1014.3 EX # 5 > 50 OCCUPANTS 20
 FT.
  
 6B) DEAD END CORR 50 FT 1016.3 PLEASE SEE 2010 FBC-B
 1814 A2 ASSEMBLY 20 FT.
  
 6C) TRAVEL DISTANCE 300 FT PLEASE REVIEW 2010 FBC-B
 TABLE 1016.1 ASSEMBLY 250 FT.
  
 6D) PLEASE UPDATE PLANS, THEY INDICATE A LEVEL III
 ALTERATION THIS IS ALSO A CHANGE OF OCCUPANCY AND THE
 2010 EXST BLDG CODE CHANGE OF OCCUPANCY 901.3.
  
 6E) OCCUPANT LOADS & EGRESS CAPACITY SEE LEVEL 3 THE
 ERGRESS CAPACITY REQUIRED INDICATES 50 INCHES WHEREAS
 250 X 0.3= 75 INCHES, PLEASE CORRECT. PLEASE ALSO
 PROVIDE ON SHEET A7.2.2 THE INSIDE CLEAR MEASUREMENT SO
 THE EGRESS CAPACITY CAN BE CLEARLY CALULATED.
  
 6F) SUBSTITUTION NOTE: 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 7) A1.1 VERSES A7.2.1 & S1.1 A11 INDICATES A SUMP IN
 THE ELEVATOR PIT, NONE OF THE OTHER SHEETS INDICATE
 SUCH SUMP. 2010 FBC-B 3004.4 THE EXCEPTION ALLOWS FOR
 SUMP PITS AND ASSOCIATED PLUMBING SUMP PUMP. PLEASE
 PROVIDE THE MANUFACTURERS SPEC FOR THE ELEVATOR TO BE
 IF THEY REQUIRE A SUMP, NOTE IF FIRE SPRIJNKLERS ARE
 ACTIVATED WHERE WILL THE WATER GO WHEN ACCUMULATED IN
 THE ELEVATOR PIT.
  
 8) LS1.1, INDICATES 1 HR GLASS WALL AT STAIR # 1. ID
 1.2 SI-4 APPEARS TO TO FOR FWIRE GLASS DETAIL AT STAIR
 # 1, WRONG HEADING, SI-9 DOES INDICATE THE USE OF 1
 HOUR FIRE RATED WIRE GLASS IN THE GLASS WALLS AND
 DOORS. PLEASE REVIEW THE MAXIMUM AREA ALLOWED IN EXIT
 DOORS FBC-B 715.4.4, 715.4.4.1 715.4.5 AS WELL AS TABLE
 715.5.4 FOR WIRE GLASS PANELS AND TABLE 715.5 FIRE
 WINDOW ASSEMBLIES IN FIRE BARRIERS (1 HR VERTICAL
 EXITS.
  
 9) SHEET LS1.1 INDICATES THE DOORS TO STAIRWELL # 1 TO
 BE HELD OPEN. SHEET A10.1 THE DOORS SCHEDULE TO
 STAIRWELL 1 ( 102.01) DO NOT INDICATE HOW THEY ARE
 GOING TO STAY OPEN OR COMPLIANCE WITH FBC-B 715.4.8.
 DOOR CLOSING, THIS REQUIREMENT WILL NEED TO BE
 INDICATED FOR ALL STAIRWELL DOORS.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-31 Cont ID  
Sent By shill Date 2013-07-31 Time 09:25 Rev Time 0.00
Received By shill Date 2013-07-15 Time 09:06 Sent To  
Notes
2013-07-31 09:26:207/31 SEE BUILDING REVIEW #2
  
