| Plan Review Stops For Permit 13060229 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2014-09-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-09-15 |
Time |
17:20 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-09-15 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2014-09-15 17:21:34 | THE PLANS WILL STILL NEED TO GO TO P B C IMPACT FEE | | | OFFICE FOR ACCESSMENT. JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2014-08-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-08-23 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-08-23 |
Time |
15:56 |
Sent To |
Z |
|
| Notes |
| 2014-08-23 16:03:02 | BUILDING PLAN REVIEW | | | PERMIT: 13060229 | | | ADD: 8170 OKEECHOBEE BLVD BLDG # 7 | | | CONT: ATLANTIC ENGINEERING SERVICES | | | TEL: (561)267-5941 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 4TH REVIEW | | | DATE: SAT. AUGUST 23/2014 | | | ACTION: DENIED | | | | | | 1) NEW SP SHEETS WILL BE REQUIRED, SOMEONE STAMPED VOID | | | ON APPROVED SHEETS. | | | | | | 2) DISCREPANCY BETWEEN THE SIZE OF THE BUILDING IN THE | | | NORTH SOUTH DIRECTION BETWEEN THE SURVEY (66.00') AND | | | SHEET A-1 DIMENSIONED 65'-2". WEST PALM BEACH | | | ADMINISTRATIVE AMENDMENTS 107.2.1.3 ADDITIONAL | | | INFORMATION IS REQUIRED TO CLEAR UP THIS DISCREPANCY. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2014-06-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-06-24 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-06-20 |
Time |
18:00 |
Sent To |
|
|
| Notes |
| 2014-06-24 14:30:14 | BUILDING PLAN REVIEW | | | PERMIT: 13060229 | | | ADD: 8170 OKEECHOBEE BLVD BLDG # 7 | | | CONT: ATLANTIC ENGINEERING SERVICES | | | TEL: (561)267-5941 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 3RD REVIEW | | | DATE: TUES. JUNE 24/ 2014 | | | ACTION: | | | BUILDING PROVISO | | | | | | DEFERRED SUBMITTALS: | | | 1A) ROOFING APPROVAL SUBMITTED NO SUBSYSTEM IDENTIFIED: | | | NOA: 13-0129.07 | | | JOHN MANVILLE BUILT-UP ROOFING OVER STEEL DECK. | | | NO SUB-SYTEM IDENTIFIED/ MAY REQUIRE ENHANCED | | | FASTENING. | | | LIMITATION # 7 REQUIRES DESIGN PROFESSIONAL FOR RAS 117 | | | CALCULATIONS. | | | | | | 1B) ROOFING APPROVAL SUBMITTED NO SUBSYSTEM IDENTIFIED: | | | NOA: 13-0129.19 | | | JOHN MANVILLE BUILT-UP ROOFING OVER STEEL DECK. | | | NO SUB-SYTEM IDENTIFIED/ MAY REQUIRE ENHANCED | | | FASTENING. | | | LIMITATION # 7 REQUIRES DESIGN PROFESSIONAL FOR RAS 117 | | | CALCULATIONS. | | | | | | 2) NO ROOF CURBING PRODUCT APPROVALS SUBMITTED, | | | DEFERRRED SUBMITTAL. | | | | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2013-11-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-11-05 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-11-05 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2013-11-05 08:58:35 | BUILDING PLAN REVIEW | | | PERMIT: 13060229 | | | ADD: 8170 OKEECHOBEE BLVD BLDG # 7 | | | CONT: ATLANTIC ENGINEERING SERVICES | | | TEL: (561)267-5941 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2ND REVIEW | | | DATE: TUES. NOV. 05/2013 | | | ACTION: DENIED | | | | | | 1) THE SURVEY INDICATES THIS SITE IS LOCATED IN A AH | | | FLOOD ZONE (EL 17'). THE CITY MUNI-CODE SECTION 94-546 | | | (B)(2) NONRESIDENTIAL CONSTRUCTION DOES ALLOW FOR | | | EITHER THE LOWEST FLOOR ELEVATION TO BE ELEVATED SIX | | | INCHES HIGHER THAN THE BASE FLOOD ELEVATION OR, | | | TOGETHER WITH THE ATTENDANT UTILITES AND SANITARY | | | FACILITIES, BE FLOODPROOFED SO THAT BELOW THE SIX | | | INCHES ABOVE THE BASE FLOOD LEVEL THE STRUCTURE IS | | | WATER TIGHT. | | | THREE FLOOD ZONE CERTIFICATES WILL BE REQUIRED DURING | | | THE CONSTRUCTION PROCESS AND BEFORE A CERTIFICATE OF | | | COMPLETION CAN BE ISSUED. | | | 1A) THE FIRST FLOOD ELEVATION CERTIFICATE WILL BE THE | | | PROPOSED FINISH FLOOR ELEVATION IN HGVD, THIS MUST BE | | | TURNED IN BEFORE PERMIT ISSUANCE. | | | 1B) THE SECOND FLOOD ELEVATION CERTIFICATE WILL BE | | | REQUIRED AFTER THE FLOOR SLAB IS POURED. | | | 1C) THE THIRD CERTIFICATE WILL BE REQUIRED PRIOR TO THE | | | CERTIFICATTE OF COMPLETION, WITH THE HEIGHT OF ANY SLAB | | | FOR A/C CONDENSORS. | | | | | | FEMA FORM OMB NO. 1660-0008 EXPIRES: | | | JULY 31,2015 | | | | | | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR | | | USE, EFFECTIVE AUGUST 1/ 2012, THROUGH JULY 31/ 2015. | | | THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL | | | SEPTEMBER 30/ 2013. ALTHOUGH THE OLD VERSION OF THE | | | FORM IS NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING | | | COPIES MAY BE USED UNTIL SEPTEMBER 30/2013. ELEVATIONS | | | CERTIFIED ON OR