Plan Review Details - Permit 13060101
Plan Review Stops For Permit 13060101
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-08-05 Cont ID  
Sent By jgomez Date 2013-08-05 Time 10:57 Rev Time 0.00
Received By jgomez Date 2013-08-05 Time 09:45 Sent To  
Notes
2013-08-05 09:55:52BUILDING REVIEW APPROVED WITH PROVISO:
 1- SOIL TEST REPORT SAYS "ALLOWABLE BEARING PRESSURE OF
 1,500 PSF". WHILE, ARCHITECT SPECIFIES ON THE
 FOUNDATION PLAN "SOIL BEARING CAPACITY MIN. 2500 PSF".
 EXISTING SOIL WILL NOT SUPPORT PROPOSED STRUCTURE. THIS
 NEEDS TO BE ADDRESSED BY THE ARCHITECT OF RECORD OR BY
 THE GEO-TECHNICAL ENGINEER.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A) GARAGE
 DOOR. NOA 12-0110.12 SUBMITTED EXPIRED ON MARCH 10,
 2013. B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS, DETAILS, SECTIONS AND SPECIFICATIONS. ONLY TWO
 CONNECTORS WERE SUBMITTED. C) PRECAST LINTELS. NOA
 11-0121.04 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE.
  
 3- ARCHITECT TO REVIEW AND APPROVE ABOVE PRODUCT
 APPROVALS.
  
 4- ARCHITECT TO SPECIFY ON PLANS DEAD LOADS, LIVE
 LOADS, AND THE ATTIC LIVE LIVE LOADS AS REQUIRED BY
 SEC. R301.1 AND TABLE R301.5 OF 2010 FBC-RESIDENTIAL.
 ***NOTE: SPECIFY EACH LOAD NOT JUST THE TOTAL LOADS.
  
 5- WALL SECTION ON SHEET 6 OF 6: CLARIFY WHAT IS "NO
 UN-INSULATED VENTED ATTIC"?. IS IT VENTED OR NOT???.
  
 6- SPECIFY R-VALUE IN WALL INSULATION. SEE ENERGY
 CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-07-24 Cont ID  
Sent By jgomez Date 2013-07-24 Time 08:56 Rev Time 0.00
Received By jgomez Date 2013-07-24 Time 08:56 Sent To  
Notes
2013-07-24 09:12:48RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) GARAGE DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ARCHITECT ON SHEET 3 OF 6. MIAMI-DADE
 NOA 12-0228.04 SUBMITTED DOESN'T MEET THE CALCULATED
 DESIGN PRESSURES. AND. IT WAS SUPERSEDED BY MIAMI-DADE.
 VISIT THE MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA
 THAT MEETS THE CALCULATED DESIGN PRESSURES.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS, DETAILS, SECTIONS AND SPECIFICATIONS. ***NOTE:
 PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND PAGE
 SHOWING SPECIFIED CONNECTOR. (NO DONE).
  
 C) PRECAST LINTELS AS SPECIFIED ON PLANS. (NO DONE).
  
 2- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL THE PRODUCT APPROVALS. SEC.
 107.3.4.1 CITY AMENDMENTS TO FBC. (NO DONE).
  
 3- SPECIFY ON PLANS CARBON MONOXIDE ALARMS AS REQUIRED
 BY SEC. R315 OF 2010 FBC-RESIDENTIAL. (NO DONE).
  
 4- SOIL TEST REPORT SUBMITTED STATES "ALLOWABLE BEARING
 PRESSURE OF 1,500 PSF". WHILE, ARCHITECT SPECIFIES ON
 THE FOUNDATION PLAN "SOIL BEARING CAPACITY MIN. 2500
 PSF". EXISTING SOIL WILL NOT SUPPORT PROPOSED
 STRUCTURE. THIS NEEDS TO BE ADDRESSED BY THE ARCHITECT
 OF RECORD OR BY THE GEOTECHNICAL ENGINEER. SEC.
 107.2.1.3 OF CITY AMENDMENTS TO FBC.
  