2013-06-18 11:48:38DOING INCOMING AND ENTERED THIS STOP BY MISTAKE. NO
 REVIEW DONE. JG.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-12-16 Cont ID  
Sent By albarran Date 2013-12-16 Time 15:27 Rev Time 0.00
Received By albarran Date 2013-12-16 Time 15:02 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-07-30 Cont ID  
Sent By dharvey Date 2013-07-30 Time 14:32 Rev Time 0.00
Received By dharvey Date 2013-07-30 Time 13:48 Sent To  
Notes
2013-07-30 14:32:25PROVIDE ARC-FLASH NOTICES AND WARNINGS PER NEC 110.16.
 PROVIDE INTERSYSTEM BONDING POINT PER 250.94. BOND ALL
 INTERIOR METAL PIPING SYSTEMS PER 250.94. PANEL B IS
 225A RATED AND PROTECTED AT 100A? LOAD IS REPRESENTED
 AS 197A ON PANEL B. SEPARATE PERMITS REQUIRED FOR FIRE
 ALARM, LOW VOLTAGE, DATA, TELEPHONE, AUDIO AND VIDEO
 SYSTEMS, ETC.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2013-07-23 Cont ID  
Sent By mgonzale Date 2013-07-23 Time   Rev Time 1.00
Received By mgonzale Date 2013-07-23 Time   Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2014-05-09 Cont ID  
Sent By skennedy Date 2014-05-11 Time 10:54 Rev Time 0.00
Received By wjolin Date 2014-05-09 Time 12:20 Sent To  
Notes
2014-05-09 12:29:33114 SOUTH OLIVE AVENUE
 PERMIT #13060638
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE CLASS 1 STANDPIPE WITH 2-1/2" HOSE VALVES IS
 REQUIRED TO PROTECT BOTH EXIT STAIR ENCLOSURES. PROVIDE
 STANDPIPE COVERAGE IN STAIR #1.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2014-04-22 Cont ID  
Sent By wjolin Date 2014-04-22 Time 15:39 Rev Time 0.00
Received By wjolin Date 2014-04-22 Time 15:37 Sent To  
Notes
2014-04-22 15:39:52114 SOUTH OLIVE AVENUE
 PERMIT #13060638
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENTS
 SHEET FS1.1: THE PLANS ARE SEVERELY LACKING THE
 REQUIRED INFORMATION THAT SHOULD BE PROVIDED ON FIRE
 PROTECTION ENGINEERING DOCUMENTS. BELOW IS A LIST (NOT
 ALL INCLUSIVE) OF INFORMATION THAT IS INCORRECT OR
 MISSING:
 - NO WATER SUPPLY POINT OF SERVICE OR PIPE SIZES
 - NO BACKFLOW PREVENTER
 - NO UNDERGROUND WATER MAIN LOCATIONS OR SIZES
 - NO SIAMESE FIRE DEPARTMENT CONNECTION
 - NO STANDPIPE RISER SIZE
 - NO WATER SUPPLY DATA
 - NO INDICATION OF HAZARD CLASSIFICATION OR DESIGN
 DENSITY FOR SPRINKLER SYSTEM
 - NO STANDPIPE RISER OR HOSE VALVES LOCATED IN STAIR #1
 - STANDPIPE INDICATES AN ALARM CHECK VALVE?
 - NO FIRE DEPARTMENT HOSE VALVES PROVIDED ON MAIN
 LANDINGS OF 3RD FLOOR STAIRS
 - SIDEWALL SPRINKLER SHALL BE LOCATED AT THE BOTTOM OF
 THE ELEVATOR SHAFT, NOT AT THE TOP OF THE SHAFT
 - NO COMBINATION SPRINKLER/STANDPIPE RISER DIAGRAM
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2014-01-31 Cont ID  
Sent By wjolin Date 2014-01-31 Time 12:01 Rev Time 0.00
Received By wjolin Date 2014-01-31 Time 09:57 Sent To  
Notes
2014-01-31 11:24:42114 SOUTH OLIVE AVENUE
 PERMIT #13060638
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET FS1.1: THE PLANS ARE SEVERELY LACKING THE
 REQUIRED INFORMATION THAT SHOULD BE PROVIDED ON FIRE
 PROTECTION ENGINEERING DOCUMENTS. BELOW IS A LIST (NOT
 ALL INCLUSIVE) OF INFORMATION THAT IS INCORRECT OR
 MISSING:
 - NO WATER SUPPLY POINT OF SERVICE OR PIPE SIZES
 - NO BACKFLOW PREVENTER
 - NO UNDERGROUND WATER MAIN LOCATIONS OR SIZES
 - NO SIAMESE FIRE DEPARTMENT CONNECTION
 - NO STANPIPE RISER SIZE
 - NO WATER SUPPLY DATA
 - NO INDICATION OF HAZARD CLASSIFICATION OR DESIGN
 DENSITY FOR SPRINKLER SYSTEM
 - NO STANDPIPE RISER OR HOSE VALVES LOCATED IN STAIR #1
 - STANDPIPE INDICATES AN ALARM CHECK VALVE?
 - NO FIRE DEPARTMENT HOSE VALVES PROVIDED ON MAIN
 LANDINGS OF 3RD FLOOR STAIRS
 - SIDEWALL SPRINKLER SHALL BE LOCATED AT THE BOTTOM OF
 THE ELEVATOR SHAFT, NOT AT THE TOP OF THE SHAFT
 - NO COMBINATION SPRINKLER/STANDPIPE RISER DIAGRAM
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-12-11 Cont ID  
Sent By wjolin Date 2013-12-11 Time 14:52 Rev Time 0.00
Received By wjolin Date 2013-12-11 Time 13:02 Sent To  
Notes
2013-12-11 14:52:23114 SOUTH OLIVE AVENUE
 PERMIT #13060638
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2009 EDITION WITH FLORIDA AMENDMENTS.)
  
