Plan Review Details - Permit 13060228
Plan Review Stops For Permit 13060228
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-05-28 Cont ID  
Sent By jwitmer Date 2014-05-28 Time 09:36 Rev Time 0.00
Received By jwitmer Date 2014-05-27 Time 09:29 Sent To  
Notes
2014-05-27 15:41:27BUILDING PLAN REVIEW
 PERMIT: 13060228
 ADD: 8170 OKEECHOBEE BLVD BLDG #5& 6
 CONT: ATLANTIC ENGINEERING SERVICES
 TEL: (561)267-5941
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: TUES. MAY 27 /2014
 ACTION: PROVISO
  
 1) THE UNITY OF TITLE HAS NOT BEEN RECORDED AT THE
 COUNTY CLERK OF THE COURT, THIS PROCEDURE HAS TO
 COMPLETED BEFORE A CERTIFICATE OF COMPELTION WILL BE
 ISSUED FOR THE SHELL BUILDINGS 5 & 6. A HOLD WILL BE
 PUT ON THE PRINTING OF THE CERTIFICATE OF COMPLETION.
  
 2) PLEASE PROVIDE ROOFTOP A/C CURB PRODUCT APPROVAL.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES (ROOF TOP A/C
 CURBING)
  
 3) ROOFING PRODUCT APPROVALS SUBMITTED:
  
 MIAMI DADE NOA: 13-0129.07 / PAGES 1-18
 JOHN MANVILLE BUILT-UP ROOFING SYSTEM OVER STEEL DECKS
 NO-SUB-SYSTEM IS IDENTIFIED MAY REQUIRE ENHANCED
 FASTENING IN ROOFING ZONES 2 & 3. NOTE OVER 3 FOOT
 PARAPET NO ZONE 3 REQUIREMENTS.
  
 MIAMI DADE NOA: 13-0129.19 / PAGES 1-38
 JOHN MANVILLE BUILT-UP ROOFING SYSTEM OVER STEEL DECKS
 NO-SUB-SYSTEM IS IDENTIFIED MAY REQUIRE ENHANCED
 FASTENING IN ROOFING ZONES 2 & 3. NOTE OVER 3 FOOT
 PARAPET NO ZONE 3 REQUIREMENTS.
  
 MIAMI DADE NOA: 13-0529.06 PAGES 1-17
 JOHN MANVILLE BUILT-UP ROOFING SYSTEM OVER STEEL DECKS
 NO-SUB-SYSTEM IS IDENTIFIED MAY REQUIRE ENHANCED
 FASTENING IN ROOFING ZONES 2 & 3. NOTE OVER 3 FOOT
 PARAPET NO ZONE 3 REQUIREMENTS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-11-04 Cont ID  
Sent By jwitmer Date 2013-11-04 Time 12:59 Rev Time 0.00
Received By jwitmer Date 2013-11-04 Time 10:30 Sent To  
Notes
2013-11-04 12:19:47BUILDING PLAN REVIEW
 PERMIT: 13060228
 ADD: 8170 OKEECHOBEE BLVD BLDG #5& 6
 CONT: ATLANTIC ENGINEERING SERVICES
 TEL: (561)267-5941
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: JULY 10/2013
 ACTION: DENIED
  
 1) 2ND REQUEST!!!!!THE SURVEY INDICATES THIS SITE IS
 LOCATED IN A AH FLOOD ZONE (EL 17'). THE CITY MUNI-CODE
 SECTION 94-546 (B)(2) NONRESIDENTIAL CONSTRUCTION DOES
 ALLOW FOR EITHER THE LOWEST FLOOR ELEVATION TO BE
 ELEVATED SIX INCHES HIGHER THAN THE BASE FLOOD
 ELEVATION OR, TOGETHER WITH THE ATTENDANT UTILITES AND
 SANITARY FACILITIES, BE FLOODPROOFED SO THAT BELOW THE
 SIX INCHES ABOVE THE BASE FLOOD LEVEL THE STRUCTURE IS
 WATER TIGHT.
 THREE FLOOD ZONE CERTIFICATES WILL BE REQUIRED DURING
 THE CONSTRUCTION PROCESS AND BEFORE A CERTIFICATE OF
 COMPLETION CAN BE ISSUED.
 1A) THE FIRST FLOOD ELEVATION CERTIFICATE WILL BE THE
 PROPOSED FINISH FLOOR ELEVATION IN HGVD, TO BE PROVIED
 TO THE CITY BEFORE PERMIT ISSUANCE.
 1B) THE SECOND FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED AFTER THE FLOOR SLAB IS POURED.
 1C) THE THIRD CERTIFICATE WILL BE REQUIRED PRIOR TO THE
 CERTIFICATTE OF COMPLETION, WITH THE HEIGHT OF ANY SLAB
 FOR A/C CONDENSORS.
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31,2015
  
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2012, THROUGH JULY 31/ 2015.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 SEPTEMBER 30/ 2013. ALTHOUGH THE OLD VERSION OF THE
 FORM IS NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING
 COPIES MAY BE USED UNTIL SEPTEMBER 30/2013. ELEVATIONS
 CERTIFIED ON OR AFTER OCTOBER 1/2013, MUST BE SUBMITTED
 ON THE NEW FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 2)SEMI-COMPLIED. SHEET A1 INDICATES THIS BUILDING WAS
 DESIGNED AS A TYPE 5B UNSPRINKLERED BUILDING, THE PLANS
 REFERENCE TABLE 503 , MERCANTILE AND ALLOWED AREA AS
 13,200 SQ FT. PLEASE REVIEW THE 2010 FBC-B TABLE 503,
 MERCANTILE ONLY ALLOWS 9,000 SQ FT FOR A TYPE VB
 -UNSPRINKLERED BUILDING. PLEASE REVIEW FBC-B 903.2.7
 (1) MERCANTILE WITH FIRE AREAS THAT EXCEED 12,000 SQ FT
 REQUIRE FIRE SPRINKLERS. PLEASE NOTE THE BUILDING
 FOOTPRINT OR AREA IS TAKEN FROM THE INTERIOR SIDE OF
 THE EXTERIOR WALL, OR APPROXIMATELY 12,902 SQ FT. THIS
 STILL EXCEEDS THE 9,000 SQ FT ALLOWED BY TABLE 503.1.
 IF THE DESIGNER WISHES TO TAKE BUILDING AREA
 MODIFICATIONS FOR FRONTAGE INCREASE (506.2) PLEASE
 PROVIDE THE FORMULA ON THE PLANS AND STATE AS SUCH,
 AREA INCREASE TAKEN.
  
