| Notes |
| 2013-06-17 12:40:28 | | | | 13060559 | | | 3436 @ 45TH ST. | | | AT&T ROOF TOP PEDESTAL | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE TWO SETS OF PLANS. INCLUDE AN ELECTRICAL RISER | | | SHOWING ALL WIRE AND CONDUIT SIZES. INDICATE THE FAULT | | | CURRENT RATING OF THE EQUIPMENT. PROVIDE SPECIFICATIONS | | | ON THE NEW ELECTRIC PEDESTAL. NEC 110.9, 215.5 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6718 | | | | | | |
|
|