  
 REPEAT COMMENT: SHEET A7.2.1.: THE STAIR GUARDRAILS FOR
 STAIR #1 ARE ONLY 30-INCHES TALL AND NEED TO BE AT
 LEAST 42-INCHES TALL. THE GUARDS SHALL BE MEASURED
 VERTICALLY ABOVE THE LEADING EDGE OF THE TREAD OR
 ADJACENT WALKING SURFACE.
  
 REPEAT COMMENT: SPRINKLER: PER FLORIDA ADMINISTRATIVE
 CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 REPEAT COMMENT: SPRINKLER: INDICATE THE LOCATION AND
 DISTANCE TO THE NEAREST FIRE HYDRANT.
  
 REPEAT COMMENT: SPRINKLER: FOR A FULLY SPRINKLERED
 BUILDING, A CLASS I FIRE PROTECTION STANDPIPE IS
 REQUIRED WHEN THE FLOOR LEVEL OF THE HIGHEST STORY IS
 LOCATED MORE THAN 30 FEET ABOVE THE LOWEST LEVEL OF
 FIRE DEPARTMENT VEHICHLE ACCESS.
  
 REPEAT COMMENT: ELEVATOR: PER SECTION 9.4.3 - FIRE
 FIGHTERS EMERGENCY OPERATIONS: ALL NEW ELEVATORS SHALL
 CONFORM TO THE FIRE FIGHTERS EMERGENCY OPERATIONS
 REQUIREMENTS OF ASME A17.1/CSA B44, SAFETY CODE FOR
 ELEVATORS AND ESCALATORS.
  
 PLUMBING: SHEETS P2.1-P2.3 INDICATE PLUMBING PIPING
 (RAIN LEADERS?) BEING ROUTED INTO AND DOWN THROUGH THE
 FIRE RATED EXIT STAIRS. PER SECTION NFPA 101 SECTION
 7.1.3.2.1, PENETRATIONS INTO, AND OPENINGS THROUGH, AN
 EXIT ENCLOSURE ASSEMBLY SHALL BE LIMITED TO DOOR
 ASSEMBLIES FROM NORMALLY OCCUPIED SPACES AND CORRIDORS,
 REQUIRED EXIT DOOR OPENINGS, ELECTRICAL CONDUIT SERVING
 THE EXIT ENCLOSURE, DUCTWORK AND EQUIPMENT NECESSARY
 FOR INDEPENDENT STAIR PRESSURIZATION, WATER OR STEAM
 PIPING NECESSARY FOR THE HEATING OR COOLING OF THE EXIT
 ENCLOSURE, SPRINKLER PIPING, STANDPIPES, AND
 PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE
 CIRCUITS ARE INSTALLED IN METAL CONDUIT AND THE
 PENETRATIONS ARE PROTECTED.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-06-26 Cont ID  
Sent By wjolin Date 2013-06-26 Time 14:50 Rev Time 0.00
Received By wjolin Date 2013-06-26 Time 13:15 Sent To  
Notes
2013-06-26 14:50:07114 SOUTH OLIVE AVENUE
 PERMIT #13060638
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2009 EDITION WITH FLORIDA AMENDMENTS.)
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING ALL
 CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 SHEET LS1.1: PER SECTION 12.2.5.1.2, A DEAD-END IN AN
 ASSEMBLY OCCUPANCY SHALL NOT EXCEED 20 FEET AND THE
 COMMON PATH OF TRAVEL SHALL NOT EXCEED 20 FEET WHEN THE
 PATH SERVES MORE THAN 50 OCCUPANTS.
  