 5- ARCHITECT TO SPECIFY ON PLANS ALL DEAD AND LIVE
 LOADS INCLUDING THE ATTIC LIVE LIVE LOADS AS REQUIRED
 BY SEC. R301.1 AND TABLE R301.5 OF 2010
 FBC-RESIDENTIAL. (NO DONE).
  
 6- PROVIDE MANUFACTURER SPECS FOR THE ICYNENE
 INSULATION SPECIFIED ON PLANS AND ENERGY CALCULATIONS.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC. (NO DONE).
  
 7- SHEET 5 OF 6: A) IDENTIFY ROOF SHEATHING ZONES AS
 REQUIRED BY FIGURE R803.2.3.1 OF 2010 FBC-RESIDENTIAL.
 NOTE THAT GABLE END REQUIRES 5'-0". (NO DONE).
  
 B) SPECIFY TRUSS CONNECTORS FOR TRUSSES THAT ARE GOING
 TO BE SUPPORTED ON EXISTING MASONRY WALL BY THE NEW
 WALK IN CLOSET. SEC. 107.2.1 CITY AMENDMENTS. (NO
 DONE).
  
 8- WALL SECTION ON SHEET 6 OF 6; A) CLARIFY IF ATTIC IS
 DESIGNED TO BE VENTED OR UNVENTED. SEC. R806 OF 2010
 FBC-RESIDENTIAL. THERE IS ONE NOTE SAYING "MATCH
 EXISTING SOFFIT & VENTS", BUT THERE ARE SPECIFICATIONS
 FOR ICYNENE INSULATION IN THE ATTIC. REVISE AS REQUIRED
 TO MATCH. COORDINATE WITH ENERGY CALCULATIONS
 SUBMITTED. (NO DONE).
  
 B) IF DESIGNING VENTED ATTIC, THEN SPECIFY VENT SIZE
 AND SPACING. SEC. R806 OF 2010 FBC-RESIDENTIAL AND SEC.
 103 OF 2010 FBC-ENERGY CONSERVATION. (NO DONE).
  
 C) CLARIFY IF USING THE RIDGE VENT OR NOT. THERE WAS A
 PRODUCT APPROVAL SUBMITTED FOR RIDGE VENT. ARCHITECT TO
 SPECIFY ON PLANS THE RIDGE VENT IF USING IT. SEC.
 107.2.1 CITY AMENDMENTS. (NO DONE).
  
 D) IF DESIGNING UNVENTED ATTIC, THEN, SPECIFY R-VALUE
 FOR THE ICYNENE INSULATION. SEC. 103 OF 2010 FBC-ENERGY
 CONSERVATION. COORDINATE WITH ENERGY CALCULATIONS. (NO
 DONE).
  
 F) SPECIFY R-VALUE IN WALL INSULATION. COORDINATE WITH
 ENERGY CALCULATIONS. SEC. 103 OF 2010 FBC-ENERGY
 CONSERVATION. (NO DONE).
  
 9- NEW TRUSS PACKAGE SUBMITTED (CHAPTER 471 FLORIDA
 STATUTE AND SEC. 61G15-31.003):
 A) COVER SHEET NEEDS TRUSS ENGINEER ORIGINAL SIGNATURE.
 NOT COPY.
  
 B) COVER PAGE IS MISSING THE MAME AND LICENSE NUMBER OF
 THE BUILDING DESIGNER OF RECORD.
  
