Plan Review Details - Permit 13060229
Plan Review Stops For Permit 13060229
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2014-09-15 Cont ID  
Sent By jwitmer Date 2014-09-15 Time 17:20 Rev Time 0.00
Received By jwitmer Date 2014-09-15 Time 17:00 Sent To  
Notes
2014-09-15 17:21:34THE PLANS WILL STILL NEED TO GO TO P B C IMPACT FEE
 OFFICE FOR ACCESSMENT. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2014-08-23 Cont ID  
Sent By jwitmer Date 2014-08-23 Time 16:09 Rev Time 0.00
Received By jwitmer Date 2014-08-23 Time 15:56 Sent To Z
Notes
2014-08-23 16:03:02BUILDING PLAN REVIEW
 PERMIT: 13060229
 ADD: 8170 OKEECHOBEE BLVD BLDG # 7
 CONT: ATLANTIC ENGINEERING SERVICES
 TEL: (561)267-5941
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 4TH REVIEW
 DATE: SAT. AUGUST 23/2014
 ACTION: DENIED
  
 1) NEW SP SHEETS WILL BE REQUIRED, SOMEONE STAMPED VOID
 ON APPROVED SHEETS.
  
 2) DISCREPANCY BETWEEN THE SIZE OF THE BUILDING IN THE
 NORTH SOUTH DIRECTION BETWEEN THE SURVEY (66.00') AND
 SHEET A-1 DIMENSIONED 65'-2". WEST PALM BEACH
 ADMINISTRATIVE AMENDMENTS 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED TO CLEAR UP THIS DISCREPANCY.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-06-24 Cont ID  
Sent By jwitmer Date 2014-06-24 Time 14:56 Rev Time 0.00
Received By jwitmer Date 2014-06-20 Time 18:00 Sent To  
Notes
2014-06-24 14:30:14BUILDING PLAN REVIEW
 PERMIT: 13060229
 ADD: 8170 OKEECHOBEE BLVD BLDG # 7
 CONT: ATLANTIC ENGINEERING SERVICES
 TEL: (561)267-5941
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: TUES. JUNE 24/ 2014
 ACTION:
 BUILDING PROVISO
  
 DEFERRED SUBMITTALS:
 1A) ROOFING APPROVAL SUBMITTED NO SUBSYSTEM IDENTIFIED:
 NOA: 13-0129.07
 JOHN MANVILLE BUILT-UP ROOFING OVER STEEL DECK.
 NO SUB-SYTEM IDENTIFIED/ MAY REQUIRE ENHANCED
 FASTENING.
 LIMITATION # 7 REQUIRES DESIGN PROFESSIONAL FOR RAS 117
 CALCULATIONS.
  
 1B) ROOFING APPROVAL SUBMITTED NO SUBSYSTEM IDENTIFIED:
 NOA: 13-0129.19
 JOHN MANVILLE BUILT-UP ROOFING OVER STEEL DECK.
 NO SUB-SYTEM IDENTIFIED/ MAY REQUIRE ENHANCED
 FASTENING.
 LIMITATION # 7 REQUIRES DESIGN PROFESSIONAL FOR RAS 117
 CALCULATIONS.
  
 2) NO ROOF CURBING PRODUCT APPROVALS SUBMITTED,
 DEFERRRED SUBMITTAL.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-11-05 Cont ID  
Sent By jwitmer Date 2013-11-05 Time 09:28 Rev Time 0.00
Received By jwitmer Date 2013-11-05 Time 08:56 Sent To  
Notes
2013-11-05 08:58:35BUILDING PLAN REVIEW
 PERMIT: 13060229
 ADD: 8170 OKEECHOBEE BLVD BLDG # 7
 CONT: ATLANTIC ENGINEERING SERVICES
 TEL: (561)267-5941
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: TUES. NOV. 05/2013
 ACTION: DENIED
  
 1) THE SURVEY INDICATES THIS SITE IS LOCATED IN A AH
 FLOOD ZONE (EL 17'). THE CITY MUNI-CODE SECTION 94-546
 (B)(2) NONRESIDENTIAL CONSTRUCTION DOES ALLOW FOR
 EITHER THE LOWEST FLOOR ELEVATION TO BE ELEVATED SIX
 INCHES HIGHER THAN THE BASE FLOOD ELEVATION OR,
 TOGETHER WITH THE ATTENDANT UTILITES AND SANITARY
 FACILITIES, BE FLOODPROOFED SO THAT BELOW THE SIX
 INCHES ABOVE THE BASE FLOOD LEVEL THE STRUCTURE IS
 WATER TIGHT.
 THREE FLOOD ZONE CERTIFICATES WILL BE REQUIRED DURING
 THE CONSTRUCTION PROCESS AND BEFORE A CERTIFICATE OF
 COMPLETION CAN BE ISSUED.
 1A) THE FIRST FLOOD ELEVATION CERTIFICATE WILL BE THE
 PROPOSED FINISH FLOOR ELEVATION IN HGVD, THIS MUST BE
 TURNED IN BEFORE PERMIT ISSUANCE.
 1B) THE SECOND FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED AFTER THE FLOOR SLAB IS POURED.
 1C) THE THIRD CERTIFICATE WILL BE REQUIRED PRIOR TO THE
 CERTIFICATTE OF COMPLETION, WITH THE HEIGHT OF ANY SLAB
 FOR A/C CONDENSORS.
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31,2015
  
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2012, THROUGH JULY 31/ 2015.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 SEPTEMBER 30/ 2013. ALTHOUGH THE OLD VERSION OF THE
 FORM IS NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING
 COPIES MAY BE USED UNTIL SEPTEMBER 30/2013. ELEVATIONS
 CERTIFIED ON OR AFTER OCTOBER 1/2013, MUST BE SUBMITTED
 ON THE NEW FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 2) COMPLIED.
  