 SHEET A7.2.1.: THE STAIR GUARDRAIL DOES NOT APPEAR TO
 BE AT LEAST 42-INCHES TALL.
  
 SHEET ID1.2: DETAIL #12 (REFERENCED FROM SHEET A1.2)
 INDICATES THE STAIR GLAZING AS NON-FIRE RATED; HOWEVER,
 DETAIL #10 INDICATES THE GLAZING IS FIRE-RATED.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED
 SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED
 IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE
 ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SPRINKLER: PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
 SPRINKLER: INDICATE THE LOCATION AND DISTANCE TO THE
 NEAREST FIRE HYDRANT.
  
 SPRINKLER: FOR A FULLY SPRINKLERED BUILDING, A CLASS I
 FIRE PROTECTION STANDPIPE IS REQUIRED WHEN THE FLOOR
 LEVEL OF THE HIGHEST STORY IS LOCATED MORE THAN 30 FEET
 ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICHLE
 ACCESS.
  
 SHEET FS1.1: ALL THE FIRE SPRINKLER FLOOR PLANS ARE
 INDICATED AS "FIRE ALARM PLANS."
  
 SHEET E4.1: ALL THREE FLOOR PLANS ARE EXACTLY THE SAME.
  
 FIRE ALARM: PER SECTION 12.3.4.3.3, PROVIDE
 SPEAKER/STROBE NOTIFICATION APPLIANCES AS ASSEMBLY
 OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING 300
 OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY
 VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS.
  
 FIRE ALARM: PROVIDE A PRE-RECORDED FIRE ALARM
 EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS
 BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT,
 AND EXIT THE BUILDING IMMEDIATELY. DO NOT USE THE
 ELEVATOR.
  
 FIRE ALARM: INDICATE THE LOCATION OF THE FACP. NEW FIRE
 ALARM SYSTEMS SHALL BE FULLY ADDRESSABLE. A CERTIFICATE
 OF COMPLETION AND A THIRD PARTY MONITORING/VERIFICATION
 (UL OR ETL) CERTIFICATE SHALL BE PROVIDED AT TIME OF
 FINAL FIRE ALARM INSPECTION. PER LOCAL AHJ POLICY, DUCT
 SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE ALARM
 CONDITION. ELEVATOR RECALL SHALL BE INTERFACED WITH
 FIRE ALARM SYSTEM.
  
 ELEVATOR: PER SECTION 9.4.3 - FIRE FIGHTERS EMERGENCY
 OPERATIONS: ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTERS EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-04-26 Cont ID  
Sent By jwitmer Date 2014-04-26 Time 11:22 Rev Time 0.00
Received By jwitmer Date 2014-04-26 Time 11:21 Sent To  
Notes
2014-04-26 11:30:19GAS REVIEWED GAS REVIEW : TABLE 402.4(2) SCH. 40
 METALLIC PIPE
 PROVISO: 404.3 PIPING IN CONCEALED LOCATIONS.
 PORTIONS OF A PIPING SYSTEM INSTALLED IN CONCEALED
 LOCATIONS SHALL NOT HAVE UNIONS, TUBING FITTINGS, RIGHT
 AND LEFT COUPLINGS, BUSHINGS, COMPRESSION COUPLINGS AND
 SWING JOINTS MADE BY COMBINATIONS OF FITTINGS.
 EXCEPTIONS:
 1. TUBING JOINED BY BRAZING.
 2. FITTINGS LISTED FOR USE IN CONCEALED LOCATIONS
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-07-31 Cont ID  
Sent By lwagner Date 2013-07-31 Time 08:51 Rev Time 0.00
Received By lwagner Date 2013-06-28 Time 15:44 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-07-30 Cont ID  
Sent By fmittner Date 2013-07-30 Time 11:42 Rev Time 0.00
Received By fmittner Date 2013-07-30 Time 11:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-05-11 Cont ID  
Sent By skennedy Date 2014-05-11 Time 10:54 Rev Time 0.00
Received By skennedy Date 2014-05-01 Time 15:08 Sent To FIRE
Notes
2014-05-01 15:08:46GIVEN TO WJOLIN.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-04-26 Cont ID  
Sent By jwitmer Date 2014-04-26 Time 13:02 Rev Time 0.00
Received By jwitmer Date 2014-04-07 Time 15:53 Sent To  
Notes
2014-04-08 15:53:41C25

