| 2013-07-05 12:57:52 | BUILDING PLAN REVIEW |
| | PERMIT: 13060271 |
| | ADD: 3800 WASHINGTON # 1106 |
| | CONT: BEE CUSTOM CONTRACTORS |
| | TEL: (954)802-7557 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 7/05/13 |
| | ACTION: DENIED |
| | |
| | 1) 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. |
| | |
| | 1A) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | MINIMUM BUILDING TYPE |
| | BLDG FIRE SPRINKLERED |
| | |
| | 1B) 107.3.5(8.) STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | PLANS DO NOT INDICATE THE MATERIALS THE SOFFITS ARE |
| | GOING TO BE BUILT FROM NOR THE THICKNESS OF DRYWALL. |
| | SIZE OF FRAMING MEMBER, SPACING OF FRAMING MEMBER, HOW |
| | WILL THE FRAMING MEMBERS BE ATTACHED TO THE DECK ABOVE, |
| | SPANS OF FRAMING MEMBERS, AND IS THE SPACE CREATED BY |
| | THE DROPPED CEILINGS AND SOFFITS TO BE A PLENUM? |
| | |
| | 1C) PROVIDE ADDITIONAL INFORMATION ON THE KITCHEN |
| | DROPPED CEILING, IS THERE GOING TO BE DRYWALL DROPPED |
| | CEILING WITH A BEAD BOARD MATERIAL ADDED TO THE DROPPED |
| | DRYWALL CEILING? SHOW COMPLIANCE WITH 2010 FBC-B TABLE |
| | 803.9 AND 803.11.2 SET-OUT CONSTRUCTION. |
| | WHERE WALLS AND CEILINGS ARE REQUIRED TO BE OF |
| | FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE CONSTRUCTION |
| | AND WALLS ARE SET OUT OR CEILINGS ARE DROPPED DISTANCES |
| | GREATER THAN SPECIFIED IN SECTION 803.11.1, CLASS A |
| | FINISH MATERIALS, IN ACCORDANCE WITH SECTION 803.1.1 OR |
| | 803.1.2, SHALL BE USED EXCEPT WHERE INTERIOR FINISH |
| | MATERIALS ARE PROTECTED ON BOTH SIDES BY AN AUTOMATIC |
| | SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1 |
| | OR 903.3.1.2, OR ATTACHED TO NONCOMBUSTIBLE BACKING OR |
| | FURRING STRIPS INSTALLED AS SPECIFIED IN SECTION |
| | 803.11.1. THE HANGERS AND ASSEMBLY MEMBERS OF SUCH |
| | DROPPED CEILINGS THAT ARE BELOW THE MAIN CEILING LINE |
| | SHALL BE OF NONCOMBUSTIBLE MATERIALS, EXCEPT THAT IN |
| | TYPES III AND V CONSTRUCTION, FIRE-RETARDANT-TREATED |
| | WOOD SHALL BE PERMITTED. THE CONSTRUCTION OF EACH |
| | SET-OUT WALL SHALL BE OF FIRE-RESISTANCE-RATED |
| | CONSTRUCTION AS REQUIRED ELSEWHERE IN THIS CODE. |
| | |
| | 2) TILE FLOORS PROVIDE DOCUMENTATION FOR CODE |
| | COMPLIANCE WITH: |
| | 2A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | 2B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING |
| | FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF |
| | NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 100. |
| | |