 3) 2ND REQUEST. IN THE NORTHWEST CORNER OF THE SURVEY
 AND NOTE # 7 INDICATE A PALM BEACH COUNTY UTILITY
 EASEMENT THAT IS TO BE VACATED, PLEASE SHOW
 DOCUMENTATION AS SUCH. 107.2.1 ADDITIONAL INFORMATION.
 LETTER RECEIVED FOR BUILDING 5 & 6 INDICATED THAT
 EASEMENTS TO BE VACATED AND NEW EASEMENTS TO BE
 SECURED.
  
 4) 2ND REQUEST. SHEET A3 SOUTH ELEVATION SHOWS A
 PERCENTAGE OF OPENINGS (WINDOWS & DOORS), THE SURVEY
 INDICATES THE DISTANCE TO THE PROPERTY LINE IS 10.1 FT.
 PLEASE EITHER PROVIDE THE PER CENT AGE OF ALLOWABLE
 OPENINGS 10-15 FT , 45% UNPROTECTED OPENINGS OR WHAT
 ARRANGEMENT HAS BEEN MADE THAT TRACT A CAN NEVER BE
 SOLD AND THE AREA CAN BE COUNTED AS PART OF THE FIRE
 DISTANCE SEPERATION ? PLEASE PROVIDE DOCUMENTATION THAT
 THE PARKING LOT (74-42-43-29-30-001-0000) TRACT A CAN
 NEVER BE SOLD AND THE AREA CAN BE COUNTED AS PART OF
 THE FIRE DISTANCE SEPARATION? THE OWNERS MUST PRODUCE
 EITHER TYPE OF THESE TYPES OF DOCUMENTS, UNITY OF
 CONTROL, A RESTRICTIVE COVENANT OR A UNITY OF TITLE FOR
 THE AMOUNT OF OPENINGS AND THE CLOSENESS OF THE
 PROPERTY LINE SHOWN ON BOTH THE SURVEY AND THE PBC
 PROPERTY APPRAISERS WEB SITE. DIRECTLY SOUTH OF TRACT C
 IS COMMON TRACT A 8120 OKEECHOBEE BLVD PCN
 74-42-43-29-30-001-0000.
  
 5) 2ND REQUEST. SHEET A2 PLEASE PROVIDE CODE COMPLIANCE
 FOR 2010 FBC-ENERGY 502.2.3.1 SHELL BUILDINGS THIS
 SHEET LIST THE COMPONENTS THAT WILL MAKE UP THE ROOFING
 INSULATION. THE ENERGY CALCULATIONS INDICATE THE ROOF
 INSULATION TO BE A R16.0 THE ENERGY CODE UNDER THE
 PRESCRIPTIVE REQUIREMENTS FOR SHELL BUILDINGS SEE TABLE
 502.1.1.1(1) INDICATE A R VALUE OF GREATER THAN OR
 EQUAL TO R40.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
 SUBMITTED WERE (2) ROOFING PRODUCT APPROVALS FOR FLAT
 ROOFS
 NOA 13-0129.07 1OF 18 SHEETS NO SUB-SYSTEM IDENTIFIED
 SEE EITHER LIMITATION # 7 OR 9 PER SUB-SYSTEM
 NOA 13-0129.19 1OF 38 SHEETS, NO SUB-SYSTEM IDENTIFIED
 SEE EITHER LIMITATION # 7 OR 9 PER SUB-SYSTEM
  
 (E) PRE-ENGINEERED A/C STANDS
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-11 Cont ID  
Sent By jwitmer Date 2013-07-11 Time 10:30 Rev Time 0.00
Received By jwitmer Date 2013-07-10 Time 14:49 Sent To  
Notes
2013-07-11 10:30:06BUILDING PLAN REVIEW
 PERMIT: 13060229
 ADD: 8170 OKEECHOBEE BLVD BLDG # 7
 CONT: ATLANTIC ENGINEERING SERVICES
 TEL: (561)267-5941
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: JULY 10/2013
 ACTION: DENIED
  
 1) THE SURVEY INDICATES THIS SITE IS LOCATED IN A AH
 FLOOD ZONE (EL 17'). THE CITY MUNI-CODE SECTION 94-546
 (B)(2) NONRESIDENTIAL CONSTRUCTION DOES ALLOW FOR
 EITHER THE LOWEST FLOOR ELEVATION TO BE ELEVATED SIX
 INCHES HIGHER THAN THE BASE FLOOD ELEVATION OR,
 TOGETHER WITH THE ATTENDANT UTILITES AND SANITARY
 FACILITIES, BE FLOODPROOFED SO THAT BELOW THE SIX
 INCHES ABOVE THE BASE FLOOD LEVEL THE STRUCTURE IS
 WATER TIGHT.
 THREE FLOOD ZONE CERTIFICATES WILL BE REQUIRED DURING
 THE CONSTRUCTION PROCESS AND BEFORE A CERTIFICATE OF
 COMPLETION CAN BE ISSUED.
 1A) THE FIRST FLOOD ELEVATION CERTIFICATE WILL BE THE
 PROPOSED FINISH FLOOR ELEVATION IN HGVD.
 1B) THE SECOND FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED AFTER THE FLOOR SLAB IS POURED.
 1C) THE THIRD CERTIFICATE WILL BE REQUIRED PRIOR TO THE
 CERTIFICATTE OF COMPLETION, WITH THE HEIGHT OF ANY SLAB
 FOR A/C CONDENSORS.
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31,2015
  
