Plan Review Details - Permit 13060277
Plan Review Stops For Permit 13060277
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-02-26 Cont ID  
Sent By jwitmer Date 2014-02-26 Time 06:45 Rev Time 0.00
Received By jwitmer Date 2014-02-26 Time 06:01 Sent To  
Notes
2014-02-26 06:45:22BUILDING PROVISO:
 NOA: 13-0219.15
 CARLISLE SURE-WELD SINGLE PLY TPO ROOF SYSTEM OVER
 LIGHTWEIGHT CONCRETE DECKS
 NONE OF THE SUB-SYSTEMS WERE IDENTIFIED AS PRODUCT TO
 BE INSTALLED
 MAXIMUM DESIGN PRESSURE??? LIMITATION # 9 NO ENHANCED
 FASTENING ALLOWED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-01-10 Cont ID  
Sent By jwitmer Date 2014-01-10 Time 09:47 Rev Time 0.00
Received By jwitmer Date 2014-01-10 Time 09:33 Sent To  
Notes
2014-01-10 09:34:51BUILDING PLAN REVIEW
 PERMIT: 13060277
 ADD: 6651 N JOG RD ELECTRIC ROOM # 4
 CONT: EMJ
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN 10/2014
 ACTION: DENIED
  
 THE PRODUCT APPROVALS SUBMITTED ARE INCOMPLETE:
 1A) NOA 13-0617.20 ELASTIZELL LIGHTWEIGHT INSUL. ON
 CONCRETE DECKS IS INCOMPLETE, ONLY THE COVER SHEET
 SUBMITTED REPORT INDICATES 12 PAGES, CIRCLE WHICH
 SUB-SYSTEM TO BE INSTALLED.
  
 1B) NOA 13-0219.15 CARLISLE SURE WELD SINGLE PLY TPO IS
 INCOMPLETE, ONLY THE COVER SHEET SUBMITTED REPORT
 INDICATES 10 PAGES, CIRCLE WHICH SUB-SYSTEM TO BE
 INSTALLED.
  
 1C) 11-1103.01 GREENHECK ALUMINUM LOVER IS INCOMPLETE,
 ONLY THE COVER SHEET SUBMITTED, NO TECHNICAL SHEETS,
 PLEASE IDENTIFY WHICH SUB-SYSTEM IS TO BE INSTALLED
 UNDER THIS PERMIT.
  
 1D) 12-0305.14 INGERSALL-RAND OUTSWINNG DOOR W/ PANIC
 EXIT DEVICES. ONLY THE COVER SHEET SUBMITTED, NO
 TECHNICAL SHEETS, PLEASE IDENTIFY WHICH SUB-SYSTEM IS
 TO BE INSTALLED UNDER THIS PERMIT.
  
 1E) 12-0305.13 INGERSALL-RAND OUTSWINNG DOUBLE DOOR W/
 PANIC EXIT DEVICES. ONLY THE COVER SHEET SUBMITTED, NO
 TECHNICAL SHEETS, PLEASE IDENTIFY WHICH SUB-SYSTEM IS
 TO BE INSTALLED UNDER THIS PERMIT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-12 Cont ID  
Sent By jwitmer Date 2013-07-12 Time 16:38 Rev Time 0.00
Received By jwitmer Date 2013-07-12 Time 11:01 Sent To  
Notes
2013-07-12 15:35:01BUILDING PLAN REVIEW
 PERMIT: 13060277
 ADD: 6671 N JOG RD ELEC ROOM # 4
 CONT: KBR CONSTRUCTION
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 12/2013
 ACTION: DENIED
  
 1) SHEET 100-A1.1 INDICATES A BATTERY ROOM # 101.
 PLEASE PROVIDE ADDITIONAL INFORMATION IN REGARDS TO THE
 TYPE AND AMOUNT OF BATTERIES THAT WIL BE HOUSED IN THIS
 ROOM. PLEASE REVIEW THE 2010 FBC-B TABLE
 508.2.5. STATIONARY STORAGE BATTERY SYSTEMS HAVING A
 LIQUID ELECTROLYTE CAPACITY OF MORE THAN 50 GALLONS, OR
 A LITHIUM-ION CAPACITY OF 1,000 POUNDS USED FOR
 FACILITY STANDBY POWER, EMERGENCY POWER OR
 UNINTERRUPTED POWER SUPPLIES. 1 HOUR IN GROUP B, F, M,
 S AND U OCCUPANCIES;.
  