AFTER OCTOBER 1/2013, MUST BE SUBMITTED | | | ON THE NEW FORM. | | | | | | ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW | | | FORM, AND INSTRUCTIONS ARE AVAILABLE AT: | | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | | | 2) COMPLIED. | | | | | | 3) 2ND REQUEST. IN THE NORTHWEST CORNER OF THE SURVEY | | | AND NOTE # 7 INDICATE A PALM BEACH COUNTY UTILITY | | | EASEMENT THAT IS TO BE VACATED, PLEASE SHOW | | | DOCUMENTATION AS SUCH. 107.2.1 ADDITIONAL INFORMATION. | | | LETTER RECEIVED FOR BUILDING 5 & 6 INDICATED THAT | | | EASEMENTS TO BE VACATED AND NEW EASEMENTS TO BE | | | SECURED. | | | | | | 4) 2ND REQUEST. SHEET A3 SOUTH ELEVATION SHOWS A | | | PERCENTAGE OF OPENINGS (WINDOWS & DOORS), THE SURVEY | | | INDICATES THE DISTANCE TO THE PROPERTY LINE IS 10.1 FT. | | | PLEASE EITHER PROVIDE THE PER CENT AGE OF ALLOWABLE | | | OPENINGS 10-15 FT , 45% UNPROTECTED OPENINGS OR WHAT | | | ARRANGEMENT HAS BEEN MADE THAT TRACT A CAN NEVER BE | | | SOLD AND THE AREA CAN BE COUNTED AS PART OF THE FIRE | | | DISTANCE SEPERATION ? PLEASE PROVIDE DOCUMENTATION THAT | | | THE PARKING LOT (74-42-43-29-30-001-0000) TRACT A CAN | | | NEVER BE SOLD AND THE AREA CAN BE COUNTED AS PART OF | | | THE FIRE DISTANCE SEPARATION? THE OWNERS MUST PRODUCE | | | EITHER TYPE OF THESE TYPES OF DOCUMENTS, UNITY OF | | | CONTROL, A RESTRICTIVE COVENANT OR A UNITY OF TITLE FOR | | | THE AMOUNT OF OPENINGS AND THE CLOSENESS OF THE | | | PROPERTY LINE SHOWN ON BOTH THE SURVEY AND THE PBC | | | PROPERTY APPRAISERS WEB SITE. DIRECTLY SOUTH OF TRACT C | | | IS COMMON TRACT A 8120 OKEECHOBEE BLVD PCN | | | 74-42-43-29-30-001-0000. | | | | | | 5) 2ND REQUEST. SHEET A2 PLEASE PROVIDE CODE COMPLIANCE | | | FOR 2010 FBC-ENERGY 502.2.3.1 SHELL BUILDINGS THIS | | | SHEET LIST THE COMPONENTS THAT WILL MAKE UP THE ROOFING | | | INSULATION. THE ENERGY CALCULATIONS INDICATE THE ROOF | | | INSULATION TO BE A R16.0 THE ENERGY CODE UNDER THE | | | PRESCRIPTIVE REQUIREMENTS FOR SHELL BUILDINGS SEE TABLE | | | 502.1.1.1(1) INDICATE A R VALUE OF GREATER THAN OR | | | EQUAL TO R40. | | | | | | 6) COMPLIED. | | | | | | 7) COMPLIED. | | | | | | 8) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.41 COMPONENTS & CLADDING | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. | | | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES | | | SUBMITTED WERE (2) ROOFING PRODUCT APPROVALS FOR FLAT | | | ROOFS | | | NOA 13-0129.07 1OF 18 SHEETS NO SUB-SYSTEM IDENTIFIED | | | SEE EITHER LIMITATION # 7 OR 9 PER SUB-SYSTEM | | | NOA 13-0129.19 1OF 38 SHEETS, NO SUB-SYSTEM IDENTIFIED | | | SEE EITHER LIMITATION # 7 OR 9 PER SUB-SYSTEM | | | | | | (E) PRE-ENGINEERED A/C STANDS | | | | | | 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-07-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-07-11 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-07-10 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2013-07-11 10:30:06 | BUILDING PLAN REVIEW | | | PERMIT: 13060229 | | | ADD: 8170 OKEECHOBEE BLVD BLDG # 7 | | | CONT: ATLANTIC ENGINEERING SERVICES | | | TEL: (561)267-5941 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 1ST REVIEW | | | DATE: JULY 10/2013 | | | ACTION: DENIED | | | | | | 1) THE SURVEY INDICATES THIS SITE IS LOCATED IN A AH | | | FLOOD ZONE (EL 17'). THE CITY MUNI-CODE SECTION 94-546 | | | (B)(2) NONRESIDENTIAL CONSTRUCTION DOES ALLOW FOR | | | EITHER THE LOWEST FLOOR ELEVATION TO BE ELEVATED SIX | | | INCHES HIGHER THAN THE BASE FLOOD ELEVATION OR, | | | TOGETHER WITH THE ATTENDANT UTILITES AND SANITARY | | | FACILITIES, BE FLOODPROOFED SO THAT BELOW THE SIX | | | INCHES ABOVE THE BASE FLOOD LEVEL THE STRUCTURE IS | | | WATER TIGHT. | | | THREE FLOOD ZONE CERTIFICATES WILL BE REQUIRED DURING | | | THE CONSTRUCTION PROCESS AND BEFORE A CERTIFICATE OF | | | COMPLETION CAN BE ISSUED. | | | 1A) THE FIRST FLOOD ELEVATION CERTIFICATE WILL BE THE | | | PROPOSED FINISH FLOOR ELEVATION IN HGVD. | | | 1B) THE SECOND FLOOD ELEVATION CERTIFICATE WILL BE | | | REQUIRED AFTER THE FLOOR SLAB IS POURED. | | | 1C) THE THIRD CERTIFICATE WILL BE REQUIRED PRIOR TO THE | | | CERTIFICATTE OF COMPLETION, WITH THE HEIGHT OF ANY SLAB | | | FOR A/C CONDENSORS. | | | | | | FEMA FORM OMB NO. 1660-0008 EXPIRES: | | | JULY 31,2015 | | | | | | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR | | | USE, EFFECTIVE AUGUST 1/ 2012, THROUGH JULY 31/ 2015. | | | THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL | | | SEPTEMBER 30/ 2013. ALTHOUGH THE OLD VERSION OF THE | | | FORM IS NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING | | | COPIES MAY BE USED UNTIL SEPTEMBER 30/2013. ELEVATIONS | | | CERTIFIED ON OR AFTER OCTOBER 1/2013, MUST BE SUBMITTED | | | ON THE NEW FORM. | | | | | | ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW | | | FORM, AND INSTRUCTIONS ARE AVAILABLE AT: | | | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM | | | | | | 2) SHEET A1 INDICATES THIS BUILDING WAS DESIGNED AS A | | | TYPE 5B UNSPRINKLERED BUILDING, THE PLANS REFERENCE | | | TABLE 503 , MERCANTILE AND ALLOWED AREA AS 12,500 SQ | | | FT. PLEASE REVIEW THE 2010 FBC-B TABLE 503, MERCANTILE | | | ONLY ALLOWS 9,000 SQ FT FOR A TYPE VB -UNSPRINKLERED | | | BUILDING. PLEASE REVIEW FBC-B 903.2.7 (1) MERCANTILE | | | WITH FIRE AREAS THAT EXCEED 12,000 SQ FT REQUIRE FIRE | | | SPRINKLERS. PLEASE NOTE THE BUILDING FOOTPRINT OR AREA | | | IS TAKEN FROM THE INTERIOR SIDE OF THE EXTERIOR WALL, | | | OR APPROXIMATELY 11,821 SQ FT. THIS STILL EXCEEDS THE | | | 9,000 SQ FT ALLOWED BY TABLE 503.1. IF THE DESIGNER | | | WISHES TO TAKE BUILDING AREA MODIFICATIONS FOR FRONTAGE | | | INCREASE (506.2) PLEASE PROVIDE THE FORMULA ON THE | | | PLANS AND STATE AS SUCH, AREA INCREASE TAKEN. | | | | | | THERE IS A DISCREPANCY BETWEEN THE SP-1 AND SHEET A-1. | | | THE SITE PLAN INDICATES ON THE NORTH SIDE OF THE | | | BUILDING 3 DOORWAYS AND LANDINGS, THESE DOOR WAYS ARE | | | NOT LOCATED ON THE A1 SHEET. FURTHER MORE AS FOR THE | | | SHELL BUILDING WITH THE TENANT LINES AS SHOWN IS CODE | | | COMPLIANT FOR COMMON PATH OF TRAVEL UNDER 75 FEET AND A | | | OCCUPANT LOAD OF LESS THAN 50. IF ON ANY TENANT | | | BUILD-OUT ANY WHERE TWO TENANT SPACES ARE COMBINED THE | | | OCCUPANT LOAD IS OVER 50, THE CODE (TABLE 1015.1) WOULD | | | TWO EXIT DOORS, AND THE TWO FRONT ENTRY DOORS DO NOT | | | COMPLY WITH FBC-B 1015.2.1 DOORS BEING 1/2 THE DIAGONAL | | | DISTANCE APART REQUIRING EITHER A DOOR TO THE REAR OF | | | THE UNIT OR THE FRONT ENTRY DOORS BEING RELOCATED TO | | | MEET THE 1/2 THE DIADONAL DISTANCE APART. | | | | | | 3) IN THE NORTHWEST CORNER OF THE SURVEY AND NOTE # 7 | | | INDICATE A PALM BEACH COUNTY UTILITY EASEMENT THAT IS | | | TO BE VACATED, PLEASE SHOW DOCUMENTATION AS SUCH. | | | 107.2.1 ADDITIONAL INFORMATION. | | | | | | 4) SHEET A3 SOUTH ELEVATION SHOWS A PERCENTAGE OF | | | OPENINGS (WINDOWS & DOORS), THE SURVEY INDICATES THE | | | DISTANCE TO THE PROPERTY LINE IS 10.1 FT. PLEASE EITHER | | | PROVIDE THE PER CENT AGE OF ALLOWABLE OPENINGS 10-15 FT | | | , 45% UNPROTECTED OPENINGS OR WHAT ARRANGEMENT HAS BEEN | | | MADE THAT TRACT A CAN NEVER BE SOLD AND THE AREA CAN BE | | | COUNTED AS PART OF THE FIRE DISTANCE SEPERATION? | | | | | | 5) SHEET A2 PLEASE PROVIDE CODE COMPLIANCE FOR 2010 | | | FBC-ENERGY 502.2.3.1 SHELL BUILDINGS. THE ENERGY | | | CALCULATIONS INDICATE THE ROOF INSULATION TO BE A R-40 | | | WHERE AS SHEET A2 INDICATES TYPES OF INSULATION TO BE | | | INSTALLED PLEASE PROVIDE HOW THEY WILL ACHIEVE A R-40 | | | VALUE. | | | | | | 6) SHEET A5 DETAIL # 1 THE PARAPET IS MISSING COPING. | | | 2010 FBC-B PARAPET WALLS SHALL BE PROPERLY COPED WITH | | | NONCOMBUSTIBLE, WEATHERPROOF MATERIALS OF A WIDTH NO | | | LESS THAN THE THICKNESS OF THE PARAPET WALL. METAL | | | COPING SHALL COMPLY WITH ANSI/SPRI ES-1 OR RAS 111. | | | | | | 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 8) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.41 COMPONENTS & CLADDING | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. | | | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS. | | | (B) WINDOWS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | (E) PRE-ENGINEERED A/C STANDS | | | | | | 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2014-07-02 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-06-30 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-06-30 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2014-06-30 14:34:20 | ELECTRICAL REVIEW IS APPROVED AS A SHELL ONLY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2013-11-25 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2013-11-25 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2013-11-25 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2013-11-25 11:13:59 | RETURNED TO BIN | | 2013-11-25 10:39:21 | THE FOLLOW CORRECTIONS AND/OR CLARIFICATIONS SHALL BE | | | SUBMITTED FOR AN ELECTRICAL PLANS APPROVAL | | | 1. THE TITLE BLOCK INDICATES THAT THE PERMIT IS FOR | | | BLDG. 5 & 6, YET THE CLOUD ON THE HOUSE PANEL IS MADE | | | AROUND THE LOAD FOR UNITS 8, 8A & 9. PLEASE CLARIFY | | | THIS. | | | 2. IF THIS IS BLDGS,5 & 6 OF A LARGER PARCEL, THIS