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2012, THROUGH JULY 31/ 2015.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 SEPTEMBER 30/ 2013. ALTHOUGH THE OLD VERSION OF THE
 FORM IS NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING
 COPIES MAY BE USED UNTIL SEPTEMBER 30/2013. ELEVATIONS
 CERTIFIED ON OR AFTER OCTOBER 1/2013, MUST BE SUBMITTED
 ON THE NEW FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 2) SHEET A1 INDICATES THIS BUILDING WAS DESIGNED AS A
 TYPE 5B UNSPRINKLERED BUILDING, THE PLANS REFERENCE
 TABLE 503 , MERCANTILE AND ALLOWED AREA AS 12,500 SQ
 FT. PLEASE REVIEW THE 2010 FBC-B TABLE 503, MERCANTILE
 ONLY ALLOWS 9,000 SQ FT FOR A TYPE VB -UNSPRINKLERED
 BUILDING. PLEASE REVIEW FBC-B 903.2.7 (1) MERCANTILE
 WITH FIRE AREAS THAT EXCEED 12,000 SQ FT REQUIRE FIRE
 SPRINKLERS. PLEASE NOTE THE BUILDING FOOTPRINT OR AREA
 IS TAKEN FROM THE INTERIOR SIDE OF THE EXTERIOR WALL,
 OR APPROXIMATELY 11,821 SQ FT. THIS STILL EXCEEDS THE
 9,000 SQ FT ALLOWED BY TABLE 503.1. IF THE DESIGNER
 WISHES TO TAKE BUILDING AREA MODIFICATIONS FOR FRONTAGE
 INCREASE (506.2) PLEASE PROVIDE THE FORMULA ON THE
 PLANS AND STATE AS SUCH, AREA INCREASE TAKEN.
  
 THERE IS A DISCREPANCY BETWEEN THE SP-1 AND SHEET A-1.
 THE SITE PLAN INDICATES ON THE NORTH SIDE OF THE
 BUILDING 3 DOORWAYS AND LANDINGS, THESE DOOR WAYS ARE
 NOT LOCATED ON THE A1 SHEET. FURTHER MORE AS FOR THE
 SHELL BUILDING WITH THE TENANT LINES AS SHOWN IS CODE
 COMPLIANT FOR COMMON PATH OF TRAVEL UNDER 75 FEET AND A
 OCCUPANT LOAD OF LESS THAN 50. IF ON ANY TENANT
 BUILD-OUT ANY WHERE TWO TENANT SPACES ARE COMBINED THE
 OCCUPANT LOAD IS OVER 50, THE CODE (TABLE 1015.1) WOULD
 TWO EXIT DOORS, AND THE TWO FRONT ENTRY DOORS DO NOT
 COMPLY WITH FBC-B 1015.2.1 DOORS BEING 1/2 THE DIAGONAL
 DISTANCE APART REQUIRING EITHER A DOOR TO THE REAR OF
 THE UNIT OR THE FRONT ENTRY DOORS BEING RELOCATED TO
 MEET THE 1/2 THE DIADONAL DISTANCE APART.
  
 3) IN THE NORTHWEST CORNER OF THE SURVEY AND NOTE # 7
 INDICATE A PALM BEACH COUNTY UTILITY EASEMENT THAT IS
 TO BE VACATED, PLEASE SHOW DOCUMENTATION AS SUCH.
 107.2.1 ADDITIONAL INFORMATION.
  
 4) SHEET A3 SOUTH ELEVATION SHOWS A PERCENTAGE OF
 OPENINGS (WINDOWS & DOORS), THE SURVEY INDICATES THE
 DISTANCE TO THE PROPERTY LINE IS 10.1 FT. PLEASE EITHER
 PROVIDE THE PER CENT AGE OF ALLOWABLE OPENINGS 10-15 FT
 , 45% UNPROTECTED OPENINGS OR WHAT ARRANGEMENT HAS BEEN
 MADE THAT TRACT A CAN NEVER BE SOLD AND THE AREA CAN BE
 COUNTED AS PART OF THE FIRE DISTANCE SEPERATION?
  
 5) SHEET A2 PLEASE PROVIDE CODE COMPLIANCE FOR 2010
 FBC-ENERGY 502.2.3.1 SHELL BUILDINGS. THE ENERGY
 CALCULATIONS INDICATE THE ROOF INSULATION TO BE A R-40
 WHERE AS SHEET A2 INDICATES TYPES OF INSULATION TO BE
 INSTALLED PLEASE PROVIDE HOW THEY WILL ACHIEVE A R-40
 VALUE.
  
 6) SHEET A5 DETAIL # 1 THE PARAPET IS MISSING COPING.
 2010 FBC-B PARAPET WALLS SHALL BE PROPERLY COPED WITH
 NONCOMBUSTIBLE, WEATHERPROOF MATERIALS OF A WIDTH NO
 LESS THAN THE THICKNESS OF THE PARAPET WALL. METAL
 COPING SHALL COMPLY WITH ANSI/SPRI ES-1 OR RAS 111.
  