 2) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 907.2.23
 SMOKE DETECTION SYSTEMS IS REQUIRED BECAUSE OF FBC-B
 SECTION TABLE 508.2.5.
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WALL LOUVERS,
 (C) ROOFING PRODUCTS AND ASSEMBLIES
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-01-17 Cont ID  
Sent By dharvey Date 2014-01-17 Time 07:28 Rev Time 0.00
Received By dharvey Date 2014-01-17 Time 07:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-08-02 Cont ID  
Sent By dharvey Date 2013-08-02 Time 16:55 Rev Time 0.00
Received By dharvey Date 2013-08-02 Time 16:10 Sent To  
Notes
2013-08-02 16:54:539/26/13 RESPONDED TO EMAILS FROM MICHAEL SANCHEZ
 REGARDING THE CLASSIFICATION OF THE BUILDING AND THE
 SEPARATION OF AREAS. INFORMATION HAS BEEN PROVIDED
 STATING "THE RECEPTACLES, LIGHT FIXTURES AND EXHAUST
 FANS SERVING THE SPACE HAVE BEEN DESIGNED TO
 ACCOMMODATE ?EXPLOSION PROOF DESIGN CRITERIA? AND ARE
 NOTED AS SUCH ON THE DESIGN PLANS ALREADY SUBMITTED."
 INFORMATION REGARDING THE BRAND, MODEL AND LISTING
 INFORMATION FOR THE EQUIPMENT TO BE INSTALLED NEEDS TO
 BE CALLED OUT ON THE PLANS AND THE CLASSIFIED AREAS OF
 THE BUILDING NEED TO BE IDENTIFIED CLEARLY AND
 DELINEATED AS TO WHICH SECTIONS ARE DEFINED AS
 CLASSIFIED AND HOW THE OTHER AREAS ARE TO BE SEPARATED.
 PLANS WILL BE PULLED AND RE-REVIEWED TO SEE IF THIS
 INFORMATION WAS PROVIDED AND MISSED ON THE ORIGINAL
 REVIEW. DH 6:50 AM
  
 8/2/13 PLANS CALL FOR THIS ROOM TO BE RATED A SCLASS I,
 DIV 2. PLEASE DEFINE THE HAZARD SO THE EQUIPMENT AND
 LOCATIONS CAN BE PROPERLY EVALUATED. IT IS NOT KNOWN TO
 THIS REVIEWER EXACTLY WHAT HAZARD IS ANTICIPATED OR
 WHAT SPECIFIC GRAVITY OF HAZARD TO EVALUATE FOR. REVIEW
 CANNOT BE COMPLETED UNTIL THESE QUESTIONS ARE ANSWERED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-12-26 Cont ID  
Sent By wjolin Date 2013-12-26 Time 11:18 Rev Time 0.00
Received By wjolin Date 2013-12-26 Time 10:35 Sent To  
Notes
2013-12-26 11:12:456651 NORTH JOG ROAD - ELECTRICAL ROOM
 PERMIT #13060277
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL PREVIOUS REVIEW COMMENTS HAVE BEEN ADDRESSED.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-06-19 Cont ID  
Sent By wjolin Date 2013-06-19 Time 09:35 Rev Time 0.00
Received By wjolin Date 2013-06-18 Time 12:12 Sent To  
Notes
2013-06-18 15:02:256651 NORTH JOG ROAD - ELECTRICAL ROOM
 PERMIT #13060277
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 GENERAL: PROVIDE BUILDING NAME OR ADDRESS ON THE
 BUILDING. NUMBERS/LETTERS SHALL BE ATTACHED TO THE
 BUILDING AND BE AT LEAST SIX-INCHES IN HEIGHT WITH
 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND.
  
 SHEET 100-EE-100: PLAN INDICATES BATTERY ROOM #101 (240
 SQ.FT.) TO BE A HAZARDOUS LOCATION. PER NFPA 101
 SECTION 7.11.4, NOT LESS THAN TWO MEANS OF EGRESS SHALL
 BE PROVIDED FROM EACH BUILDING OR HAZARDOUS AREA
 EXCEEDING 200 SQ.FT. PER SECTION 7.5.1.3.3, THE MINIMUM
 SEPARATION DISTANCE BETWEEN TWO EXITS OR EXIT ACCESS
 DOORS SHALL BE NOT LESS THAN ONE-HALF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA BEING SERVED.
  