HAS | | | TO BE INDICATED AND A SITE PLAN SUBMITTED. | | | 3. THE LOAD CALCS REFLECTED ON THE E1 PAGE ONLY INCLUDE | | | THE "HP" LOAD. A PANEL SCHEDULE REFLECTING THE | | | INDIVIDUAL LOADS OF EACH OF THE UNITS SHALL BE INCLUDED | | | EVEN IF TYPICAL OF ALL, SO SUCH BE ADDRESSED, THESE | | | UNITS SHALL BE EQUIPPED WITH MINIMAL ELECTRIC FOR LIFE | | | SAFETY. | | | 4. YOU SHALL INCLUDE THE MINIMAL EMERGENCY LIGHTING AND | | | ILLUMINATION FOR LIFE SAFETY. | | | 5. PAGE M1, REFLECTS A ROOF MOUNTED A/C TYPICAL OF EACH | | | UNIT WHICH IS NOT INCLUDED IN ANY ELECTRICAL PANEL | | | 6. A COMPLETE SERVICE DIAGRAM SHALL BE PROVIDED | | | INDICATING THE APPROPRIATE LOAD CALCULATIONS. | | | 7. AS PER THE FBC-ENERGY CONSERVATION SECTION 101.4.9 | | | SHELL BUILDINGS A SUBMITTAL COMPLYING SHALL BE | | | SUBMITTED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2013-07-10 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-07-10 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-07-10 |
Time |
11:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2013-07-23 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2013-07-23 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2013-07-23 |
Time |
|
Sent To |
I |
|
| Notes |
| 2013-07-23 15:20:28 | NO CONFLICT WITH UTILITIES |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2014-05-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2014-05-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2014-05-19 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2014-05-19 14:12:02 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENT: | | | | | | NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME | | | TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR | | | ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR | | | MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME | | | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED | | | WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE | | | PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY | | | DOOR. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2013-12-09 |
|
|
Cont ID |
|
| Sent By |
lphilmor |
Date |
2013-12-09 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
lphilmor |
Date |
2013-12-09 |
Time |
12:14 |
Sent To |
|
|
| Notes |
| 2013-12-09 12:15:31 | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PLANS WILL BE STAMPED UPON COMPLETION OF BUILDING | | | REQUIREMENTS | | | | | | LAUREN PHILMORE | | | FIRE INSPECTOR II / INVESTIGATOR I | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4783 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2013-06-21 |
|
|
Cont ID |
|
| Sent By |
lphilmor |
Date |
2013-06-21 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
lphilmor |
Date |
2013-06-20 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2013-06-21 11:43:06 | 8170 OKEECHOBEE BLVD., BUILDING 7 | | | PERMIT #13060229 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 1. NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK | | | INFORMATION. | | | 2. PROVIDE A LIFE SAFETY PLAN SHOWING ALL EXIT SIGNS, | | | EMERGENCY LIGHTING, PORTABLE FIRE EXTINGUISHERS. | | | 3. PLAN INDICATES SUITES 1-9, BUT NO FIRE RATED WALLS | | | PROVIDED. | | | 4. THUMB-TURN LOCK TO BE EQUIPPED WITH A LOCK/UNLOCK | | | INDICATOR. | | | 5. CONSTRUCTION TYPE IS REFERENCED TO BE TYPE VB, | | | HOWEVER, PLANS DO NOT APPEAR TO BE WOOD FRAMED | | | STRUCTURE. | | | 6. PLANS INDICATE NO TENANT SEPARATION WALLS AND THE | | | AREA IS INDICIATED AT 12,500 SQ. FT OF MERCANTILE | | | OCCUPANCY. PER NFPA 101 SECTION 36.3.5.1(2) STIPULATES | | | THAT SPRINKLERS ARE REQUIRED FOR MERCANTILE AREAS | | | EXCEEDING 12,000 SQ FT IN GROSS AREA. | | | 7. PROVIDE TACTILE SIGNAGE AT ALL EXIT DOORS. | | | 8. PLANS INDICATE TWO HYDRANTS ON THE SITE. PLEASE | | | INDICATE ANY ADDITIONAL HYDRANTS THAT MAY BE LOCATED TO | | | THE EAST AND SOUTH OF THIS BUILDING. | | | | | | | | | LAUREN PHILMORE | | | FIRE INSPECTOR II / INVESTIGATOR I | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4783 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2014-09-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-09-19 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-09-18 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2014-09-18 14:18:45 | SENT TO J WITMER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2014-09-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-07-29 |
Time |
18:14 |
Sent To |
|
|
| Notes |