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) PRE-ENGINEERED A/C STANDS
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-07-02 Cont ID  
Sent By dhayes Date 2014-06-30 Time 15:55 Rev Time 0.00
Received By dhayes Date 2014-06-30 Time 14:33 Sent To  
Notes
2014-06-30 14:34:20ELECTRICAL REVIEW IS APPROVED AS A SHELL ONLY.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-11-25 Cont ID  
Sent By albarran Date 2013-11-25 Time 10:23 Rev Time 0.00
Received By albarran Date 2013-11-25 Time 09:52 Sent To  
Notes
2013-11-25 11:13:59RETURNED TO BIN
2013-11-25 10:39:21THE FOLLOW CORRECTIONS AND/OR CLARIFICATIONS SHALL BE
 SUBMITTED FOR AN ELECTRICAL PLANS APPROVAL
 1. THE TITLE BLOCK INDICATES THAT THE PERMIT IS FOR
 BLDG. 5 & 6, YET THE CLOUD ON THE HOUSE PANEL IS MADE
 AROUND THE LOAD FOR UNITS 8, 8A & 9. PLEASE CLARIFY
 THIS.
 2. IF THIS IS BLDGS,5 & 6 OF A LARGER PARCEL, THIS HAS
 TO BE INDICATED AND A SITE PLAN SUBMITTED.
 3. THE LOAD CALCS REFLECTED ON THE E1 PAGE ONLY INCLUDE
 THE "HP" LOAD. A PANEL SCHEDULE REFLECTING THE
 INDIVIDUAL LOADS OF EACH OF THE UNITS SHALL BE INCLUDED
 EVEN IF TYPICAL OF ALL, SO SUCH BE ADDRESSED, THESE
 UNITS SHALL BE EQUIPPED WITH MINIMAL ELECTRIC FOR LIFE
 SAFETY.
 4. YOU SHALL INCLUDE THE MINIMAL EMERGENCY LIGHTING AND
 ILLUMINATION FOR LIFE SAFETY.
 5. PAGE M1, REFLECTS A ROOF MOUNTED A/C TYPICAL OF EACH
 UNIT WHICH IS NOT INCLUDED IN ANY ELECTRICAL PANEL
 6. A COMPLETE SERVICE DIAGRAM SHALL BE PROVIDED
 INDICATING THE APPROPRIATE LOAD CALCULATIONS.
 7. AS PER THE FBC-ENERGY CONSERVATION SECTION 101.4.9
 SHELL BUILDINGS A SUBMITTAL COMPLYING SHALL BE
 SUBMITTED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-07-10 Cont ID  
Sent By dharvey Date 2013-07-10 Time 11:32 Rev Time 0.00
Received By dharvey Date 2013-07-10 Time 11:19 Sent To  
Notes
2013-07-10 11:32:35BY RL

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2013-07-23 Cont ID  
Sent By Mgonzale Date 2013-07-23 Time   Rev Time 1.00
Received By mgonzale Date 2013-07-23 Time   Sent To I
Notes
2013-07-23 15:20:28NO CONFLICT WITH UTILITIES

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2014-05-19 Cont ID  
Sent By pleduc Date 2014-05-19 Time   Rev Time 0.00
Received By pleduc Date 2014-05-19 Time 14:01 Sent To  
Notes
2014-05-19 14:12:02THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENT:
  
 NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-12-09 Cont ID  
Sent By lphilmor Date 2013-12-09 Time 12:14 Rev Time 0.00
Received By lphilmor Date 2013-12-09 Time 12:14 Sent To  
Notes
2013-12-09 12:15:31REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS WILL BE STAMPED UPON COMPLETION OF BUILDING
 REQUIREMENTS
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-06-21 Cont ID  
Sent By lphilmor Date 2013-06-21 Time 11:43 Rev Time 0.00
Received By lphilmor Date 2013-06-20 Time 12:58 Sent To  
Notes
2013-06-21 11:43:068170 OKEECHOBEE BLVD., BUILDING 7
 PERMIT #13060229
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1. NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK
 INFORMATION.
 2. PROVIDE A LIFE SAFETY PLAN SHOWING ALL EXIT SIGNS,
 EMERGENCY LIGHTING, PORTABLE FIRE EXTINGUISHERS.
 3. PLAN INDICATES SUITES 1-9, BUT NO FIRE RATED WALLS
 PROVIDED.
 4. THUMB-TURN LOCK TO BE EQUIPPED WITH A LOCK/UNLOCK
 INDICATOR.
 5. CONSTRUCTION TYPE IS REFERENCED TO BE TYPE VB,
 HOWEVER, PLANS DO NOT APPEAR TO BE WOOD FRAMED
 STRUCTURE.
 6. PLANS INDICATE NO TENANT SEPARATION WALLS AND THE
 AREA IS INDICIATED AT 12,500 SQ. FT OF MERCANTILE
 OCCUPANCY. PER NFPA 101 SECTION 36.3.5.1(2) STIPULATES
 THAT SPRINKLERS ARE REQUIRED FOR MERCANTILE AREAS
 EXCEEDING 12,000 SQ FT IN GROSS AREA.
 7. PROVIDE TACTILE SIGNAGE AT ALL EXIT DOORS.
 8. PLANS INDICATE TWO HYDRANTS ON THE SITE. PLEASE
 INDICATE ANY ADDITIONAL HYDRANTS THAT MAY BE LOCATED TO
 THE EAST AND SOUTH OF THIS BUILDING.
  