 THIS PERMIT IS FOR THE BUILDING OF BUILDINGS 5 & 6
 CONNECTED BY A (4) HOUR FIRE WALL. THE ISSUE IS THE
 PROPERTY APPRAISERS OFFICE INDICATES AS WELL AS THE
 SURVEY THE TWO BUILDINGS ARE ON 2 SEPARATE PARCELS OF
 LAND, BLDG # 5 ONTRACT E 74-442-43-29-30-005-0000 AND
 BLDG # 6 ON TRACT 74-42-43-29-30-004-0000. AUNITY OF
 TITLE WIL BE REQUIRED TO UNIT THESE 2 TRACTS OF LAND SO
 THERE WILL BE NO PROPERTY LINE BETWEEN THEM.
  
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
  
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 3) 2ND REQUEST, IN THE RESPONSE LETTER IT DOES STATE
 THAT A NEW EASEMENT IS TO BE SECURED. IN THE WEST SIDR
 OF THE SURVEY AND NOTE # 7 INDICATE A PALM BEACH COUNTY
 UTILITY EASEMENT THAT IS TO BE VACATED, PLEASE SHOW
 DOCUMENTATION AS SUCH. 107.2.1 ADDITIONAL INFORMATION.
  
 4A) 2ND REQUEST, SHEET A3 EAST ELEVATION SHOWS A
 PERCENTAGE OF OPENINGS (WINDOWS & DOORS), THE SURVEY
 INDICATES THE DISTANCE TO THE PROPERTY LINE IS 9.6 FT.
 PLEASE EITHER PROVIDE THE PER CENT AGE OF ALLOWABLE
 OPENINGS 5-10 FT , 10% UNPROTECTED OPENINGS OR WHAT
 ARRANGEMENT HAS BEEN MADE THAT TRACT A CAN NEVER BE
 SOLD AND THE AREA CAN BE COUNTED AS PART OF THE FIRE
 DISTANCE SEPERATION? THE OWNERS MUST PRODUCE EITHER
 TYPE OF THESE TYPES OF DOCUMENTS, UNITY OF CONTROL, A
 RESTRICTIVE COVENENT OR A UNITY OF TITLE FOR THE AMOUNT
 OF QPENINGS AND THE CLOSENESS OF THE PREOPERTY LINE
 SHOWN ON BOTH THE SURVEY AND THE PBC PROPERTY
 APPRAISERS WEB SITE. DIRECTLY EAST OF TRACT D IS COMMON
 TRACT A 8120 OKEECHOBEE BLVD PCN
 74-42-43-29-30-001-0000.
  
 4B) 2ND REQUEST, BUILDING #6 TRACT D, SEE SURVEY FOR
 LOT LINE TO BUILDING DISTANCE (IRC LB # 7344) MARKERS
 SEE SURVEY. SHEET A3 SOUTH ELEVATION INDICATES WINDOWS
 IN THIS WALL SECTION THAT ARE 3.7 FT AWAY FROM THE
 PROPERTY LINE, THE WALL SHOWS COMPLIANCE WITH TABLE
 602, PLEASE SHOW CODE COMPLIANCE FOR OPENINING 3-5 FT
 FROM THE PROPERTY LINE, TABLE 705.8 NOT PERMITED FOR
 UNPROTECTED WINDOWS.
  
 4C) 2ND REQUEST, SHEET A2 THE EAST SIDE OF BUILDING # 5
 LOCATED ON TRACT E, SEE SURVEY INDICATES THE DISTANCE
 FROM THE PROPERTY LINE AS 6.2 FT AWAY, SHOW COMPLIANCE
 WITH ALLOWABLE OPENINGS FOR WINDOWS & A DOORS FROM THE
 PROPERTY LINE. PLEASE PROVIDE COMPLIANCE WITH FBC-B
 TABLE 705.8 10 % OPENINGS.
  
 5) 2ND REQUEST, SHEET A2 PLEASE PROVIDE CODE COMPLIANCE
 FOR 2010 FBC-ENERGY 502.2.3.1 SHELL BUILDINGS. THE
 ENERGY CALCULATIONS INDICATE THE ROOF INSULATION TO BE
 A R-40
 SHEET A2 INDICATES TYPES OF INSULATION TO BE INSTALLED
 PLEASE PROVIDE HOW THEY WILL ACHIEVE A R-40 VALUE, NOTE
 WITHIN THE ENERGY CALCULATIONS SUBMITED FOR SHELL
 BUILDINGS UNDER THE HEADING MATERIALS USED THERE ARE NO
 MATERIALS LISTED FOR THE ROOFING SHOWING A VALUE OF
 R40. 2010 FL ENERGY CODE TABLE 502.1.1.1(1). ENVELOPE
 PRESRIPTIVE MEASURES FOR SHELL BUILDINGS. THE PLANS
 SHOW MATERIAL TO BE INSTALLED BUT NOT IN THE ENERGY
 DOCUMENTS THAT PROVIDE THE R-VALUE FOR EACH COMPONENT.
  
 6)COMPLIED. SHEET A5 DETAIL # 1 THE PARAPET IS MISSING
 COPING. 2010 FBC-B PARAPET WALLS SHALL BE PROPERLY
 COPED WITH NONCOMBUSTIBLE, WEATHERPROOF MATERIALS OF A
 WIDTH NO LESS THAN THE THICKNESS OF THE PARAPET WALL.
 METAL COPING SHALL COMPLY WITH ANSI/SPRI ES-1 OR RAS
 111.
  