| 2014-07-29 18:14:32 | TO ZONING | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-06-30 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-06-30 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-05-14 |
Time |
16:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-01-06 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-01-06 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2013-10-17 |
Time |
09:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-07-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-07-23 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-06-06 |
Time |
13:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
4 |
Status |
P |
Date |
2014-09-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-09-19 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-09-19 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2014-09-19 10:02:22 | IMPACT FEE ASSESSMENT: | | | MU-2014-020572-0000 | | | PROJECT NO, 00074-230 | | | $157,284.95 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
F |
Date |
2014-06-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-06-24 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2014-06-24 14:57:31 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2013-11-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-11-05 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-11-05 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2013-11-05 09:20:27 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2013-07-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-07-11 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-07-11 |
Time |
10:30 |
Sent To |
|
|
| Notes |
| 2013-07-11 10:30:51 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2014-08-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-08-23 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-08-23 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2014-08-23 16:09:19 | REVISION # 3 IS FOR WINDOW & DOOR LOCATION NORTH WALL. | | | JW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2013-11-13 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-11-13 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-11-13 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2013-11-13 09:08:18 | PASS PROVISO | | | CURBS ONLY TO BE INSTALLED ON SHELL. | | | AIRCONDITIONING PLAN AND ENERGY CALCULATIONS | | | WILL BE PROVIDED FOR EACH BUILDOUT. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2013-07-12 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-07-12 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-07-12 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2013-07-12 09:35:16 | CURBS ONLY TO BE INSTALLED ON SHELL. | | | AIR CONDITIONING PLAN AND ENERGY CALCULATION | | | WILL BE PROVIDED FOR EACH BUILD OUT | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2014-08-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-08-23 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-08-23 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2014-08-23 16:08:56 | REVISION # 3 IS FOR WINDOW & DOOR LOCATION NORTH WALL. | | | JW |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2013-10-30 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2013-10-30 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-10-30 |
Time |
10:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2013-06-19 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2013-06-19 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-06-19 |
Time |
13:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2014-09-08 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-09-08 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2014-09-08 |
Time |
17:35 |
Sent To |
|
|
| Notes |
| 2014-09-08 17:37:33 | SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE | | | FOLLOWING: | | | | | | A. LANDSCAPE REQUIRES A SEPARATE PERMIT APPLICATION FOR | | | EACH PARCEL (TRACT A & TRACT F) ON WHICH WORK IS BEING | | | DONE. THE SAME 2 COPIES OF THE LANDSCAPE PLAN MAY BE | | | USED FOR BOTH APPLICATIONS (SUBJECT TO CONCURRENT | | | SUBMITTAL). A COST ESTIMATE IS REQUIRED WITH THE | | | SUBMITTAL. | | | B. SIGNAGE | | | C. AWNINGS | | | D. PARKING LOT STRIPING | | | E. BICYCLE RACKS | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2014-09-08 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-08-19 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2014-08-19 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2014-08-19 16:26:03 | IN REVIEW | | | | | | AWAITING INFORMATION FROM ARCHITECT ON: | | | | | | 2) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO. | | | 