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-09-19 Cont ID  
Sent By jwitmer Date 2014-09-19 Time 10:02 Rev Time 0.00
Received By jwitmer Date 2014-09-18 Time 14:18 Sent To  
Notes
2014-09-18 14:18:45SENT TO J WITMER

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2014-09-18 Time   Rev Time 0.00
Received By shill Date 2014-07-29 Time 18:14 Sent To  
Notes
2014-07-29 18:14:32TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-06-30 Cont ID  
Sent By dhayes Date 2014-06-30 Time 15:57 Rev Time 0.00
Received By dhayes Date 2014-05-14 Time 16:31 Sent To  
Notes
2014-05-14 16:31:16C33

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-06 Cont ID  
Sent By albarran Date 2014-01-06 Time 15:19 Rev Time 0.00
Received By eschneid Date 2013-10-17 Time 09:35 Sent To  
Notes
2013-10-21 09:35:22C30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-23 Cont ID  
Sent By shill Date 2013-07-23 Time 16:38 Rev Time 0.00
Received By shill Date 2013-06-06 Time 13:37 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2014-09-19 Cont ID  
Sent By jwitmer Date 2014-09-19 Time 09:58 Rev Time 0.00
Received By jwitmer Date 2014-09-19 Time 09:58 Sent To  
Notes
2014-09-19 10:02:22IMPACT FEE ASSESSMENT:
 MU-2014-020572-0000
 PROJECT NO, 00074-230
 $157,284.95

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2014-06-24 Cont ID  
Sent By jwitmer Date 2014-06-24 Time 14:57 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2014-06-24 14:57:31BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-11-05 Cont ID  
Sent By jwitmer Date 2013-11-05 Time 09:20 Rev Time 0.00
Received By jwitmer Date 2013-11-05 Time 09:20 Sent To  
Notes
2013-11-05 09:20:27BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-07-11 Cont ID  
Sent By jwitmer Date 2013-07-11 Time 10:30 Rev Time 0.00
Received By jwitmer Date 2013-07-11 Time 10:30 Sent To  
Notes
2013-07-11 10:30:51BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-08-23 Cont ID  
Sent By jwitmer Date 2014-08-23 Time 16:09 Rev Time 0.00
Received By jwitmer Date 2014-08-23 Time 16:09 Sent To  
Notes
2014-08-23 16:09:19REVISION # 3 IS FOR WINDOW & DOOR LOCATION NORTH WALL.
 JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-11-13 Cont ID  
Sent By hmoser Date 2013-11-13 Time 09:08 Rev Time 0.00
Received By hmoser Date 2013-11-13 Time 08:23 Sent To  
Notes
2013-11-13 09:08:18PASS PROVISO
 CURBS ONLY TO BE INSTALLED ON SHELL.
 AIRCONDITIONING PLAN AND ENERGY CALCULATIONS
 WILL BE PROVIDED FOR EACH BUILDOUT.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-07-12 Cont ID  
Sent By hmoser Date 2013-07-12 Time 09:35 Rev Time 0.00
Received By hmoser Date 2013-07-12 Time 09:16 Sent To  
Notes
2013-07-12 09:35:16CURBS ONLY TO BE INSTALLED ON SHELL.
 AIR CONDITIONING PLAN AND ENERGY CALCULATION
 WILL BE PROVIDED FOR EACH BUILD OUT
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-08-23 Cont ID  
Sent By jwitmer Date 2014-08-23 Time 16:03 Rev Time 0.00
Received By jwitmer Date 2014-08-23 Time 16:03 Sent To  
Notes
2014-08-23 16:08:56REVISION # 3 IS FOR WINDOW & DOOR LOCATION NORTH WALL.
 JW

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-10-30 Cont ID  
Sent By lwagner Date 2013-10-30 Time 10:35 Rev Time 0.00
Received By lwagner Date 2013-10-30 Time 10:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-06-19 Cont ID  
Sent By lwagner Date 2013-06-19 Time 14:07 Rev Time 0.00
Received By lwagner Date 2013-06-19 Time 13:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2014-09-08 Cont ID  
Sent By eschneid Date 2014-09-08 Time 17:35 Rev Time 0.00
Received By eschneid Date 2014-09-08 Time 17:35 Sent To  
Notes
2014-09-08 17:37:33SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE
 FOLLOWING:
  
 A. LANDSCAPE REQUIRES A SEPARATE PERMIT APPLICATION FOR
 EACH PARCEL (TRACT A & TRACT F) ON WHICH WORK IS BEING
 DONE. THE SAME 2 COPIES OF THE LANDSCAPE PLAN MAY BE
 USED FOR BOTH APPLICATIONS (SUBJECT TO CONCURRENT
 SUBMITTAL). A COST ESTIMATE IS REQUIRED WITH THE
 SUBMITTAL.
 B. SIGNAGE
 C. AWNINGS
 D. PARKING LOT STRIPING
 E. BICYCLE RACKS
  
  
  
  

Review Stop Z ZONING
Rev No 4 Status F Date 2014-09-08 Cont ID  
Sent By eschneid Date 2014-08-19 Time 16:13 Rev Time 0.00
Received By eschneid Date 2014-08-19 Time 16:12 Sent To  
Notes
2014-08-19 16:26:03IN REVIEW
  
 AWAITING INFORMATION FROM ARCHITECT ON:
  
 2) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO.
 288-11, ALL ROOF MOUNTED AIR CONDITIONING, MECHANICAL
 EQUIPMENT, SATELLITE DISHES, GENERATORS, ETC., SHALL BE
 SCREENED FROM VIEW ON ALL SIDES BY A VISUALLY OPAQUE
 BARRIER CONSISTENT WITH THE COLOR, CHARACTER AND
 ARCHITECTURAL STYLE OF THE STRUCTURES OR EQUIVALENT
 LANDSCAPE MATERIAL. THE HEIGHT OF THE OPAQUE BARRIER
 SHALL BE AS REQUIRED TO PROVIDE AMPLE SCREENING.
 PROVIDE VERIFICATION THAT THE ROOFTOP MECHANICAL
 EQUIPMENT WILL BE SCREENED AS REQUIRED BY THE
 RESOLUTION FOR THE SPECIFIC EQUIPMENT PROPOSED FOR
 INSTALLATION (EX. LINE OF SIGHT OR ELEVATIONS WITH THE
 EQUIPMENT).
  