 C) DESIGNER OF RECORD TO REVIEW AND APPROVE TRUSS
 PACKAGE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date 2013-07-16 Cont ID  
Sent By jgomez Date 2013-07-16 Time 10:31 Rev Time 0.00
Received By jgomez Date 2013-07-16 Time 10:31 Sent To  
Notes
2013-07-16 10:39:38 
 ***REVIEW IN PROGRESS...
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-20 Cont ID  
Sent By jgomez Date 2013-06-19 Time 16:52 Rev Time 0.00
Received By jgomez Date 2013-06-19 Time 16:29 Sent To  
Notes
2013-06-19 16:52:52RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF THE PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE
 COUNTY IMPACT FEE UNIFIED LAND DEVELOPMENT CODE.
  
 2- CARPORT AREA SHEET 3 OF 6:
 A) PLANS SHOW INSTALLATION OF NEW GARAGE DOOR IN THE
 CARPORT. THIS WILL AFFECT THE STRUCTURAL STABILITY OF
 THE HOUSE. THE HOUSE WAS DESIGNED FOR AN OPEN CARPORT.
 THE NEW FRONT WALL AND GARAGE DOOR WILL CREATE MORE
 WIND LOADS TO THE ROOF ABOVE CARPORT AND SIDE WALLS.
 PROVIDE ENGINEERING ANALYSIS FOR THE PROPOSED
 INSTALLATION. AND, PROVIDE COMPLETE SPECS AND DETAILS
 SHOWING REINFORCEMENT, IF REQUIRED TO RESIST THE
 ADDITIONAL LOADS. SEC. 107.2.1.3 CITY AMENDMENTS TO
 FBC. ALSO, COORDINATE WITH ITEM #3 BELOW.
  
 B) PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR THE
 GARAGE DOOR STRUCTURAL BUCK DETAIL ATTACHMENT. THIS IS
 THE DESIGNER OF RECORD RESPONSIBILITY, NOT THE PRODUCT
 APPROVALS AS SPECIFIED ON "GARAGE DOOR BUCKS" NOTE ON
 SHEET 3 OF 6. STRUCTURAL BUCK DETAIL TO RESIST THE
 DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) GARAGE DOOR AS SHOWN ON PLANS. *** NOTE: NEED
 PRODUCT APPROVAL FOR GARAGE DOOR THAT IS DESIGNED TO
 RECEIVE THE WIND LOADS FROM BOTH SIDES AS SHOWN ON
 PLANS. COORDINATE WITH ITEM #2 ABOVE.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS, DETAILS, SECTIONS AND SPECIFICATIONS. ***NOTE:
 PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND PAGE
 SHOWING SPECIFIED CONNECTOR.
  
 C) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL THE PRODUCT APPROVALS. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 5- SPECIFY ON PLANS CARBON MONOXIDE ALARMS AS REQUIRED
 BY SEC. R315 OF 2010 FBC-RESIDENTIAL.
  
 6- A) SOIL TEST REPORT SUBMITTED IS INCOMPLETE. IS
 MISSING THE ENGINEERING INFORMATION CONTAINED IN A
 TYPICAL SOIL TEST REPORT. THE REPORT IS MISSING THE
 RECOMMENDATIONS FOR DESIGN, ESTIMATED SETTLEMENT, SOIL
 PREPARATION INCLUDING NEW FILL, ETC. SEC. 107.2.1.3
 CITY AMENDMENTS.
  
 B) ENGINEER SEALING THE REPORT TO USE CURRENT SEAL AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE. SEAL USED IS
 NO LONGER VALID SINCE JANUARY 2006.
  
 C) PROVIDE SOIL TEST REPORT (2 COPIES) WITH ORIGINAL
 ENGINEER'S SEAL AND SIGNATURE, NOT COPY. SEC. 471
 FLORIDA STATUTE.
  
 7- VALUED DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUES WAS UPDATED AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS TO FBC. VALUATION TO INCLUDE SOIL
 PREPARATION, ALL LABOR AND MATERIALS, ALL PROFESSIONAL
 DESIGN FEES. ESTIMATED VALUE IS $83,040. PERMIT FEE
 BALANCE IS $2303.04.
  