288-11, ALL ROOF MOUNTED AIR CONDITIONING, MECHANICAL | | | EQUIPMENT, SATELLITE DISHES, GENERATORS, ETC., SHALL BE | | | SCREENED FROM VIEW ON ALL SIDES BY A VISUALLY OPAQUE | | | BARRIER CONSISTENT WITH THE COLOR, CHARACTER AND | | | ARCHITECTURAL STYLE OF THE STRUCTURES OR EQUIVALENT | | | LANDSCAPE MATERIAL. THE HEIGHT OF THE OPAQUE BARRIER | | | SHALL BE AS REQUIRED TO PROVIDE AMPLE SCREENING. | | | PROVIDE VERIFICATION THAT THE ROOFTOP MECHANICAL | | | EQUIPMENT WILL BE SCREENED AS REQUIRED BY THE | | | RESOLUTION FOR THE SPECIFIC EQUIPMENT PROPOSED FOR | | | INSTALLATION (EX. LINE OF SIGHT OR ELEVATIONS WITH THE | | | EQUIPMENT). | | | | | | AWAITING INFORMATION FROM LAND PLANNER ON: | | | | | | 1) REPEAT COMMENT: PURSUANT TO RESOLUTION NO. 288-11, A | | | CONSTRUCTION SITE SECURITY AND MANAGEMENT PLAN SHALL BE | | | SUBMITTED TO THE CITY'S POLICE DEPARTMENT CRIME | | | PREVENTION THROUGH ENVIRONMENTAL DESIGN ("CPTED") | | | OFFICIAL AND APPROVED PRIOR TO THE ISSUANCE OF THE | | | BUILDING PERMIT. | | | | | | SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE | | | FOLLOWING: | | | | | | A. LANDSCAPE REQUIRES A SEPARATE PERMIT APPLICATION FOR | | | EACH PARCEL (TRACT A & TRACT F) ON WHICH WORK IS BEING | | | DONE. THE SAME 2 COPIES OF THE LANDSCAPE PLAN MAY BE | | | USED FOR BOTH APPLICATIONS (SUBJECT TO CONCURRENT | | | SUBMITTAL). A COST ESTIMATE IS REQUIRED WITH THE | | | SUBMITTAL. | | | B. SIGNAGE | | | C. AWNINGS | | | D. PARKING LOT STRIPING | | | E. BICYCLE RACKS | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2014-06-04 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-06-04 |
Time |
15:39 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
2014-06-04 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2014-06-04 15:46:16 | FAILED | | | | | | PLEASE PROVIDE WRITTEN RESPONSES. | | | | | | 1) REPEAT COMMENT: PURSUANT TO RESOLUTION NO. 288-11, A | | | CONSTRUCTION SITE SECURITY AND MANAGEMENT PLAN SHALL BE | | | SUBMITTED TO THE CITY'S POLICE DEPARTMENT CRIME | | | PREVENTION THROUGH ENVIRONMENTAL DESIGN ("CPTED") | | | OFFICIAL AND APPROVED PRIOR TO THE ISSUANCE OF THE | | | BUILDING PERMIT. (CONTRARY TO THE RESPONSE COMMENT, NO | | | PLAN HAS BEEN SUBMITTED TO OFFICER KELLY CARSILLO) | | | | | | I) THE APPLICANT, AFTER SITE CLEARING AND PLACEMENT OF | | | CONSTRUCTION TRAILERS, SHALL INSTITUTE SECURITY | | | MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES FOR | | | THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT TO BE | | | LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL, | | | VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS, | | | REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE | | | SUBCONTRACTORS TO SECURE MACHINERY AND TOOLS AT END OF | | | WORK DAY AND/OR ANY OTHER MEASURE DEEMED APPROPRIATE TO | | | PROVIDE A SAFE AND SECURE WORKING ENVIRONMENT. | | | II) THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED | | | THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT. | | | NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A | | | STOP-WORK ORDER FOR THE ENTIRE PLANNED DEVELOPMENT. | | | | | | 2) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO. | | | 288-11, ALL ROOF MOUNTED AIR CONDITIONING, MECHANICAL | | | EQUIPMENT, SATELLITE DISHES, GENERATORS, ETC., SHALL BE | | | SCREENED FROM VIEW ON ALL SIDES BY A VISUALLY OPAQUE | | | BARRIER CONSISTENT WITH THE COLOR, CHARACTER AND | | | ARCHITECTURAL STYLE OF THE STRUCTURES OR EQUIVALENT | | | LANDSCAPE MATERIAL. THE HEIGHT OF THE OPAQUE BARRIER | | | SHALL BE AS REQUIRED TO PROVIDE AMPLE SCREENING. | | | PROVIDE VERIFICATION THAT THE ROOFTOP MECHANICAL | | | EQUIPMENT WILL BE SCREENED AS REQUIRED BY THE | | | RESOLUTION FOR THE SPECIFIC EQUIPMENT PROPOSED FOR | | | INSTALLATION (EX. LINE OF SIGHT OR ELEVATIONS WITH THE | | | EQUIPMENT). | | | | | | 3) REPEAT COMMENT: THE APPROVED ELEVATIONS FOR BUILDING | | | #7 HAVE CHANGED. THE ZONING STAFF HAS NOT APPROVED THE | | | REVISED ELEVATIONS, SPECIFICALLY: | | | | | | A. THE PREVIOUS MINOR AMENDMENT APPROVAL FOR BUILDING | | | #7 PERMITTED THE REDUCTION OF THE CITY COMMISSION | | | APPROVED 9 DOORS TO 3 DOORS ON THE NORTHERN ELEVATION, | | | PROVIDED THAT WINDOWS ARE PROVIDED IN THEIR PLACE WHERE | | | THE 6 DOORS HAD BEEN. THE TWO END BAY LOCATIONS SHALL | | | INCLUDE WINDOWS, NOT STUCCO DESIGNED TO LOOK SIMILAR TO | | | A WINDOW. | | | | | | 4) NEW COMMENT: THE REVISED NORTH/SOUTH BUILDING | | | DIMENSION TO ACCOMMODATE THE 12,000 SQUARE FOOT | | | BUILDING IS NOT REFLECTED ON THE CONSTRUCTION LAYOUT | | | SURVEY. THE NORTH SETBACK (19.5 FEET) DOES NOT COMPLY | | | WITH THE SETBACK APPROVED ON THE SITE PLAN (20.4 FEET). | | | | | | 5) REPEAT COMMENT: PROVIDE A COPY OF THE REVISED SITE | | | PLAN APPROVED BY ZONING THROUGH THE MINOR AMENDMENT | | | PROCESS. | | | | | | SEPTATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE | | | FOLLOWING: | | | | | | A. LANDSCAPE REQUIRES A SEPARATE PERMIT APPLICATION FOR | | | EACH PARCEL (TRACT A & TRACT F) ON WHICH WORK IS BEING | | | DONE. THE SAME 2 COPIES OF THE LANDSCAPE PLAN MAY BE | | | USED FOR BOTH APPLICATIONS (SUBJECT TO CONCURRENT | | | SUBMITTAL). A COST ESTIMATE IS REQUIRED WITH THE | | | SUBMITTAL. | | | B. SIGNAGE | | | C. AWNINGS | | | D. PARKING LOT STRIPING | | | E. BICYCLE RACKS | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | 2014-05-15 16:25:09 | 5/15/14 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2014-01-06 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-01-06 |
Time |
15:18 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
2014-01-06 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2014-01-06 15:18:39 | FAILED | | | | | | PLEASE PROVIDE WRITTEN RESPONSES. | | | | | | 1) REPEAT COMMENT: PURSUANT TO THE PALM BEACH COUNTY | | | TRAFFIC PERFORMANCE STANDARDS REVIEW LETTER ISSUED ON | | | SEPTEMBER 17, 2009, NO BUILDING PERMITS SHALL BE ISSUED | | | BY THE CITY AFTER DECEMBER 31, 2012. AN EXTENSION OF | | | THIS DEADLINE MAY BE ISSUED BY PALM BEACH COUNTY. A | | | MINOR PLANNED DEVELOPMENT AMENDMENT IS REQUIRED TO | | | UPDATE THE COUNTY BUILD OUT DATE. | | | | | | 2) REPEAT COMMENT: PURSUANT TO RESOLUTION NO. 288-11, A | | | CONSTRUCTION SITE SECURITY AND MANAGEMENT PLAN SHALL BE | | | SUBMITTED TO THE CITY'S POLICE DEPARTMENT CRIME | | | PREVENTION THROUGH ENVIRONMENTAL DESIGN ("CPTED") | | | OFFICIAL AND APPROVED PRIOR TO THE ISSUANCE OF THE | | | BUILDING PERMIT. (CONTRARY TO THE RESPONSE COMMENT, NO | | | PLAN HAS BEEN SUBMITTED TO OFFICER KELLY CARSILLO) | | | | | | I) THE APPLICANT, AFTER SITE CLEARING AND PLACEMENT OF | | | CONSTRUCTION TRAILERS, SHALL INSTITUTE SECURITY | | | MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES FOR | | | THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT TO BE | | | LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL, | | | VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS, | | | REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE | | | SUBCONTRACTORS TO SECURE MACHINERY AND TOOLS AT END OF | | | WORK DAY AND/OR ANY OTHER MEASURE DEEMED APPROPRIATE TO | | | PROVIDE A SAFE AND SECURE WORKING ENVIRONMENT. | | | II) THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED | | | THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT. | | | NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A | | | STOP-WORK ORDER FOR THE ENTIRE PLANNED DEVELOPMENT. | | | | | | 3) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO. | | | 288-11, ALL ROOF MOUNTED AIR CONDITIONING, MECHANICAL | | | EQUIPMENT, SATELLITE DISHES, GENERATORS, ETC., SHALL BE | | | SCREENED FROM VIEW ON ALL SIDES BY A VISUALLY OPAQUE | | | BARRIER CONSISTENT WITH THE COLOR, CHARACTER AND | | | ARCHITECTURAL STYLE OF THE STRUCTURES OR EQUIVALENT | | | LANDSCAPE MATERIAL. THE HEIGHT OF THE OPAQUE BARRIER | | | SHALL BE AS REQUIRED TO PROVIDE AMPLE SCREENING. | | | PROVIDE VERIFICATION THAT THE ROOFTOP MECHANICAL | | | EQUIPMENT WILL BE SCREENED AS REQUIRED BY THE | | | RESOLUTION FOR THE SPECIFIC EQUIPMENT PROPOSED FOR | | | INSTALLATION (EX. LINE OF SIGHT OR ELEVATIONS WITH THE | | | EQUIPMENT). | | | | | | 4) THE APPROVED ELEVATIONS FOR BUILDING 7 HAVE CHANGED. | | | THE ZONING STAFF HAS NOT APPROVED THE REVISED | | | ELEVATIONS, SPECIFICALLY: | | | | | | A. THE PREVIOUS MINOR AMENDMENT APPROVAL FOR BUILDING | | | #7 PERMITTED THE REDUCTION OF THE CITY COMMISSION | | | APPROVED 9 DOORS TO 3 DOORS ON THE NORTHERN ELEVATION, | | | PROVIDED THAT WINDOWS ARE PROVIDED IN THEIR PLACE WHERE | | | THE 6 DOORS HAD BEEN. THE TWO END BAY LOCATIONS SHALL | | | INCLUDE WINDOWS. | | | | | | B. THE THREE DOORS SHALL HAVE A SIMILAR BANDING AROUND | | | THEM AS THE WINDOWS TO ENHANCE THE APPEARANCE OF THE | | | DOORWAY ELEMENTS. THIS WILL OFFSET THE FACT THAT THE | | | DOORWAYS HAVE BEEN NARROWED WITH THE PROPOSED PLANS | | | WHEN COMPARED TO THE APPROVED PLANS. PLEASE CONSIDER | | | ALIGNING THE DOORS IN A SYMMETRICAL PATTERN ALONG THE | | | FACADE. | | | | | | 5) PROVIDE A COPY OF THE REVISED SITE PLAN ONCE IT IS | | | APPROVED BY ZONING THROUGH THE MINOR AMENDMENT PROCESS. | | | | | | 6) THE LANDSCAPE REQUIRES A SEPARATE PERMIT APPLICATION | | | FOR EACH PARCEL (TRACT A & TRACT F) ON WHICH WORK IS | | | BEING DONE. THE SAME 2 COPIES OF THE LANDSCAPE PLAN MAY | | | BE USED FOR BOTH APPLICATIONS (SUBJECT TO CONCURRENT | | | SUBMITTAL). A COST ESTIMATE IS REQUIRED WITH THE | | | SUBMITTAL. | | | | | | 7) SIGNAGE AND AWNINGS REQUIRE SEPARATE PERMITS WITH | | | PLANS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | | | | | | 2013-10-30 15:08:11 | 10/29/13 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2013-06-24 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2013-06-24 |