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-02-12 Cont ID  
Sent By jwitmer Date 2014-02-12 Time 10:47 Rev Time 0.00
Received By jwitmer Date 2014-01-15 Time 09:03 Sent To  
Notes
2014-01-16 09:04:23INCOMING SENT TO C-25. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-16 Cont ID  
Sent By hmoser Date 2013-12-16 Time 15:29 Rev Time 0.00
Received By hmoser Date 2013-10-31 Time 10:50 Sent To  
Notes
2013-10-31 17:58:28INCOMING SENT TO C-26 .JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-31 Cont ID  
Sent By shill Date 2013-07-31 Time 09:26 Rev Time 0.00
Received By shill Date 2013-06-17 Time 11:43 Sent To  
Notes
2013-06-18 11:43:50SENT TO C28 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2014-04-26 Cont ID  
Sent By jwitmer Date 2014-04-26 Time 10:30 Rev Time 0.00
Received By jwitmer Date 2014-04-26 Time 10:27 Sent To  
Notes
2014-04-26 10:30:32FEB. 18/2014
 PALM BEACH COUNTY IMPACT FEE OFFICE
 MU 2014-3565
 A-2 RESTARAUNT
 SQ. FT. 10,284
 FEES ASSESSED:
 $19,900.78.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2014-02-01 Cont ID  
Sent By jwitmer Date 2014-02-01 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2014-02-01 Time 12:29 Sent To  
Notes
2014-02-01 12:30:09BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-11-22 Cont ID  
Sent By jwitmer Date 2013-11-22 Time 13:22 Rev Time 0.00
Received By jwitmer Date 2013-11-22 Time 13:22 Sent To  
Notes
2013-11-22 13:22:32BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-07-17 Cont ID  
Sent By jwitmer Date 2013-07-17 Time 11:53 Rev Time 0.00
Received By jwitmer Date 2013-07-17 Time 11:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-12-16 Cont ID  
Sent By hmoser Date 2013-12-16 Time 15:25 Rev Time 0.00
Received By hmoser Date 2013-12-16 Time 14:09 Sent To  
Notes
2013-12-16 15:29:01KITCHEN HOOD AND COOLERS WERE NOT REVIEWED.
 HOODS AND COOLERS REQUIRE SEPARATE PERMIT APPLICATION
 PLANS AND PERMIT.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805- 6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-07-16 Cont ID  
Sent By hmoser Date 2013-07-16 Time 13:36 Rev Time 0.00
Received By hmoser Date 2013-07-16 Time 08:56 Sent To  
Notes
2013-07-16 13:36:39PLANS DENIED
 1) IN REGARDS TO RTU ATTACHMENT TO ROOF CURB
 DETAIL. PAGE M0.1 OF PLANS REFER TO TABLE 1509.7
 CLEARANCE BELOW RAISED ROOF MOUNTED MECHANICAL
 UNITS 2010 FBC.
 2) SAME DETAIL PAGE M0.1 OF PLANS
 MINIMUM DESIGN WIND LOADS OF 170 MPH 2010 FBC
 3) PROVIDE A DETAIL FROM THE ENGINEER ON THE CURB TO
 ROOF TIE DOWN PROVIDE SCREW OR BOLT SIZE PER SECTION
 301.12 WIND RESISTANCE 2010 FBC (M)
 4) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS
 FOR OUT DOOR AIR AND EXHAUST. 2010 FLORIDA ENERGY CODE
 5) SEPARATE APPLICATION , PLANS AND PERMIT REQUIRED FOR
 HOOD AND COOLERS.
 6) IN REGARDS TO AIR HANDLERS 1,2,3 AND 4 REFER TO
 SECTION
 306.1 ACCESS FOR MAINTENANCE AND REPLACEMENT. 1210
 FBC (M)
 7) PROVIDE PRODUCT APPROVAL FOR OUT SIDE GRILLS
 AND WALL CAPS PER SECTION 107.3.4.1 2010 FBC
 8) OUT SIDE AIR DUCT SHALL BE METAL PER DUCT BOARD
 MANUFACTURER'S ENGINEER.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-04-26 Cont ID  
Sent By jwitmer Date 2014-04-26 Time 11:05 Rev Time 0.00
Received By jwitmer Date 2014-04-26 Time 11:05 Sent To  
Notes
2014-04-26 11:15:51GREASE INTERCEPTOR SIZED SHEET P2.1 SCHIER MODEL GB-75
 / 75 GPM FLOW RATE / 616 GREASE HOLDING CAPACITY.