 7) SEMI-COMPLIED. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 8) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)((D) ROOFING PRODUCTS AND ASSEMBLIES
 SUBMITTED WERE (2) ROOFING PRODUCT APPROVALS FOR FLAT
 ROOFS
 NOA 13-0129.07 1OF 18 SHEETS NO SUB-SYSTEM IDENTIFIED
 SEE EITHER LIMITATION # 7 OR 9 PER SUB-SYSTEM
 NOA 13-0129.19 1OF 38 SHEETS, NO SUB-SYSTEM IDENTIED
 SEE EITHER LIMITATION # 7 OR 9 PER SUB-SYSTEM
 (E) PRE-ENGINEERED A/C STANDS
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-11 Cont ID  
Sent By jwitmer Date 2013-07-11 Time 12:13 Rev Time 0.00
Received By jwitmer Date 2013-07-11 Time 11:03 Sent To  
Notes
2013-07-11 11:29:16BUILDING PLAN REVIEW
 PERMIT: 13060228
 ADD: 8170 OKEECHOBEE BLVD BLDG # 6
 CONT: ATLANTIC ENGINEERING SERVICES
 TEL: (561)267-5941
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: JULY 10/2013
 ACTION: DENIED
  
 1) THE SURVEY INDICATES THIS SITE IS LOCATED IN A AH
 FLOOD ZONE (EL 17'). THE CITY MUNI-CODE SECTION 94-546
 (B)(2) NONRESIDENTIAL CONSTRUCTION DOES ALLOW FOR
 EITHER THE LOWEST FLOOR ELEVATION TO BE ELEVATED SIX
 INCHES HIGHER THAN THE BASE FLOOD ELEVATION OR,
 TOGETHER WITH THE ATTENDANT UTILITES AND SANITARY
 FACILITIES, BE FLOODPROOFED SO THAT BELOW THE SIX
 INCHES ABOVE THE BASE FLOOD LEVEL THE STRUCTURE IS
 WATER TIGHT.
 THREE FLOOD ZONE CERTIFICATES WILL BE REQUIRED DURING
 THE CONSTRUCTION PROCESS AND BEFORE A CERTIFICATE OF
 COMPLETION CAN BE ISSUED.
 1A) THE FIRST FLOOD ELEVATION CERTIFICATE WILL BE THE
 PROPOSED FINISH FLOOR ELEVATION IN HGVD.
 1B) THE SECOND FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED AFTER THE FLOOR SLAB IS POURED.
 1C) THE THIRD CERTIFICATE WILL BE REQUIRED PRIOR TO THE
 CERTIFICATTE OF COMPLETION, WITH THE HEIGHT OF ANY SLAB
 FOR A/C CONDENSORS.
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31,2015
  
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2012, THROUGH JULY 31/ 2015.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 SEPTEMBER 30/ 2013. ALTHOUGH THE OLD VERSION OF THE
 FORM IS NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING
 COPIES MAY BE USED UNTIL SEPTEMBER 30/2013. ELEVATIONS
 CERTIFIED ON OR AFTER OCTOBER 1/2013, MUST BE SUBMITTED
 ON THE NEW FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 2) SHEET A1 INDICATES THIS BUILDING WAS DESIGNED AS A
 TYPE 5B UNSPRINKLERED BUILDING, THE PLANS REFERENCE
 TABLE 503 , MERCANTILE AND ALLOWED AREA AS 13,200 SQ
 FT. PLEASE REVIEW THE 2010 FBC-B TABLE 503, MERCANTILE
 ONLY ALLOWS 9,000 SQ FT FOR A TYPE VB -UNSPRINKLERED
 BUILDING. PLEASE REVIEW FBC-B 903.2.7 (1) MERCANTILE
 WITH FIRE AREAS THAT EXCEED 12,000 SQ FT REQUIRE FIRE
 SPRINKLERS. PLEASE NOTE THE BUILDING FOOTPRINT OR AREA
 IS TAKEN FROM THE INTERIOR SIDE OF THE EXTERIOR WALL,
 OR APPROXIMATELY 12,902 SQ FT. THIS STILL EXCEEDS THE
 9,000 SQ FT ALLOWED BY TABLE 503.1. IF THE DESIGNER
 WISHES TO TAKE BUILDING AREA MODIFICATIONS FOR FRONTAGE
 INCREASE (506.2) PLEASE PROVIDE THE FORMULA ON THE
 PLANS AND STATE AS SUCH, AREA INCREASE TAKEN.
  
 THERE IS A DISCREPANCY BETWEEN THE SP-1 AND SHEET A-1.
 THE SITE PLAN INDICATES ON THE NORTHWEST CORNER OF THE
 BUILDING 1 DOORWAY AND LANDING, THIS DOOR WAY IS NOT
 LOCATED ON THE A1 SHEET. FURTHER MORE AS FOR THE SHELL
 BUILDING WITH THE TENANT LINES AS SHOWN IS CODE
 COMPLIANT FOR COMMON PATH OF TRAVEL UNDER 75 FEET AND A
 OCCUPANT LOAD OF LESS THAN 50. IF ON ANY TENANT
 BUILD-OUT ANY WHERE TWO TENANT SPACES ARE COMBINED THE
 OCCUPANT LOAD IS OVER 50, THE CODE (TABLE 1015.1) WOULD
 TWO EXIT DOORS, AND THE TWO FRONT ENTRY DOORS DO NOT
 COMPLY WITH FBC-B 1015.2.1 DOORS BEING 1/2 THE DIAGONAL
 DISTANCE APART REQUIRING EITHER A DOOR TO THE REAR OF
 THE UNIT OR THE FRONT ENTRY DOORS BEING RELOCATED TO
 MEET THE 1/2 THE DIADONAL DISTANCE APART.
  
 3) IN THE WEST SIDR OF THE SURVEY AND NOTE # 7 INDICATE
 A PALM BEACH COUNTY UTILITY EASEMENT THAT IS TO BE
 VACATED, PLEASE SHOW DOCUMENTATION AS SUCH. 107.2.1
 ADDITIONAL INFORMATION.
  
 4A) SHEET A3 EAST ELEVATION SHOWS A PERCENTAGE OF
 OPENINGS (WINDOWS & DOORS), THE SURVEY INDICATES THE
 DISTANCE TO THE PROPERTY LINE IS 9.6 FT. PLEASE EITHER
 PROVIDE THE PER CENT AGE OF ALLOWABLE OPENINGS 5-10 FT
 , 10% UNPROTECTED OPENINGS OR WHAT ARRANGEMENT HAS BEEN
 MADE THAT TRACT A CAN NEVER BE SOLD AND THE AREA CAN BE
 COUNTED AS PART OF THE FIRE DISTANCE SEPERATION?
  