 8- ARCHITECT TO SPECIFY ON PLANS ALL DEAD AND LIVE
 LOADS INCLUDING THE ATTIC LIVE LIVE LOADS AS REQUIRED
 BY SEC. R301.1 AND TABLE R301.5 OF 2010
 FBC-RESIDENTIAL.
  
 9- PROVIDE MANUFACTURER SPECS FOR THE ICYNENE
 INSULATION SPECIFIED ON PLANS AND ENERGY CALCULATIONS.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 10- SOIL TEST REPORT SUBMITTED STATES THAT SOIL BEARING
 CAPACITY IS 2,000 PSF. ARCHITECT'S PLANS AND DETAILS
 REQUIRE 2500PSF SOIL BEARING CAPACITY. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 11- SHEET 5 OF 6: A) REVISE ROOF SHEATHING NOTES: NEED
 TO SPECIFY MIN. 8D RING SHANK NAILS AT 4"-0" IN ROOF
 ZONE #3 AS REQUIRED BY SEC. R803.2.3.1 OF 2010
 FBC-RESIDENTIAL.
  
 B) IDENTIFY ROOF SHEATHING ZONES AS REQUIRED BY FIGURE
 R803.2.3.1 OF 2010 FBC-RESIDENTIAL. NOTE THAT GABLE END
 REQUIRES 5'-0".
  
 C) SPECIFY TRUSS CONNECTORS FOR TRUSSES THAT ARE GOING
 TO BE SUPPORTED ON EXISTING MASONRY WALL BY THE NEW
 WALK IN CLOSET. SEC. 107.2.1 CITY AMENDMENTS.
  
 12- WALL SECTION ON SHEET 6 OF 6; A) CLARIFY IF ATTIC
 IS DESIGNED TO BE VENTED OR UNVENTED. SEC. R806 OF 2010
 FBC-RESIDENTIAL. THERE IS ONE NOTE SAYING "MATCH
 EXISTING SOFFIT & VENTS", BUT THERE ARE SPECIFICATIONS
 FOR ICYNENE INSULATION IN THE ATTIC. REVISE AS REQUIRED
 TO MATCH. COORDINATE WITH ENERGY CALCULATIONS
 SUBMITTED.
  
 B) IF DESIGNING VENTED ATTIC, THEN SPECIFY VENT SIZE
 AND SPACING. SEC. R806 OF 2010 FBC-RESIDENTIAL AND SEC.
 103 OF 2010 FBC-ENERGY CONSERVATION.
  
 C) CLARIFY IF USING THE RIDGE VENT OR NOT. THERE WAS A
 PRODUCT APPROVAL SUBMITTED FOR RIDGE VENT. ARCHITECT TO
 SPECIFY ON PLANS THE RIDGE VENT IF USING IT. SEC.
 107.2.1 CITY AMENDMENTS.
  
 D) IF DESIGNING UNVENTED ATTIC, THEN, SPECIFY R-VALUE
 FOR THE ICYNENE INSULATION. SEC. 103 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 F) SPECIFY R-VALUE IN WALL INSULATION. COORDINATE WITH
 ENERGY CALCULATIONS. SEC. 103 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 13- TRUSS PACKAGE (CHAPTER 471 FLORIDA STATUTE AND SEC.
 61G15-31.003):
 A) TRUSS ENGINEER TO PROVIDE TITLE BLOCK ON EACH SHEET.
  
 B) TRUSS ENGINEER TO USE CURRENT SEAL. SEAL USED IS NO
 VALID SINCE JANUARY 2006.
  
 C) ALL THE SHEETS NEED TO BE NUMBERED AND COORDINATED
 WITH COVER SHEET.
  
 D) TRUSS ENGINEER NEED TO UPDATE HIS LICENSE WITH DPBR.
  