 SHEET 100-A1.1: PANIC HARDWARE MAY BE NEEDED ON THE
 EXIT DOORS. PER NFPA 70 ARTICLE 110.26(C)(3): WHERE
 EQUIPMENT RATED 1200 A OR MORE THAT CONTAINS
 OVERCURRENT DEVICES, SWITCHING DEVICES, OR CONTROL
 DEVICES IS INSTALLED AND THERE ARE PERSONNEL DOORS
 INTENDED FOR ENTRANCE TO AND EGRESS FROM THE WORKING
 SPACE LESS THAN 25 FEET FROM THE NEAREST EDGE OF THE
 WORKING SPACE, THE DOORS SHALL OPEN IN THE DIRECTION OF
 EGRESS AND BE EQUIPPED WITH PANIC BARS, PRESSURE
 PLATES, OR OTHER DEVICES THAT ARE NORMALLY LATCHED BUT
 OPEN UNDER SIMPLE PRESSURE.
  
 SHEET 100-A1.1: ACCESS AROUND THE LARGE PIECE OF
 ELECTRICAL EQUIPMENT (NORTH PART OF SPACE) MAY BE
 NEEDED TO ELIMINATE THE DEAD-END WORKER SPACE CREATED
 BY THE EQUIPMENT.. PER NFPA 70 ARTICLE 110.26(C)(2):
 FOR EQUIPMENT RATED 1200 AMPERES OR MORE AND OVER 6
 FEET WIDE THAT CONTAINS OVERCURRENT DEVICES, SWITCHING
 DEVICES, OR CONTROL DEVICES, THERE SHALL BE ONE
 ENTRANCE TO AND EGRESS FROM THE REQUIRED WORKING SPACE
 NOT LESS THAN 24 INCHES WIDE AND 6.5 FEET HIGH AT EACH
 END OF THE WORKING SPACE. A SINGLE ENTRANCE TO AND
 EGRESS FROM THE REQUIRED WORKING SPACE SHALL BE
 PERMITTED WHERE EITHER OF THE CONDITIONS IN
 110.26(C)(2)(A) OR (C)(2)(B) IS MET.
  
 (A) UNOBSTRUCTED EGRESS. WHERE THE LOCATION PERMITS A
 CONTINUOUS AND UNOBSTRUCTED WAY OF EGRESS TRAVEL, A
 SINGLE ENTRANCE TO THE WORKING SPACE SHALL BE
 PERMITTED.
 (B) EXTRA WORKING SPACE. WHERE THE DEPTH OF THE WORKING
 SPACE IS TWICE THAT REQUIRED BY 110.26(A)(1), A SINGLE
 ENTRANCE SHALL BE PERMITTED. IT SHALL BE LOCATED SUCH
 THAT THE DISTANCE FROM THE EQUIPMENT TO THE NEAREST
 EDGE OF THE ENTRANCE IS NOT LESS THAN THE MINIMUM CLEAR
 DISTANCE SPECIFIED IN TABLE 110.26(A)(1) FOR EQUIPMENT
 OPERATING AT THAT VOLTAGE AND IN THAT CONDITION.
  
 SHEET 100-A1.1: VERY LITTLE INFORMATION PROVIDED FOR
 BATTERY STORAGE ROOM. DESIGN SHALL CONFORM TO NFPA 1 -
 CHAPTER 52 "STATIONARY STORAGE BATTERY SYSTEMS".
 PROVIDE ADDITIONAL INFORMATION SUCH AS THE BATTERY
 TYPES (FLOODED LEAD-ACID, FLOODED NICKEL-CADMIUM,
 LITHION-ION, VALVE REGULATED, ETC.), ELECTOLYTE
 CAPACITY, SPILL CONTROL ETC. LISTED BELOW ARE SOME ON
 THE REQUIREMENTS FROM NFPA 101 CHAPTER 52.:
  
 STATIONARY STORAGE BATTERY SYSTEMS HAVING AN
 ELECTROLYTE CAPACITY OF MORE THAN 100 GAL IN
 SPRINKLERED BUILDINGS OR 50 GAL IN UNSPRINKLERED
 BUILDINGS FOR FLOODED LEAD-ACID, NICKEL-CADMIUM, AND
 VALVE-REGULATED LEAD-ACID (VRLA) BATTERIES OR 1000 LB
 FOR LITHIUM-ION AND LITHIUM METAL POLYMER BATTERIES
 USED FOR FACILITY STANDBY POWER, EMERGENCY POWER, OR
 UNINTERRUPTED POWER SUPPLIES SHALL BE IN ACCORDANCE
 WITH CHAPTER 52 AND TABLE 52.1.
  