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-11-27 Cont ID  
Sent By lwagner Date 2013-11-27 Time 14:10 Rev Time 0.00
Received By lwagner Date 2013-11-25 Time 14:57 Sent To  
Notes
2013-11-27 13:51:03***PROVISO***
 ROOF DRAINAGE SHALL BE TO AN APPROVED PLACE OF
 DISPOSAL:
 1101.2 WHERE REQUIRED.
 ALL ROOFS, PAVED AREAS, YARDS, COURTS AND COURTYARDS
 SHALL DRAIN INTO A SEPARATE STORM SEWER SYSTEM, OR A
 COMBINED SEWER SYSTEM, OR TO AN APPROVED PLACE OF
 DISPOSAL. FOR ONE- AND TWO-FAMILY DWELLINGS, AND WHERE
 APPROVED, STORM WATER IS PERMITTED TO DISCHARGE ONTO
 FLAT AREAS, SUCH AS STREETS OR LAWNS, PROVIDED THAT THE
 STORM WATER FLOWS AWAY FROM THE BUILDING.

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-07-01 Cont ID  
Sent By lwagner Date 2013-07-01 Time 14:43 Rev Time 0.00
Received By lwagner Date 2013-06-28 Time 13:30 Sent To  
Notes
2013-07-01 14:41:38FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET A 1.2 THE RESTROOMS HAVE 6 OR MORE REQUIRED
 FACILITIES. THE UNISEX RESTROON MAY BE USED IN THE
 REQUIRED FIXTURE COUNT FOR MALE OR FEMALE.
 403.5 UNISEX TOILET AND BATHING ROOMS.
 IN ASSEMBLY AND MERCANTILE OCCUPANCIES, AN ACCESSIBLE
 UNISEX TOILET ROOM SHALL BE PROVIDED WHERE AN AGGREGATE
 OF SIX OR MORE MALE AND FEMALE WATER CLOSETS IS
 REQUIRED. IN BUILDINGS OF MIXED OCCUPANCY, ONLY THOSE
 WATER CLOSETS REQUIRED FOR THE ASSEMBLY OR MERCANTILE
 OCCUPANCY SHALL BE USED TO DETERMINE THE UNISEX TOILET
 ROOM REQUIREMENT. IN RECREATIONAL FACILITIES WHERE
 SEPARATE-SEX BATHING ROOMS ARE PROVIDED, AN ACCESSIBLE
 UNISEX BATHING ROOM SHALL BE PROVIDED. FIXTURES LOCATED
 WITHIN UNISEX TOILET AND BATHING ROOMS SHALL BE
 INCLUDED IN DETERMINING THE NUMBER OF FIXTURES PROVIDED
 IN AN OCCUPANCY.
  
 2. SHEET P 2.2 THE RAIN WATER LINES ARE NOT LABELED FOR
 SIZE OR SQUARE FEET.
  
 3. SUMP PUMPS OR FLOOR DRAINS ARE REQUIRED IN ELEVATORS
 WITH FIREFIGHTERS' EMERGENCY OPERATION. THE DRAIN SHALL
 BE INDIRECT TO THE SANITARY.
 ASME A17.1 2.2.2.5
 P 301.6 EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS
 SHALL BE PERMITTED AT THE BASE OF THE SHAFT, PROVIDED
 THAT THEY ARE INDIRECTLY CONNECTED TO THE PLUMBING
 SYSTEM AND COMPLY WITH SECTION 1003.4.
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2014-02-21 Cont ID  
Sent By   Date 2014-02-21 Time   Rev Time 0.00
Received By   Date 2014-02-21 Time   Sent To I
Notes
2014-02-21 10:03:56CHANGED ADDRESS: 310 CLEMATIS STREET TO 114 SOUTH OLIVE
 AVENUE.

Review Stop Z ZONING
Rev No 1 Status P Date 2013-07-30 Cont ID  
Sent By aaponte Date 2013-07-30 Time 09:59 Rev Time 0.00
Received By aaponte Date 2013-07-30 Time 09:59 Sent To  
Notes
2013-06-20 09:26:506/20/13