 E) DESIGNER OF RECORD TO REVIEW AND APPROVE TRUSS
 PACKAGE. PERSON WHO REVIEWED TRUSS PACKAGE IS NOT THE
 SAME SIGNING AND SEALING THE PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-08-05 Cont ID  
Sent By rmcdouga Date 2013-08-05 Time 16:02 Rev Time 0.00
Received By rmcdouga Date 2013-08-05 Time 16:02 Sent To  
Notes
2013-08-05 16:03:13RESTAMP PLANS. PASSED WITH EXCEPTION TO ADDRESS ALL
 DEFICIENCIES RED-LINED ON ELECTRICAL PLANS.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-06-05 Cont ID  
Sent By dharvey Date 2013-06-05 Time 11:20 Rev Time 0.00
Received By dharvey Date 2013-06-05 Time 11:20 Sent To  
Notes
2013-06-05 11:21:106-5-13
  
 APPROVED WITH EXCEPTION. SEE NOTES ON DRAWING
 VB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-08-05 Cont ID  
Sent By jgomez Date 2013-08-05 Time 14:04 Rev Time 0.00
Received By jgomez Date 2013-08-01 Time 14:04 Sent To  
Notes
2013-08-01 14:04:46SENT TO J. G. DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-07-24 Cont ID  
Sent By jgomez Date 2013-07-24 Time 15:04 Rev Time 0.00
Received By jgomez Date 2013-07-19 Time 14:24 Sent To  
Notes
2013-07-19 14:24:37INCOMING SENT TO R19 BOX . JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-24 Cont ID  
Sent By jgomez Date 2013-07-24 Time 15:04 Rev Time 0.00
Received By jgomez Date 2013-07-11 Time 12:14 Sent To  
Notes
2013-07-12 12:16:35R19
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-26 Cont ID  
Sent By jgomez Date 2013-06-26 Time 10:40 Rev Time 0.00
Received By jgomez Date 2013-06-04 Time 17:07 Sent To  
Notes
2013-06-04 17:25:28*EXPEDITED*
 R--13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2013-08-05 Cont ID  
Sent By jgomez Date 2013-08-05 Time 14:35 Rev Time 0.00
Received By jgomez Date 2013-08-05 Time 14:35 Sent To  
Notes
2013-08-05 14:36:01MU-2013-16181. CALLED COUNTY TO VERIFY IF IMPACT FEES
 WERE PAID. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2013-07-24 Cont ID  
Sent By jgomez Date 2013-07-24 Time 14:31 Rev Time 0.00
Received By jgomez Date 2013-07-24 Time 14:31 Sent To  
Notes
2013-07-24 14:32:081- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF THE PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE
 COUNTY IMPACT FEE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-07-16 Cont ID  
Sent By jgomez Date 2013-07-16 Time 10:40 Rev Time 0.00
Received By jgomez Date 2013-07-16 Time 10:40 Sent To  
Notes
2013-07-16 10:40:191- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF THE PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE
 COUNTY IMPACT FEE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-06-20 Cont ID  
Sent By jgomez Date 2013-06-20 Time 07:54 Rev Time 0.00
Received By jgomez Date 2013-06-20 Time 07:54 Sent To  
Notes
2013-06-20 07:54:251- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF THE PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE
 COUNTY IMPACT FEE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-08-05 Cont ID  
Sent By jgomez Date 2013-08-05 Time 14:37 Rev Time 0.00
Received By jgomez Date 2013-08-05 Time 14:37 Sent To  
Notes
2013-08-05 14:45:27MECHANICAL REVIEW APPROVED WITH PROVISO:
 1- REVISE THE EQUIPMENT SIZING CALCULATIONS. THERE IS A
 MISMATCH ON THE OUTDOOR UNIT AND THE INDOOR UNIT
 SPECIFIED ON THE EQUIPMENT DATA SHEET. THEY ARE TWO
 DIFFERENT COMPANIES. THE OUTDOOR UNIT CORRESPONDS TO
 "CARRIER", WHILE THE INDOOR UNIT CORRESPONDS TO
 "TRANE".
  