 4B) SHEET A3 SOUTH ELEVATION INDICATES WINDOWS IN THIS
 WALL SECTION THAT ARE 3.7 FT AWAY FROM THE PROPERTY
 LINETHE WALL SHOWS COMPLIANCE WITH TABLE 602, PLEASE
 SHOW CODE COMPLIANCE FOR OPENINING 3-5 FT FROM THE
 PROPERTY LINE, TABLE 705.8 NOT PERMITED FOR UNPROTECTED
 WINDOWS.
  
 4C) SHEET A2 THE SOUTH END OF THE BUILDING ALSO SHOWS
 WINDOWS & A DOOR 6.2 FT AWAY FROM THE PROPERTY LINE.
 PLEASE PROVIDE COMPLIANCE WITH FBC-B TABLE 705.8 10 %
 OPENINGS.
  
 5) SHEET A2 PLEASE PROVIDE CODE COMPLIANCE FOR 2010
 FBC-ENERGY 502.2.3.1 SHELL BUILDINGS. THE ENERGY
 CALCULATIONS INDICATE THE ROOF INSULATION TO BE A R-40
 WHERE AS SHEET A2 INDICATES TYPES OF INSULATION TO BE
 INSTALLED PLEASE PROVIDE HOW THEY WILL ACHIEVE A R-40
 VALUE.
  
 6) SHEET A5 DETAIL # 1 THE PARAPET IS MISSING COPING.
 2010 FBC-B PARAPET WALLS SHALL BE PROPERLY COPED WITH
 NONCOMBUSTIBLE, WEATHERPROOF MATERIALS OF A WIDTH NO
 LESS THAN THE THICKNESS OF THE PARAPET WALL. METAL
 COPING SHALL COMPLY WITH ANSI/SPRI ES-1 OR RAS 111.
  
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) PRE-ENGINEERED A/C STANDS
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2014-06-11 Cont ID  
Sent By albarran Date 2014-06-11 Time 15:11 Rev Time 0.00
Received By albarran Date 2014-06-11 Time 14:38 Sent To I
Notes
2014-06-11 15:12:01IMPORTANT NOTICE
 THIS STRUCTURE IS PERMTTED AS AN EMPTY SHELL ONLY.
 NO OCCUPANCY PERMITTED.
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2013-11-25 Cont ID  
Sent By albarran Date 2013-11-25 Time 09:38 Rev Time 0.00
Received By albarran Date 2013-11-25 Time 08:59 Sent To  
Notes
2013-11-25 09:50:36RETURNED TO BIN
2013-11-25 09:48:26THE FOLLOW CORRECTIONS AND/OR CLARIFICATIONS SHALL BE
 SUBMITTED FOR AN ELECTRICAL PLANS APPROVAL
 1. THE TITLE BLOCK INDICATES THAT THE PERMIT IS FOR
 BLDG. 5 & 6, YET THE CLOUD ON THE HOUSE PANEL IS MADE
 AROUND THE LOAD FOR UNITS 8, 8A & 9. PLEASE CLARIFY
 THIS.
 2. IF THIS IS BLDGS,5 & 6 OF A LARGER PARCEL, THIS HAS
 TO BE INDICATED AND A SITE PLAN SUBMITTED.
 3. THE LOAD CALCS REFLECTED ON THE E1 PAGE ONLY INCLUDE
 THE "HP" LOAD. A PANEL SCHEDULE REFLECTING THE
 INDIVIDUAL LOADS OF EACH OF THE UNITS SHALL BE INCLUDED
 EVEN IF TYPICAL OF ALL, SO SUCH BE ADDRESSED, THESE
 UNITS SHALL BE EQUIPPED WITH MINIMAL ELECTRIC FOR LIFE
 SAFETY.
 4. YOU SHALL INCLUDE THE MINIMAL EMERGENCY LIGHTING AND
 ILLUMINATION FOR LIFE SAFETY.
 5. PAGE M1, REFLECTS A ROOF MOUNTED A/C TYPICAL OF EACH
 UNIT WHICH IS NOT INCLUDED IN ANY ELECTRICAL PANEL
 6. A COMPLETE SERVICE DIAGRAM SHALL BE PROVIDED
 INDICATING THE APPROPRIATE LOAD CALCULATIONS.
 7. AS PER THE FBC-ENERGY CONSERVATION SECTION 101.4.9
 SHELL BUILDINGS A SUBMITTAL COMPLYING SHALL BE
 SUBMITTED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-07-02 Cont ID  
Sent By dharvey Date 2013-07-02 Time 12:41 Rev Time 0.00
Received By dharvey Date 2013-07-02 Time 12:20 Sent To  
Notes
2013-07-02 12:41:16BY RL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-07-02 Cont ID  
Sent By lphilmor Date 2013-06-21 Time 12:02 Rev Time 0.00
Received By dharvey Date 2013-07-02 Time 12:21 Sent To  
Notes
2013-07-02 12:22:52SEE SECOND REVIEW FOR ELECTRIC. RL
  
  
2013-06-21 12:02:028146-8160 OKEECHOBEE BLVD.
 PERMIT #13060228
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1. NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK
 INFORMATION.
 2. PROVIDE A LIFE SAFETY PLAN SHOWING ALL EXIT SIGNS,
 EMERGENCY LIGHTING, PORTABLE FIRE EXTINGUISHERS.
 3. PLAN INDICATES SUITES 1-8, BUT NO FIRE RATED WALLS
 PROVIDED.
 4. THUMB-TURN LOCK TO BE EQUIPPED WITH A LOCK/UNLOCK
 INDICATOR.
 5. CONSTRUCTION TYPE IS REFERENCED TO BE TYPE VB,
 HOWEVER, PLANS DO NOT APPEAR TO BE WOOD FRAMED
 STRUCTURE.
 6. PLANS INDICATE NO TENANT SEPARATION WALLS AND THE
 AREA IS INDICIATED AT 13,200 SQ. FT OF MERCANTILE
 OCCUPANCY. PER NFPA 101 SECTION 36.3.5.1(2) STIPULATES
 THAT SPRINKLERS ARE REQUIRED FOR MERCANTILE AREAS
 EXCEEDING 12,000 SQ FT IN GROSS AREA.
 7. PROVIDE TACTILE SIGNAGE AT ALL EXIT DOORS.
 8. PLANS INDICATE TWO HYDRANTS ON THE SITE. PLEASE
 INDICATE ANY ADDITIONAL HYDRANTS THAT MAY BE LOCATED TO
 THE EAST AND SOUTH OF THIS BUILDING.
  
