Plan Review Details - Permit 13060323
Plan Review Stops For Permit 13060323
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-07-14 Cont ID  
Sent By jwitmer Date 2013-07-14 Time 07:37 Rev Time 0.00
Received By jwitmer Date 2013-07-14 Time 07:03 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-07-01 Cont ID  
Sent By jwitmer Date 2013-07-01 Time 07:36 Rev Time 0.00
Received By jwitmer Date 2013-07-01 Time 07:08 Sent To  
Notes
2013-07-01 07:36:00BUILDING PLAN REVIEW
 PERMIT: 13060323
 ADD: 400 N FLAGLER # 2004
 CONT: CAMBRIDGE CONSTRUCTION
 TEL: (561)784-3722
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: 7/01/2013
 ACTION: DENIED
  
 1) DESCCRIPTION OF WORK INDICATES STRIPPING FLOORS AND
 NEW FLOOR TILE PROVIDE CODE COMPLIANCE FOR:
 FBC-B 2010 603.2 EXCEPTION (1)
 FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 2) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 WHILE PROTECTO MAT MAY MEET THE SOUND REDUCTION
 REQUIREMENTS OF 1207.3 THIS PRODUCT DOES NOT MEET THE
 REQUIREMENTS OF 603.2 EXCETION # 1. 802.1 PROVIDES THE
 DEFINITION AND TESTING METHOD FOR FLAME SPREAD INDEX:
 2010 FBC-B 802.1FLAME SPREAD INDEX. A COMPARATIVE
 MEASURE, EXPRESSED AS A DIMENSIONLESS NUMBER, DERIVED
 FROM VISUAL MEASUREMENTS OF THE SPREAD OF FLAME VERSUS
 TIME FOR A MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  
 3-5) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-12 Cont ID  
Sent By jwitmer Date 2013-06-12 Time 13:01 Rev Time 0.00
Received By jwitmer Date 2013-06-12 Time 12:30 Sent To  
Notes
2013-06-12 13:30:27BUILDING PLAN REVIEW
 PERMIT: 13060323
 ADD: 400 N FLAGLER # 2004
 CONT: CAMBRIDGE CONSTRUCTION
 TEL: (561)784-3722
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 6/12/2013
 ACTION: DENIED
  
 1) DESCCRIPTION OF WORK INDICATES STRIPPING FLOORS AND
 NEW FLOOR TILE PROVIDE CODE COMPLIANCE FOR:
 FBC-B 2010 603.2 EXCEPTION (1)
 FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 2) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3) SCOPE OF WORK INDICATES TTHE REPLACEMENT OF SLIDING
 GLASS DOORS, MISSING WIND DESIGN CRITERIA:
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
 NOTE A "D" EXPOSURE!!!
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-07-15 Cont ID  
Sent By dharvey Date 2013-07-15 Time 16:23 Rev Time 0.00
Received By dharvey Date 2013-07-15 Time 15:45 Sent To  
Notes
2013-07-15 16:19:57SCOPE OF ELECTRICLA WORK NOT CLEAR. PLAN INDICATES ONLY
 A SWITCH AND PADDLE FAN. PLAN ALSO INDICATES WALLS
 BEING REMOVED AND KITCHEN BEING REMOVED. BOTH BEING
 REPLACED. ALL WORK SUBJECT TO FIELD INSPECTION,
 VERIFICATION AND COMPLIANCE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-07-01 Cont ID  
Sent By dharvey Date 2013-07-01 Time 12:32 Rev Time 0.00
Received By dharvey Date 2013-07-01 Time 12:26 Sent To  
Notes
2013-07-01 12:35:34THE SCOPE OF THE ELECTRICAL WORK IS NOT CLEAR.
 RECOMMEND AN ELECTRICAL PERMIT BE SUBMITTED WITH THE
 SCOPE OF THE WORK PROPOSED.
  
 VERIFY THAT THE REQUIRED WORKING CLEARANCES AND
 DEDICATED WORKING SPACE HAS BEEN PROVIDED FOR THE
 ELECTRICAL EQUIPMENT AND PANEL BOARDS. NEC 110.26,
 240.24, 408.17
  
  
 RL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-06-12 Cont ID  
Sent By dharvey Date 2013-06-12 Time 14:53 Rev Time 0.00
Received By dharvey Date 2013-06-12 Time 14:53 Sent To  
Notes
2013-06-12 14:57:266-12-13
  
 PLEASE INDICATE THE USE OF ARC FAULT CIRCUIT BREAKERS
 PLEASE INDICATE TWO SEPERATE CIRCUITS. ONE FOR EACH
 LOCATION
 WHAT SIZE CIRCUIT BREAKERS ARE TO BE INSTALLED.
 WHAT SIZE CONDUCTORS ARE TO BE INSTALLED?
 IS THIS A STANDARD HOUSE CEILING FAN? WHAT IS THE
 AMPERAGE?
 VB
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-07-16 Cont ID  
Sent By shill Date 2013-07-16 Time 08:11 Rev Time 0.00
Received By shill Date 2013-07-10 Time 09:23 Sent To  
Notes
2013-07-11 09:25:46SENT TO B2 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-01 Cont ID  
Sent By dharvey Date 2013-07-01 Time 12:36 Rev Time 0.00
Received By dharvey Date 2013-06-21 Time 14:28 Sent To  
Notes
2013-06-21 14:29:12RESUBMITTAL SENT TO B23 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-18 Cont ID  
Sent By lwagner Date 2013-06-18 Time 12:38 Rev Time 0.00
Received By lwagner Date 2013-06-10 Time 16:17 Sent To  
Notes
2013-06-10 16:24:21*EXPEDITED*
 B--23

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-06-18 Cont ID  
Sent By lwagner Date 2013-06-18 Time 12:38 Rev Time 0.00
Received By lwagner Date 2013-06-18 Time 12:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-06-17 Cont ID  
Sent By ajones Date 2013-06-17 Time 13:26 Rev Time 0.00
Received By ajones Date 2013-06-17 Time 13:26 Sent To  
Notes
***NONE***