 AWAITING INFORMATION FROM LAND PLANNER ON:
  
 1) REPEAT COMMENT: PURSUANT TO RESOLUTION NO. 288-11, A
 CONSTRUCTION SITE SECURITY AND MANAGEMENT PLAN SHALL BE
 SUBMITTED TO THE CITY'S POLICE DEPARTMENT CRIME
 PREVENTION THROUGH ENVIRONMENTAL DESIGN ("CPTED")
 OFFICIAL AND APPROVED PRIOR TO THE ISSUANCE OF THE
 BUILDING PERMIT.
  
 SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE
 FOLLOWING:
  
 A. LANDSCAPE REQUIRES A SEPARATE PERMIT APPLICATION FOR
 EACH PARCEL (TRACT A & TRACT F) ON WHICH WORK IS BEING
 DONE. THE SAME 2 COPIES OF THE LANDSCAPE PLAN MAY BE
 USED FOR BOTH APPLICATIONS (SUBJECT TO CONCURRENT
 SUBMITTAL). A COST ESTIMATE IS REQUIRED WITH THE
 SUBMITTAL.
 B. SIGNAGE
 C. AWNINGS
 D. PARKING LOT STRIPING
 E. BICYCLE RACKS
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 2014-06-04 Cont ID  
Sent By eschneid Date 2014-06-04 Time 15:39 Rev Time 1.00
Received By eschneid Date 2014-06-04 Time 15:39 Sent To  
Notes
2014-06-04 15:46:16FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) REPEAT COMMENT: PURSUANT TO RESOLUTION NO. 288-11, A
 CONSTRUCTION SITE SECURITY AND MANAGEMENT PLAN SHALL BE
 SUBMITTED TO THE CITY'S POLICE DEPARTMENT CRIME
 PREVENTION THROUGH ENVIRONMENTAL DESIGN ("CPTED")
 OFFICIAL AND APPROVED PRIOR TO THE ISSUANCE OF THE
 BUILDING PERMIT. (CONTRARY TO THE RESPONSE COMMENT, NO
 PLAN HAS BEEN SUBMITTED TO OFFICER KELLY CARSILLO)
  
 I) THE APPLICANT, AFTER SITE CLEARING AND PLACEMENT OF
 CONSTRUCTION TRAILERS, SHALL INSTITUTE SECURITY
 MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES FOR
 THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT TO BE
 LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY AND TOOLS AT END OF
 WORK DAY AND/OR ANY OTHER MEASURE DEEMED APPROPRIATE TO
 PROVIDE A SAFE AND SECURE WORKING ENVIRONMENT.
 II) THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED DEVELOPMENT.
  
 2) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO.
 288-11, ALL ROOF MOUNTED AIR CONDITIONING, MECHANICAL
 EQUIPMENT, SATELLITE DISHES, GENERATORS, ETC., SHALL BE
 SCREENED FROM VIEW ON ALL SIDES BY A VISUALLY OPAQUE
 BARRIER CONSISTENT WITH THE COLOR, CHARACTER AND
 ARCHITECTURAL STYLE OF THE STRUCTURES OR EQUIVALENT
 LANDSCAPE MATERIAL. THE HEIGHT OF THE OPAQUE BARRIER
 SHALL BE AS REQUIRED TO PROVIDE AMPLE SCREENING.
 PROVIDE VERIFICATION THAT THE ROOFTOP MECHANICAL
 EQUIPMENT WILL BE SCREENED AS REQUIRED BY THE
 RESOLUTION FOR THE SPECIFIC EQUIPMENT PROPOSED FOR
 INSTALLATION (EX. LINE OF SIGHT OR ELEVATIONS WITH THE
 EQUIPMENT).
  
 3) REPEAT COMMENT: THE APPROVED ELEVATIONS FOR BUILDING
 #7 HAVE CHANGED. THE ZONING STAFF HAS NOT APPROVED THE
 REVISED ELEVATIONS, SPECIFICALLY:
  
 A. THE PREVIOUS MINOR AMENDMENT APPROVAL FOR BUILDING
 #7 PERMITTED THE REDUCTION OF THE CITY COMMISSION
 APPROVED 9 DOORS TO 3 DOORS ON THE NORTHERN ELEVATION,
 PROVIDED THAT WINDOWS ARE PROVIDED IN THEIR PLACE WHERE
 THE 6 DOORS HAD BEEN. THE TWO END BAY LOCATIONS SHALL
 INCLUDE WINDOWS, NOT STUCCO DESIGNED TO LOOK SIMILAR TO
 A WINDOW.
  
 4) NEW COMMENT: THE REVISED NORTH/SOUTH BUILDING
 DIMENSION TO ACCOMMODATE THE 12,000 SQUARE FOOT
 BUILDING IS NOT REFLECTED ON THE CONSTRUCTION LAYOUT
 SURVEY. THE NORTH SETBACK (19.5 FEET) DOES NOT COMPLY
 WITH THE SETBACK APPROVED ON THE SITE PLAN (20.4 FEET).
  
 5) REPEAT COMMENT: PROVIDE A COPY OF THE REVISED SITE
 PLAN APPROVED BY ZONING THROUGH THE MINOR AMENDMENT
 PROCESS.
  
 SEPTATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE
 FOLLOWING:
  
 A. LANDSCAPE REQUIRES A SEPARATE PERMIT APPLICATION FOR
 EACH PARCEL (TRACT A & TRACT F) ON WHICH WORK IS BEING
 DONE. THE SAME 2 COPIES OF THE LANDSCAPE PLAN MAY BE
 USED FOR BOTH APPLICATIONS (SUBJECT TO CONCURRENT
 SUBMITTAL). A COST ESTIMATE IS REQUIRED WITH THE
 SUBMITTAL.
 B. SIGNAGE
 C. AWNINGS
 D. PARKING LOT STRIPING
 E. BICYCLE RACKS
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2014-05-15 16:25:095/15/14

Review Stop Z ZONING
Rev No 2 Status F Date 2014-01-06 Cont ID  
Sent By eschneid Date 2014-01-06 Time 15:18 Rev Time 1.00
Received By eschneid Date 2014-01-06 Time 15:18 Sent To  
Notes
2014-01-06 15:18:39FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) REPEAT COMMENT: PURSUANT TO THE PALM BEACH COUNTY
 TRAFFIC PERFORMANCE STANDARDS REVIEW LETTER ISSUED ON
 SEPTEMBER 17, 2009, NO BUILDING PERMITS SHALL BE ISSUED
 BY THE CITY AFTER DECEMBER 31, 2012. AN EXTENSION OF
 THIS DEADLINE MAY BE ISSUED BY PALM BEACH COUNTY. A
 MINOR PLANNED DEVELOPMENT AMENDMENT IS REQUIRED TO
 UPDATE THE COUNTY BUILD OUT DATE.
  
 2) REPEAT COMMENT: PURSUANT TO RESOLUTION NO. 288-11, A
 CONSTRUCTION SITE SECURITY AND MANAGEMENT PLAN SHALL BE
 SUBMITTED TO THE CITY'S POLICE DEPARTMENT CRIME
 PREVENTION THROUGH ENVIRONMENTAL DESIGN ("CPTED")
 OFFICIAL AND APPROVED PRIOR TO THE ISSUANCE OF THE
 BUILDING PERMIT. (CONTRARY TO THE RESPONSE COMMENT, NO
 PLAN HAS BEEN SUBMITTED TO OFFICER KELLY CARSILLO)
  
 I) THE APPLICANT, AFTER SITE CLEARING AND PLACEMENT OF
 CONSTRUCTION TRAILERS, SHALL INSTITUTE SECURITY
 MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES FOR
 THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT TO BE
 LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY AND TOOLS AT END OF
 WORK DAY AND/OR ANY OTHER MEASURE DEEMED APPROPRIATE TO
 PROVIDE A SAFE AND SECURE WORKING ENVIRONMENT.
 II) THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED DEVELOPMENT.
  
 3) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO.
 288-11, ALL ROOF MOUNTED AIR CONDITIONING, MECHANICAL
 EQUIPMENT, SATELLITE DISHES, GENERATORS, ETC., SHALL BE
 SCREENED FROM VIEW ON ALL SIDES BY A VISUALLY OPAQUE
 BARRIER CONSISTENT WITH THE COLOR, CHARACTER AND
 ARCHITECTURAL STYLE OF THE STRUCTURES OR EQUIVALENT
 LANDSCAPE MATERIAL. THE HEIGHT OF THE OPAQUE BARRIER
 SHALL BE AS REQUIRED TO PROVIDE AMPLE SCREENING.
 PROVIDE VERIFICATION THAT THE ROOFTOP MECHANICAL
 EQUIPMENT WILL BE SCREENED AS REQUIRED BY THE
 RESOLUTION FOR THE SPECIFIC EQUIPMENT PROPOSED FOR
 INSTALLATION (EX. LINE OF SIGHT OR ELEVATIONS WITH THE
 EQUIPMENT).
  
 4) THE APPROVED ELEVATIONS FOR BUILDING 7 HAVE CHANGED.
 THE ZONING STAFF HAS NOT APPROVED THE REVISED
 ELEVATIONS, SPECIFICALLY:
  
 A. THE PREVIOUS MINOR AMENDMENT APPROVAL FOR BUILDING
 #7 PERMITTED THE REDUCTION OF THE CITY COMMISSION
 APPROVED 9 DOORS TO 3 DOORS ON THE NORTHERN ELEVATION,
 PROVIDED THAT WINDOWS ARE PROVIDED IN THEIR PLACE WHERE
 THE 6 DOORS HAD BEEN. THE TWO END BAY LOCATIONS SHALL
 INCLUDE WINDOWS.
  
 B. THE THREE DOORS SHALL HAVE A SIMILAR BANDING AROUND
 THEM AS THE WINDOWS TO ENHANCE THE APPEARANCE OF THE
 DOORWAY ELEMENTS. THIS WILL OFFSET THE FACT THAT THE
 DOORWAYS HAVE BEEN NARROWED WITH THE PROPOSED PLANS
 WHEN COMPARED TO THE APPROVED PLANS. PLEASE CONSIDER
 ALIGNING THE DOORS IN A SYMMETRICAL PATTERN ALONG THE
 FACADE.
  
 5) PROVIDE A COPY OF THE REVISED SITE PLAN ONCE IT IS
 APPROVED BY ZONING THROUGH THE MINOR AMENDMENT PROCESS.
  