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2013-08-12 Cont ID  
Sent By Mgonzale Date 2013-08-12 Time   Rev Time 1.00
Received By mgonzale Date 2013-08-12 Time   Sent To Z
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2014-05-19 Cont ID  
Sent By pleduc Date 2014-05-19 Time   Rev Time 0.00
Received By pleduc Date 2014-05-19 Time 10:48 Sent To  
Notes
2014-05-19 11:05:47THIS PLAN WAS REVIEWED AND PASSED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENT.
  
 NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-12-04 Cont ID  
Sent By lphilmor Date 2013-12-04 Time 15:05 Rev Time 0.00
Received By lphilmor Date 2013-12-04 Time 15:05 Sent To  
Notes
2013-12-04 15:07:31PERMIT # 13060228
 PLAN REVIEW COMMENTS - FIRE DEPT
  
 PLANS WILL BE STAMPED UPON SATISFACTION OF BUILDING
 REQUIREMENTS.
  
  
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-06-25 Cont ID  
Sent By lphilmor Date 2013-06-25 Time 14:20 Rev Time 0.00
Received By lphilmor Date 2013-06-25 Time 14:20 Sent To  
Notes
2013-06-25 14:20:228146-8160 OKEECHOBEE BLVD.
 PERMIT #13060228
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1. NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK
 INFORMATION.
 2. PROVIDE A LIFE SAFETY PLAN SHOWING ALL EXIT SIGNS,
 EMERGENCY LIGHTING, PORTABLE FIRE EXTINGUISHERS.
 3. PLAN INDICATES SUITES 1-8, BUT NO FIRE RATED WALLS
 PROVIDED.
 4. THUMB-TURN LOCK TO BE EQUIPPED WITH A LOCK/UNLOCK
 INDICATOR.
 5. CONSTRUCTION TYPE IS REFERENCED TO BE TYPE VB,
 HOWEVER, PLANS DO NOT APPEAR TO BE WOOD FRAMED
 STRUCTURE.
 6. PLANS INDICATE NO TENANT SEPARATION WALLS AND THE
 AREA IS INDICIATED AT 13,200 SQ. FT OF MERCANTILE
 OCCUPANCY. PER NFPA 101 SECTION 36.3.5.1(2) STIPULATES
 THAT SPRINKLERS ARE REQUIRED FOR MERCANTILE AREAS
 EXCEEDING 12,000 SQ FT IN GROSS AREA.
 7. PROVIDE TACTILE SIGNAGE AT ALL EXIT DOORS.
 8. PLANS INDICATE TWO HYDRANTS ON THE SITE. PLEASE
 INDICATE ANY ADDITIONAL HYDRANTS THAT MAY BE LOCATED TO
 THE EAST AND SOUTH OF THIS BUILDING.
  
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-11-04 Cont ID  
Sent By jwitmer Date 2014-11-04 Time 14:14 Rev Time 0.00
Received By jwitmer Date 2014-10-09 Time 15:15 Sent To  
Notes
2014-10-21 14:44:52TO ZONING
  
2014-10-09 15:17:13TO SH DESK FOR REVIEW OF ELEVATION CERTIFICATE
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-09-19 Cont ID  
Sent By jwitmer Date 2014-09-19 Time 09:38 Rev Time 0.00
Received By jwitmer Date 2014-09-18 Time 14:17 Sent To  
Notes
2014-09-18 14:17:43SENT TO J WITMER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-06-11 Cont ID  
Sent By albarran Date 2014-06-11 Time 15:12 Rev Time 0.00
Received By albarran Date 2014-05-09 Time 15:57 Sent To PC
Notes
2014-06-11 15:12:47APPROVED AS NOTED AND PROCESSED.
2014-05-14 16:09:50C30
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-06 Cont ID  
Sent By eschneid Date 2014-01-06 Time 14:42 Rev Time 0.00
Received By eschneid Date 2013-10-17 Time 09:16 Sent To  
Notes
2013-10-21 09:22:00C29
 NEW ELEC, PLUMBING, MECH SHEETS SUBMITTED
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-12 Cont ID  
Sent By jwitmer Date 2013-08-09 Time 09:55 Rev Time 0.00
Received By jwitmer Date 2013-06-06 Time 13:43 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status N Date 2014-09-19 Cont ID  
Sent By jwitmer Date 2014-09-19 Time 09:35 Rev Time 0.00
Received By jwitmer Date 2014-09-19 Time 09:35 Sent To  
Notes
2014-09-19 09:38:278146 OKEECHOBEE BLVD
 PERMIT 13060228
 IMPACT FEE ASSESSMENT
 RECEIPT NO. 2014-0918-271
 TRAKING NO. MU-2014-020571-0000
 FEES: $39,905.37

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2014-05-27 Cont ID  
Sent By jwitmer Date 2014-05-27 Time 17:15 Rev Time 0.00
Received By jwitmer Date 2014-05-27 Time 17:14 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-11-04 Cont ID  
Sent By jwitmer Date 2013-11-04 Time 13:04 Rev Time 0.00
Received By jwitmer Date 2013-11-04 Time 13:04 Sent To  
Notes
2013-11-04 13:04:20BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-07-11 Cont ID  
Sent By jwitmer Date 2013-07-11 Time 12:14 Rev Time 0.00
Received By jwitmer Date 2013-07-11 Time 12:14 Sent To  
Notes
2013-07-11 12:14:40BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-05-28 Cont ID  
Sent By hmoser Date 2014-05-28 Time 13:26 Rev Time 0.00
Received By hmoser Date 2014-05-28 Time 13:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-11-12 Cont ID  
Sent By hmoser Date 2013-11-12 Time 13:10 Rev Time 0.00
Received By hmoser Date 2013-11-12 Time 13:05 Sent To  
Notes
2013-11-12 13:06:32CURBS ONLY TO BE INSTALLED ON SHELL.
 AIRCONDITIONING PLAN AND ENERGY CALCULATION
 REQUIRED FOR EACH BUILDOUT.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-07-12 Cont ID  
Sent By hmoser Date 2013-07-12 Time 10:00 Rev Time 0.00
Received By hmoser Date 2013-07-12 Time 09:39 Sent To  
Notes
2013-07-12 09:59:56CURBS ONLY TO BE INSTALLED ON SHELL.
 AIR CONDITIONING PLANS AND ENERGY CALCULATIONS
 REQUIRED FOR EACH BUILD OUT.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2014-11-04 Cont ID  
Sent By jwitmer Date 2014-11-04 Time 14:19 Rev Time 0.00
Received By jwitmer Date 2014-11-04 Time 14:19 Sent To  
Notes
2014-11-04 14:19:52PROPOSED FLOOD ELEVATION CERTIFICATE.

