Plan Review Details - Permit 13060271
Plan Review Stops For Permit 13060271
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-08-01 Cont ID  
Sent By jwitmer Date 2013-08-01 Time 17:37 Rev Time 0.00
Received By jwitmer Date 2013-08-01 Time 17:00 Sent To  
Notes
2013-08-01 17:37:16BUILDING PLAN REVIEW
 PERMIT: 13060271
 ADD: 3800 WASHINGTON # 1106
 CONT: BEE CUSTOM CONTRACTORS
 TEL: (954)802-7557
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE:8/01/13
 ACTION: PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) TILE FLOORS PROVIDE DOCUMENTATION TESTING FOR CODE
 COMPLIANCE WITH:
 1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 1B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING
 FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-05 Cont ID  
Sent By jwitmer Date 2013-07-05 Time 12:57 Rev Time 0.00
Received By jwitmer Date 2013-07-05 Time 12:31 Sent To  
Notes
2013-07-05 12:57:52BUILDING PLAN REVIEW
 PERMIT: 13060271
 ADD: 3800 WASHINGTON # 1106
 CONT: BEE CUSTOM CONTRACTORS
 TEL: (954)802-7557
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 7/05/13
 ACTION: DENIED
  
 1) 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 1A) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 MINIMUM BUILDING TYPE
 BLDG FIRE SPRINKLERED
  
 1B) 107.3.5(8.) STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 PLANS DO NOT INDICATE THE MATERIALS THE SOFFITS ARE
 GOING TO BE BUILT FROM NOR THE THICKNESS OF DRYWALL.
 SIZE OF FRAMING MEMBER, SPACING OF FRAMING MEMBER, HOW
 WILL THE FRAMING MEMBERS BE ATTACHED TO THE DECK ABOVE,
 SPANS OF FRAMING MEMBERS, AND IS THE SPACE CREATED BY
 THE DROPPED CEILINGS AND SOFFITS TO BE A PLENUM?
  
 1C) PROVIDE ADDITIONAL INFORMATION ON THE KITCHEN
 DROPPED CEILING, IS THERE GOING TO BE DRYWALL DROPPED
 CEILING WITH A BEAD BOARD MATERIAL ADDED TO THE DROPPED
 DRYWALL CEILING? SHOW COMPLIANCE WITH 2010 FBC-B TABLE
 803.9 AND 803.11.2 SET-OUT CONSTRUCTION.
 WHERE WALLS AND CEILINGS ARE REQUIRED TO BE OF
 FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE CONSTRUCTION
 AND WALLS ARE SET OUT OR CEILINGS ARE DROPPED DISTANCES
 GREATER THAN SPECIFIED IN SECTION 803.11.1, CLASS A
 FINISH MATERIALS, IN ACCORDANCE WITH SECTION 803.1.1 OR
 803.1.2, SHALL BE USED EXCEPT WHERE INTERIOR FINISH
 MATERIALS ARE PROTECTED ON BOTH SIDES BY AN AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1
 OR 903.3.1.2, OR ATTACHED TO NONCOMBUSTIBLE BACKING OR
 FURRING STRIPS INSTALLED AS SPECIFIED IN SECTION
 803.11.1. THE HANGERS AND ASSEMBLY MEMBERS OF SUCH
 DROPPED CEILINGS THAT ARE BELOW THE MAIN CEILING LINE
 SHALL BE OF NONCOMBUSTIBLE MATERIALS, EXCEPT THAT IN
 TYPES III AND V CONSTRUCTION, FIRE-RETARDANT-TREATED
 WOOD SHALL BE PERMITTED. THE CONSTRUCTION OF EACH
 SET-OUT WALL SHALL BE OF FIRE-RESISTANCE-RATED
 CONSTRUCTION AS REQUIRED ELSEWHERE IN THIS CODE.
  
 2) TILE FLOORS PROVIDE DOCUMENTATION FOR CODE
 COMPLIANCE WITH:
 2A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 2B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING
 FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-08-15 Cont ID  
Sent By dharvey Date 2013-08-15 Time 11:35 Rev Time 0.00
Received By dharvey Date 2013-08-15 Time 11:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-06-27 Cont ID  
Sent By dharvey Date 2013-06-27 Time 14:19 Rev Time 0.00
Received By dharvey Date 2013-06-27 Time 13:58 Sent To  
Notes
2013-06-27 14:19:3913060271
 3800 WASHINGTON RD. #1106
 INTERIOR REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 INDICATE THE LOCATION OF THE ELECTRIC PANEL BOARD.
 PROVIDE A PANEL SCHEDULE SHOWING THE NEW AND EXISTING
 CIRCUITS. VERIFY THE REQUIRED WORKING CLEARANCES AND
 DEDICATED WORKING SPACE HAS BEEN PROVIDED FOR PANEL
 BOARD. NEC 110.26, 240.24, 408.17
  
 PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE BRANCH
 CIRCUITS. NEC 210.52
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. FBC 704.4.3
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2013-06-15 Cont ID  
Sent By wjolin Date 2013-06-15 Time 12:00 Rev Time 0.00
Received By wjolin Date 2013-06-15 Time 11:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-15 Cont ID  
Sent By dharvey Date 2013-08-15 Time 11:35 Rev Time 0.00
Received By dharvey Date 2013-07-29 Time 14:08 Sent To  
Notes
2013-08-15 11:36:29TO S HILL DH
2013-07-30 14:56:16B36

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-12 Cont ID  
Sent By hmoser Date 2013-07-12 Time 10:18 Rev Time 0.00
Received By hmoser Date 2013-06-07 Time 11:08 Sent To  
Notes
2013-06-10 11:10:56B07

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-08-13 Cont ID  
Sent By hmoser Date 2013-08-13 Time 10:46 Rev Time 0.00
Received By hmoser Date 2013-08-13 Time 10:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-07-12 Cont ID  
Sent By hmoser Date 2013-07-12 Time 10:18 Rev Time 0.00
Received By hmoser Date 2013-07-12 Time 10:13 Sent To  
Notes
2013-07-12 10:18:04PLANS DENIED
 PROVIDE DUCT AND GRILLE SIZE ON THE PLANS.
 PER SECTION 107 FBC 2010
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-06-18 Cont ID  
Sent By lwagner Date 2013-06-18 Time 12:25 Rev Time 0.00
Received By lwagner Date 2013-06-18 Time 12:17 Sent To  
Notes
2013-06-18 12:25:35REPLACE EXISTING FIXTURES

Review Stop Z ZONING
Rev No 1 Status N Date 2013-06-10 Cont ID  
Sent By ajones Date 2013-06-10 Time 15:36 Rev Time 0.00
Received By ajones Date 2013-06-10 Time 15:36 Sent To  
Notes
***NONE***