 6) THE LANDSCAPE REQUIRES A SEPARATE PERMIT APPLICATION
 FOR EACH PARCEL (TRACT A & TRACT F) ON WHICH WORK IS
 BEING DONE. THE SAME 2 COPIES OF THE LANDSCAPE PLAN MAY
 BE USED FOR BOTH APPLICATIONS (SUBJECT TO CONCURRENT
 SUBMITTAL). A COST ESTIMATE IS REQUIRED WITH THE
 SUBMITTAL.
  
 7) SIGNAGE AND AWNINGS REQUIRE SEPARATE PERMITS WITH
 PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
2013-10-30 15:08:1110/29/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-06-24 Cont ID  
Sent By eschneid Date 2013-06-24 Time 15:58 Rev Time 1.00
Received By eschneid Date 2013-06-21 Time 16:41 Sent To  
Notes
2013-06-24 16:21:01FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) PURSUANT TO THE PALM BEACH COUNTY TRAFFIC
 PERFORMANCE STANDARDS REVIEW LETTER ISSUED ON SEPTEMBER
 17, 2009, NO BUILDING PERMITS SHALL BE ISSUED BY THE
 CITY AFTER DECEMBER 31, 2012. AN EXTENSION OF THIS
 DEADLINE MAY BE ISSUED BY PALM BEACH COUNTY. A MINOR
 PLANNED DEVELOPMENT AMENDMENT IS REQUIRED TO UPDATE THE
 THE COUNTY BUILD OUT DATE.
  
 2) PURSUANT TO RESOLUTION NO. 288-11, A CONSTRUCTION
 SITE SECURITY AND MANAGEMENT PLAN SHALL BE SUBMITTED TO
 THE CITY'S POLICE DEPARTMENT CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN ("CPTED") OFFICIAL AND APPROVED
 PRIOR TO THE ISSUANCE OF THE BUILDING PERMIT.
  
 I) THE APPLICANT, AFTER SITE CLEARING AND PLACEMENT OF
 CONSTRUCTION TRAILERS, SHALL INSTITUTE SECURITY
 MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES FOR
 THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT TO BE
 LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY AND TOOLS AT END OF
 WORK DAY AND/OR ANY OTHER MEASURE DEEMED APPROPRIATE TO
 PROVIDE A SAFE AND SECURE WORKING ENVIRONMENT.
 II) THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED DEVELOPMENT.
  
 3) SHEET A-1 DOES NOT SHOW THE FOUNDATION PLANTING
 AREAS AT FIVE (5) FEET WIDE UNDER THE AREAS COVERED BY
 THE AWNINGS.
  
 4) IN ACCORDANCE WITH RESOLUTION NO. 288-11, ALL ROOF
 MOUNTED AIR CONDITIONING, MECHANICAL EQUIPMENT,
 SATELLITE DISHES, GENERATORS, ETC., SHALL BE SCREENED
 FROM VIEW ON ALL SIDES BY A VISUALLY OPAQUE BARRIER
 CONSISTENT WITH THE COLOR, CHARACTER AND ARCHITECTURAL
 STYLE OF THE STRUCTURES OR EQUIVALENT LANDSCAPE
 MATERIAL. THE HEIGHT OF THE OPAQUE BARRIER SHALL BE AS
 REQUIRED TO PROVIDE AMPLE SCREENING. PROVIDE
 VERIFICATION THAT THE ROOFTOP MECHANICAL EQUIPMENT WILL
 BE SCREENED AS REQUIRED BY THE RESOLUTION FOR THE
 SPECIFIC EQUIPMENT PROPOSED FOR INSTALLATION (EX. LINE
 OF SIGHT OR ELEVATIONS WITH THE EQUIPMENT).
  
 5) THE APPROVED ELEVATIONS FOR BUILDING 7 HAVE CHANGED.
 THE BUILDING IS TALLER AND THE REQUIRED DOORS ON THE
 NORTH FACADE HAVE BEEN RELOCATED (2) AND REMOVED (1)
 AND ADDITIONAL WINDOWS WERE ADDED ON THE WESTERN
 FACADE. REVISED ELEVATIONS ARE REQUIRED AS PART OF A
 MINOR PLANNED DEVELOPMENT AMENDMENT TO SHOW THE ACTUAL
 CONDITIONS. THE SITE AND LANDSCAPE PLANS DO NOT MATCH
 THE PROPOSED DOOR MODIFICATIONS.
  
 6) THE LANDSCAPE REQUIRES A SEPARATE PERMIT APPLICATION
 FOR EACH PARCEL (TRACT A & TRACT F) ON WHICH WORK IS
 BEING DONE. THE SAME 2 COPIES OF THE LANDSCAPE PLAN MAY
 BE USED FOR BOTH APPLICATIONS (SUBJECT TO CONCURRENT
 SUBMITTAL). A COST ESTIMATE IS REQUIRED WITH THE
 SUBMITTAL.
  
 7) THE PLANS TO CONSTRUCT THE PARKING REQUIRED PRIOR TO
 THE C.O. OF THE LAST PHASE I BUILDING (GENERALLY ALONG
 THE SOUTH ACCESS DRIVE) SHALL BE INCLUDED ON A PARKING
 LOT STRIPING PERMIT FOR TRACT A PRIOR TO ZONING
 APPROVAL OF THIS PERMIT. STRIPING DETAILS FOR ALL
 CONDITIONS SHALL BE PROVIDED. THE PARKING SHALL BE
 INSTALLED PRIOR TO THE C.O. OF THIS BUILDING OR
 BUILDING 5/6, WHICHEVER OCCURS LAST.
  
 8) SIGNAGE AND AWNINGS REQUIRE SEPARATE PERMITS WITH
 PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  