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-05-27 Cont ID  
Sent By jwitmer Date 2014-05-27 Time 17:15 Rev Time 0.00
Received By jwitmer Date 2014-05-27 Time 09:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-10-30 Cont ID  
Sent By lwagner Date 2013-10-30 Time 10:11 Rev Time 0.00
Received By lwagner Date 2013-10-30 Time 09:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-06-19 Cont ID  
Sent By lwagner Date 2013-06-19 Time 14:34 Rev Time 0.00
Received By lwagner Date 2013-06-19 Time 14:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2014-10-30 Cont ID  
Sent By eschneid Date 2014-10-30 Time 08:48 Rev Time 0.50
Received By eschneid Date 2014-10-30 Time 08:48 Sent To B
Notes
2014-10-30 10:27:45PASSED
  
 SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE
 FOLLOWING:
  
 A. LANDSCAPE REQUIRES A SEPARATE PERMIT APPLICATION FOR
 EACH PARCEL (TRACT A & TRACT F) ON WHICH WORK IS BEING
 DONE. THE SAME 2 COPIES OF THE LANDSCAPE PLAN MAY BE
 USED FOR BOTH APPLICATIONS (SUBJECT TO CONCURRENT
 SUBMITTAL). A COST ESTIMATE IS REQUIRED WITH THE
 SUBMITTAL.
 B. SIGNAGE
 C. AWNINGS
 D. BICYCLE RACKS
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 3 Status F Date 2014-06-04 Cont ID  
Sent By eschneid Date 2014-06-04 Time 18:11 Rev Time 0.75
Received By eschneid Date 2014-06-04 Time 18:11 Sent To  
Notes
2014-06-04 18:12:20FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) REPEAT COMMENT: PURSUANT TO RESOLUTION NO. 288-11, A
 CONSTRUCTION SITE SECURITY AND MANAGEMENT PLAN SHALL BE
 SUBMITTED TO THE CITY'S POLICE DEPARTMENT CRIME
 PREVENTION THROUGH ENVIRONMENTAL DESIGN ("CPTED")
 OFFICIAL AND APPROVED PRIOR TO THE ISSUANCE OF THE
 BUILDING PERMIT. (CONTRARY TO THE RESPONSE COMMENT, NO
 PLAN HAS BEEN SUBMITTED TO OFFICER KELLY CARSILLO)
  
 I) THE APPLICANT, AFTER SITE CLEARING AND PLACEMENT OF
 CONSTRUCTION TRAILERS, SHALL INSTITUTE SECURITY
 MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES FOR
 THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT TO BE
 LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY AND TOOLS AT END OF
 WORK DAY AND/OR ANY OTHER MEASURE DEEMED APPROPRIATE TO
 PROVIDE A SAFE AND SECURE WORKING ENVIRONMENT.
 II) THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED DEVELOPMENT.
  
 2) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO.
 288-11, ALL ROOF MOUNTED AIR CONDITIONING, MECHANICAL
 EQUIPMENT, SATELLITE DISHES, GENERATORS, ETC., SHALL BE
 SCREENED FROM VIEW ON ALL SIDES BY A VISUALLY OPAQUE
 BARRIER CONSISTENT WITH THE COLOR, CHARACTER AND
 ARCHITECTURAL STYLE OF THE STRUCTURES OR EQUIVALENT
 LANDSCAPE MATERIAL. THE HEIGHT OF THE OPAQUE BARRIER
 SHALL BE AS REQUIRED TO PROVIDE AMPLE SCREENING.
 PROVIDE VERIFICATION THAT THE ROOFTOP MECHANICAL
 EQUIPMENT WILL BE SCREENED AS REQUIRED BY THE
 RESOLUTION FOR THE SPECIFIC EQUIPMENT PROPOSED FOR
 INSTALLATION (EX. LINE OF SIGHT OR ELEVATIONS WITH THE
 EQUIPMENT).
  
 3) NEW COMMENT: THE ELEVATION SUBMITTED WITH THE MINOR
 AMENDMENT DOES NOT MATCH THE ELEVATION SUBMITTED WITH
 THE BUILDING PERMIT - THE WINDOW ON THE SOUTH ELEVATION
 HAS BEEN REMOVED ON THE BUILDING PERMIT SUBMITTAL. THIS
 IS INTERNAL TO THE SITE, SO STAFF DOES NOT OBJECT TO
 THE REMOVAL OF THE WINDOW; HOWEVER, ALL PLANS SHALL
 MATCH.
  
 4) NEW COMMENT: THE CONSTRUCTION LAYOUT SURVEY
 INCORRECTLY DISPLAYS THE LENGTH OF THE SOUTH SECTION OF
 THE BUILDING (90 FEET INSTEAD OF 94 FEET). THE SOUTH
 SETBACK (23.4 FEET) DOES NOT COMPLY WITH THE SETBACK
 APPROVED ON THE SITE PLAN (19FEET).
  
 5) REPEAT COMMENT: PROVIDE A COPY OF THE REVISED SITE
 PLAN APPROVED BY ZONING THROUGH THE MINOR AMENDMENT
 PROCESS.
  
 SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE
 FOLLOWING:
  
 A. LANDSCAPE REQUIRES A SEPARATE PERMIT APPLICATION FOR
 EACH PARCEL (TRACT A & TRACT F) ON WHICH WORK IS BEING
 DONE. THE SAME 2 COPIES OF THE LANDSCAPE PLAN MAY BE
 USED FOR BOTH APPLICATIONS (SUBJECT TO CONCURRENT
 SUBMITTAL). A COST ESTIMATE IS REQUIRED WITH THE
 SUBMITTAL.
 B. SIGNAGE
 C. AWNINGS
 D. PARKING LOT STRIPING
 E. BICYCLE RACKS
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2014-05-15 16:21:215/15/14

Review Stop Z ZONING
Rev No 2 Status F Date 2014-01-06 Cont ID  
Sent By eschneid Date 2014-01-06 Time 14:40 Rev Time 1.00
Received By eschneid Date 2014-01-06 Time 14:40 Sent To  
Notes
2014-01-06 14:41:10FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) REPEAT COMMENT: PURSUANT TO THE PALM BEACH COUNTY
 TRAFFIC PERFORMANCE STANDARDS REVIEW LETTER ISSUED ON
 SEPTEMBER 17, 2009, NO BUILDING PERMITS SHALL BE ISSUED
 BY THE CITY AFTER DECEMBER 31, 2012. AN EXTENSION OF
 THIS DEADLINE MAY BE ISSUED BY PALM BEACH COUNTY. A
 MINOR PLANNED DEVELOPMENT AMENDMENT IS REQUIRED TO
 UPDATE THE COUNTY BUILD OUT DATE.
  
 2) REPEAT COMMENT: PURSUANT TO RESOLUTION NO. 288-11, A
 CONSTRUCTION SITE SECURITY AND MANAGEMENT PLAN SHALL BE
 SUBMITTED TO THE CITY'S POLICE DEPARTMENT CRIME
 PREVENTION THROUGH ENVIRONMENTAL DESIGN ("CPTED")
 OFFICIAL AND APPROVED PRIOR TO THE ISSUANCE OF THE
 BUILDING PERMIT. (CONTRARY TO THE RESPONSE COMMENT, NO
 PLAN HAS BEEN SUBMITTED TO OFFICER KELLY CARSILLO)
  
 I) THE APPLICANT, AFTER SITE CLEARING AND PLACEMENT OF
 CONSTRUCTION TRAILERS, SHALL INSTITUTE SECURITY
 MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES FOR
 THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT TO BE
 LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY AND TOOLS AT END OF
 WORK DAY AND/OR ANY OTHER MEASURE DEEMED APPROPRIATE TO
 PROVIDE A SAFE AND SECURE WORKING ENVIRONMENT.
 II) THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED DEVELOPMENT.
  
 3) PRIOR TO THIS ISSUANCE OF THE BUILDING PERMIT:
  
 I) REPEAT COMMENT: A SUFFICIENT UNITY OF TITLE TO
 COMBINE D & E SHALL BE SUBMITTED TO VINCE NOEL, CITY
 SURVEYOR AND THE UNITY OF TITLE SHALL BE RECORDED.
 II) REPEAT COMMENT: PROVIDE VERIFICATION THAT THE
 PORTION OF THE FPL EASEMENT, RECORDED IN ORB 1852, PG
 1500, WHICH IS LOCATED UNDER THE PROPOSED BUILDING
 SHALL HAS BEEN VACATED OR WILL BE ALLOWED TO BE VACATED
 BY FPL. ADDITIONALLY, ANY UTILITIES THAT WERE IN THE
 EASEMENT SHALL BE RELOCATED. THE CITY WOULD ISSUE THE
 PERMIT WITH A PROVISO THAT THE EASEMENT SHALL BE
 VACATED AND THE UTILITIES RELOCATED PRIOR TO THE FIRST
 INSPECTION.
  
 4) THE SQUARE FOOTAGE FOR BUILDING #5/6 HAS INCREASED
 140 SQUARE FEET FROM THE SEDONA COMMONS MASTER SITE
 PLAN APPROVED 13,200 SQUARE FEET. THE ADDITIONAL SQUARE
 FOOTAGE REQUIRES ONE MORE PARKING SPACE ON THE SITE AND
 A REVISED PALM BEACH COUNTY TRAFFIC LETTER APPROVING
 THE ADDITIONAL SQUARE FOOTAGE, ALL OF WHICH SHALL BE
 REFLECTED WITH THE MINOR AMENDMENT APPLICATION AND BE
 IN PLACE PRIOR TO THE APPROVAL OF THIS PERMIT BY
 ZONING.
  
 5) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO.
 288-11, ALL ROOF MOUNTED AIR CONDITIONING, MECHANICAL
 EQUIPMENT, SATELLITE DISHES, GENERATORS, ETC., SHALL BE
 SCREENED FROM VIEW ON ALL SIDES BY A VISUALLY OPAQUE
 BARRIER CONSISTENT WITH THE COLOR, CHARACTER AND
 ARCHITECTURAL STYLE OF THE STRUCTURES OR EQUIVALENT
 LANDSCAPE MATERIAL. THE HEIGHT OF THE OPAQUE BARRIER
 SHALL BE AS REQUIRED TO PROVIDE AMPLE SCREENING.
 PROVIDE VERIFICATION THAT THE ROOFTOP MECHANICAL
 EQUIPMENT WILL BE SCREENED AS REQUIRED BY THE
 RESOLUTION FOR THE SPECIFIC EQUIPMENT PROPOSED FOR
 INSTALLATION (EX. LINE OF SIGHT OR ELEVATIONS WITH THE
 EQUIPMENT).
  
 6) PROVIDE A COPY OF THE REVISED SITE PLAN ONCE IT IS
 APPROVED BY ZONING THROUGH THE MINOR AMENDMENT PROCESS.
  
 7) THE LANDSCAPE REQUIRES A SEPARATE PERMIT APPLICATION
 FOR EACH PARCEL (TRACT A & TRACTS D/E) ON WHICH WORK IS
 BEING DONE. THE SAME 2 COPIES OF THE LANDSCAPE PLAN MAY
 BE USED FOR BOTH APPLICATIONS (SUBJECT TO CONCURRENT
 SUBMITTAL). A COST ESTIMATE IS REQUIRED WITH THE
 SUBMITTAL.
  
 8) SIGNAGE AND AWNINGS REQUIRE SEPARATE PERMITS WITH
 PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2013-10-30 15:08:4110/29/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-06-24 Cont ID  
Sent By eschneid Date 2013-06-24 Time 14:41 Rev Time 3.00
Received By eschneid Date 2013-06-24 Time 11:01 Sent To  
Notes
2013-06-24 15:26:35FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) PURSUANT TO THE PALM BEACH COUNTY TRAFFIC
 PERFORMANCE STANDARDS REVIEW LETTER ISSUED ON SEPTEMBER
 17, 2009, NO BUILDING PERMITS SHALL BE ISSUED BY THE
 CITY AFTER DECEMBER 31, 2012. AN EXTENSION OF THIS
 DEADLINE MAY BE ISSUED BY PALM BEACH COUNTY. A MINOR
 PLANNED DEVELOPMENT AMENDMENT IS REQUIRED TO UPDATE THE
 THE COUNTY BUILD OUT DATE.
  