 52.3.4.1 ROOMS, BUILDINGS, OR AREAS CONTAINING
 FREE-FLOWING LIQUID ELECTROLYTE IN INDIVIDUAL VESSELS
 HAVING A CAPACITY OF MORE THAN 55 GAL OR MULTIPLE
 VESSELS HAVING AN AGGREGATE CAPACITY EXCEEDING 1000 GAL
 SHALL BE PROVIDED WITH SPILL CONTROL TO PREVENT THE
 FLOW OF LIQUIDS TO ADJOINING AREAS.
  
 52.3.8.1 DOORS OR ACCESSES INTO ROOMS, BUILDINGS, OR
 AREAS CONTAINING STATIONARY STORAGE BATTERY SYSTEMS
 SHALL BE PROVIDED WITH APPROVED SIGNS.
  
 52.3.8.2 THE SIGNS REQUIRED BY 52.3.8.1 SHALL STATE
 THAT THE ROOM CONTAINS STATIONARY STORAGE BATTERY
 SYSTEMS, THAT THE BATTERY ROOM CONTAINS ENERGIZED
 ELECTRICAL CIRCUITS, AND THAT THE BATTERY ELECTROLYTE,
 WHERE PRESENT, ARE CORROSIVE LIQUIDS.
  
 52.3.10 SMOKE DETECTION. AN APPROVED AUTOMATIC SMOKE
 DETECTION SYSTEM SHALL BE INSTALLED IN SUCH AREAS AND
 SUPERVISED BY AN APPROVED CENTRAL, PROPRIETARY, OR
 REMOTE STATION SERVICE OR A LOCAL ALARM THAT WILL GIVE
 AN AUDIBLE SIGNAL AT A CONSTANTLY ATTENDED LOCATION.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-02-26 Cont ID  
Sent By jwitmer Date 2014-02-26 Time 06:45 Rev Time 0.00
Received By jwitmer Date 2014-02-06 Time 16:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-17 Cont ID  
Sent By rregueir Date 2014-01-17 Time 08:26 Rev Time 0.00
Received By rregueir Date 2013-12-19 Time 14:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-14 Cont ID  
Sent By rregueir Date 2013-08-02 Time 15:59 Rev Time 0.00
Received By rregueir Date 2013-06-07 Time 15:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-07-25 Cont ID  
Sent By rregueir Date 2013-07-25 Time 11:47 Rev Time 0.00
Received By rregueir Date 2013-07-25 Time 11:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-06-24 Cont ID  
Sent By lwagner Date 2013-06-24 Time 09:15 Rev Time 0.00
Received By lwagner Date 2013-06-24 Time 08:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-12-26 Cont ID  
Sent By rregueir Date 2013-12-26 Time 11:57 Rev Time 0.00
Received By rregueir Date 2013-12-26 Time 11:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-07-12 Cont ID  
Sent By escenid Date 2013-07-12 Time 15:03 Rev Time 0.50
Received By eschneid Date 2013-07-12 Time 15:03 Sent To  
Notes
2013-07-12 15:08:46PASSED W/PROVISO
  
 1) THE BUILDING FOOTPRINT DOES NOT EXACTLY MATCH THE
 APPROVED SITE PLAN - FINAL AS BUILT PLANS SHALL BE
 SUBMITTED AS A ZONING SITE PLAN REVISION PRIOR TO C.O.
 THIS SHALL INCLUDE THE STAIRS, THE A/C BALCONY, THE
 GROUND MOUNTED UNIT AND THE ELEVATION OF THE BUILDING.
  
 STAFF OBSERVATIONS:
  
 A. THE BUILDING'S EXTERIOR TREATMENT (BRICK) DOES NOT
 MATCH THE OTHER BUILDINGS ON THE SITE.
 B. ONE OF THE COLUMNS FOR THE A/C BALCONY DOES NOT SEEM
 TO BE LOCATED IN A VERY SAFE AREA - APPROXIMATELY 5
 FEET IN FRONT OF A SET OF STAIRS.
2013-06-17 13:42:296/17/13