Time |
15:58 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
2013-06-21 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2013-06-24 16:21:01 | FAILED | | | | | | PLEASE PROVIDE WRITTEN RESPONSES. | | | | | | 1) PURSUANT TO THE PALM BEACH COUNTY TRAFFIC | | | PERFORMANCE STANDARDS REVIEW LETTER ISSUED ON SEPTEMBER | | | 17, 2009, NO BUILDING PERMITS SHALL BE ISSUED BY THE | | | CITY AFTER DECEMBER 31, 2012. AN EXTENSION OF THIS | | | DEADLINE MAY BE ISSUED BY PALM BEACH COUNTY. A MINOR | | | PLANNED DEVELOPMENT AMENDMENT IS REQUIRED TO UPDATE THE | | | THE COUNTY BUILD OUT DATE. | | | | | | 2) PURSUANT TO RESOLUTION NO. 288-11, A CONSTRUCTION | | | SITE SECURITY AND MANAGEMENT PLAN SHALL BE SUBMITTED TO | | | THE CITY'S POLICE DEPARTMENT CRIME PREVENTION THROUGH | | | ENVIRONMENTAL DESIGN ("CPTED") OFFICIAL AND APPROVED | | | PRIOR TO THE ISSUANCE OF THE BUILDING PERMIT. | | | | | | I) THE APPLICANT, AFTER SITE CLEARING AND PLACEMENT OF | | | CONSTRUCTION TRAILERS, SHALL INSTITUTE SECURITY | | | MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES FOR | | | THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT TO BE | | | LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL, | | | VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS, | | | REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE | | | SUBCONTRACTORS TO SECURE MACHINERY AND TOOLS AT END OF | | | WORK DAY AND/OR ANY OTHER MEASURE DEEMED APPROPRIATE TO | | | PROVIDE A SAFE AND SECURE WORKING ENVIRONMENT. | | | II) THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED | | | THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT. | | | NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A | | | STOP-WORK ORDER FOR THE ENTIRE PLANNED DEVELOPMENT. | | | | | | 3) SHEET A-1 DOES NOT SHOW THE FOUNDATION PLANTING | | | AREAS AT FIVE (5) FEET WIDE UNDER THE AREAS COVERED BY | | | THE AWNINGS. | | | | | | 4) IN ACCORDANCE WITH RESOLUTION NO. 288-11, ALL ROOF | | | MOUNTED AIR CONDITIONING, MECHANICAL EQUIPMENT, | | | SATELLITE DISHES, GENERATORS, ETC., SHALL BE SCREENED | | | FROM VIEW ON ALL SIDES BY A VISUALLY OPAQUE BARRIER | | | CONSISTENT WITH THE COLOR, CHARACTER AND ARCHITECTURAL | | | STYLE OF THE STRUCTURES OR EQUIVALENT LANDSCAPE | | | MATERIAL. THE HEIGHT OF THE OPAQUE BARRIER SHALL BE AS | | | REQUIRED TO PROVIDE AMPLE SCREENING. PROVIDE | | | VERIFICATION THAT THE ROOFTOP MECHANICAL EQUIPMENT WILL | | | BE SCREENED AS REQUIRED BY THE RESOLUTION FOR THE | | | SPECIFIC EQUIPMENT PROPOSED FOR INSTALLATION (EX. LINE | | | OF SIGHT OR ELEVATIONS WITH THE EQUIPMENT). | | | | | | 5) THE APPROVED ELEVATIONS FOR BUILDING 7 HAVE CHANGED. | | | THE BUILDING IS TALLER AND THE REQUIRED DOORS ON THE | | | NORTH FACADE HAVE BEEN RELOCATED (2) AND REMOVED (1) | | | AND ADDITIONAL WINDOWS WERE ADDED ON THE WESTERN | | | FACADE. REVISED ELEVATIONS ARE REQUIRED AS PART OF A | | | MINOR PLANNED DEVELOPMENT AMENDMENT TO SHOW THE ACTUAL | | | CONDITIONS. THE SITE AND LANDSCAPE PLANS DO NOT MATCH | | | THE PROPOSED DOOR MODIFICATIONS. | | | | | | 6) THE LANDSCAPE REQUIRES A SEPARATE PERMIT APPLICATION | | | FOR EACH PARCEL (TRACT A & TRACT F) ON WHICH WORK IS | | | BEING DONE. THE SAME 2 COPIES OF THE LANDSCAPE PLAN MAY | | | BE USED FOR BOTH APPLICATIONS (SUBJECT TO CONCURRENT | | | SUBMITTAL). A COST ESTIMATE IS REQUIRED WITH THE | | | SUBMITTAL. | | | | | | 7) THE PLANS TO CONSTRUCT THE PARKING REQUIRED PRIOR TO | | | THE C.O. OF THE LAST PHASE I BUILDING (GENERALLY ALONG | | | THE SOUTH ACCESS DRIVE) SHALL BE INCLUDED ON A PARKING | | | LOT STRIPING PERMIT FOR TRACT A PRIOR TO ZONING | | | APPROVAL OF THIS PERMIT. STRIPING DETAILS FOR ALL | | | CONDITIONS SHALL BE PROVIDED. THE PARKING SHALL BE | | | INSTALLED PRIOR TO THE C.O. OF THIS BUILDING OR | | | BUILDING 5/6, WHICHEVER OCCURS LAST. | | | | | | 8) SIGNAGE AND AWNINGS REQUIRE SEPARATE PERMITS WITH | | | PLANS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | |
|
|