 2) PURSUANT TO RESOLUTION NO. 288-11, A CONSTRUCTION
 SITE SECURITY AND MANAGEMENT PLAN SHALL BE SUBMITTED TO
 THE CITY'S POLICE DEPARTMENT CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN ("CPTED") OFFICIAL AND APPROVED
 PRIOR TO THE ISSUANCE OF THE BUILDING PERMIT.
  
 I) THE APPLICANT, AFTER SITE CLEARING AND PLACEMENT OF
 CONSTRUCTION TRAILERS, SHALL INSTITUTE SECURITY
 MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES FOR
 THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT TO BE
 LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY AND TOOLS AT END OF
 WORK DAY AND/OR ANY OTHER MEASURE DEEMED APPROPRIATE TO
 PROVIDE A SAFE AND SECURE WORKING ENVIRONMENT.
 II) THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED DEVELOPMENT.
  
 3) PRIOR TO THIS ISSUANCE OF THE BUILDING PERMIT:
  
 I) A SUFFICIENT UNITY OF TITLE TO COMBINE D & E SHALL
 BE SUBMITTED TO VINCE NOEL, CITY SURVEYOR AND THE UNITY
 OF TITLE SHALL BE RECORDED.
 II) PROVIDE VERIFICATION THAT THE PORTION OF THE FPL
 EASEMENT, RECORDED IN ORB 1852, PG 1500, WHICH IS
 LOCATED UNDER THE PROPOSED BUILDING SHALL HAS BEEN
 VACATED. ADDITIONALLY, ANY UTILITIES THAT WERE IN THE
 EASEMENT SHALL BE RELOCATED.
  
 4) SHEETS A-1 AND A-2 STATE THAT THE OVERALL BUILDING
 LENGTH IS 297'4", WHILE THE SURVEY, SITE PLAN AND
 INDIVIDUAL PORTIONS OF THE BUILDING SHOWN 257'4".
  
 5) IN ACCORDANCE WITH RESOLUTION NO. 288-11, ALL ROOF
 MOUNTED AIR CONDITIONING, MECHANICAL EQUIPMENT,
 SATELLITE DISHES, GENERATORS, ETC., SHALL BE SCREENED
 FROM VIEW ON ALL SIDES BY A VISUALLY OPAQUE BARRIER
 CONSISTENT WITH THE COLOR, CHARACTER AND ARCHITECTURAL
 STYLE OF THE STRUCTURES OR EQUIVALENT LANDSCAPE
 MATERIAL. THE HEIGHT OF THE OPAQUE BARRIER SHALL BE AS
 REQUIRED TO PROVIDE AMPLE SCREENING. PROVIDE
 VERIFICATION THAT THE ROOFTOP MECHANICAL EQUIPMENT WILL
 BE SCREENED AS REQUIRED BY THE RESOLUTION FOR THE
 SPECIFIC EQUIPMENT PROPOSED FOR INSTALLATION (EX. LINE
 OF SIGHT OR ELEVATIONS WITH THE EQUIPMENT).
  
 6) THE APPROVED ELEVATIONS FOR BUILDING 5/6 HAVE
 CHANGED. THE BUILDING IS TALLER AND THE DOOR THAT WAS
 AT THE BACK OF SUITE #1 HAS NOW BECOME A WINDOW.
 REVISED ELEVATIONS ARE REQUIRED AS PART OF A MINOR
 PLANNED DEVELOPMENT AMENDMENT TO SHOW THE ACTUAL
 CONDITIONS.
  
 7) THE REMOVAL OF THE DOOR REQUIRES THE RELOCATION OF
 THE BICYCLE RACK AND PAD, AS THE RACK IS NO LONGER NEXT
 TO AN INGRESS/EGRESS POINT TO THE BUILDING. THE
 RELOCATED RACK AND PAD REQUIRES THE SITE PLAN AND
 LANDSCAPE PLAN TO BE UPDATED AS PART OF A MINOR
 AMENDMENT. PLEASE NOTE THAT THE BICYCLE RACK AND PAD IS
 SHOWN (NINE FEET) WIDER THAT IT NEEDS TO BE (SEVEN
 FEET), SO THERE IS AN OPPORTUNITY TO PLACE IT IN THE
 TERMINAL LANDSCAPE ISLAND ON THE NORTHWEST CORNER OF
 THE BUILDING. THE NEW BICYCLE PARKING LOCATION WOULD BE
 IN TRACT A AND MAY NOT BE INCLUDED ON THIS PERMIT. THE
 BICYCLE RACK AND PAD REQUIRE A SEPARATE PERMIT WITH THE
 DETAILS OF BOTH FEATURES.
  
 8) THE LANDSCAPE REQUIRES A SEPARATE PERMIT APPLICATION
 FOR EACH PARCEL (TRACT A & TRACTS D/E) ON WHICH WORK IS
 BEING DONE. THE SAME 2 COPIES OF THE LANDSCAPE PLAN MAY
 BE USED FOR BOTH APPLICATIONS (SUBJECT TO CONCURRENT
 SUBMITTAL). A COST ESTIMATE IS REQUIRED WITH THE
 SUBMITTAL.
  
 9) THE PLANS TO CONSTRUCT THE PARKING REQUIRED PRIOR TO
 THE C.O. OF THE LAST PHASE I BUILDING (GENERALLY ALONG
 THE SOUTH ACCESS DRIVE) SHALL BE INCLUDED ON A PARKING
 LOT STRIPING PERMIT FOR TRACT A PRIOR TO ZONING
 APPROVAL OF THIS PERMIT. STRIPING DETAILS FOR ALL
 CONDITIONS SHALL BE PROVIDED. THE PARKING SHALL BE
 INSTALLED PRIOR TO THE C.O. OF THIS BUILDING OR
 BUILDING 7, WHICHEVER OCCURS LAST.
  
 10) SIGNAGE AND AWNINGS REQUIRE SEPARATE PERMITS WITH
 PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.