 2- PROVIDE ALL THE EQUIPMENT INFORMATION ON THE A/C
 PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-07-24 Cont ID  
Sent By jgomez Date 2013-07-24 Time 14:33 Rev Time 0.00
Received By jgomez Date 2013-07-24 Time 14:32 Sent To  
Notes
2013-07-24 14:40:01RESIDENTIAL (R3) ADDITION, SECOND MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE THE EQUIPMENT SIZING CALCULATIONS. THERE IS A
 MISMATCH ON THE OUTDOOR UNIT AND THE INDOOR UNIT
 SPECIFIED ON THE EQUIPMENT DATA SHEET. THEY ARE TWO
 DIFFERENT COMPANIES. THE OUTDOOR UNIT CORRESPONDS TO
 "CARRIER", WHILE THE INDOOR UNIT CORRESPONDS TO
 "TRANE". SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
 (NO DONE).
  
 2- PROVIDE ALL THE EQUIPMENT INFORMATION ON THE A/C
 PLAN. SEC. 107.3.5.3(10) OF CITY AMENDMENTS TO FBC. (NO
 DONE).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-06-26 Cont ID  
Sent By jgomez Date 2013-06-26 Time 10:28 Rev Time 0.00
Received By jgomez Date 2013-06-26 Time 10:28 Sent To  
Notes
2013-06-26 10:40:08RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE THE EQUIPMENT SIZING CALCULATIONS. THERE IS A
 MISMATCH ON THE OUTDOOR UNIT AND THE INDOOR UNIT
 SPECIFIED ON THE EQUIPMENT DATA SHEET. THEY ARE TWO
 DIFFERENT COMPANIES. THE OUTDOOR UNIT CORRESPONDS TO
 "CARRIER", WHILE THE INDOOR UNIT CORRESPONDS TO
 "TRANE". SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- PROVIDE ALL THE EQUIPMENT INFORMATION ON THE A/C
 PLAN. SEC. 107.3.5.3(10) OF CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 3 Status P Date 2013-08-05 Cont ID  
Sent By jgomez Date 2013-08-05 Time 14:23 Rev Time 0.00
Received By jgomez Date 2013-08-05 Time 14:23 Sent To  
Notes
2013-08-05 14:26:01PLUMBING REVIEW APPROVED WITH PROVISO:
 1- REVISE PLUMBING RISER DIAGRAM. "NOT MORE THAN ONE
 WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF
 THE DRY-VENTED FIXTURE DRAIN CONNECTION". SEC.
 P3108.2.1 OF 2010 FBC-RESIDENTIAL

Review Stop P PLUMBING
Rev No 2 Status F Date 2013-07-24 Cont ID  
Sent By jgomez Date 2013-07-24 Time 14:51 Rev Time 0.00
Received By jgomez Date 2013-07-24 Time 14:40 Sent To  
Notes
2013-07-24 14:51:41RESIDENTIAL (R3) ADDITION, SECOND PLUMBING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISED PLUMBING RISER DIAGRAM SUBMITTED DOESN'T
 COMPLY WITH THE VENTING REQUIREMENTS OF SEC. P3108.2.1
 OF 2010 FBC-RESIDENTIAL. "NOT MORE THAN ONE WET-VENTED
 FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF THE
 DRY-VENTED FIXTURE DRAIN CONNECTION". REVISED PLUMBING
 RISER DIAGRAM SHOWS THE TUB AND SHOWER UPSTREAM OF THE
 DRY-VENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-06-20 Cont ID  
Sent By jgomez Date 2013-06-20 Time 11:24 Rev Time 0.00
Received By jgomez Date 2013-06-20 Time 11:24 Sent To  
Notes
2013-06-20 11:30:19RESIDENTIAL (R3) ADDITION, PLUMBING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PLUMBING RISER DIAGRAM DOESN'T MATCH PLANS. MISSING
 THE SHOWER. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 1 Status P Date 2013-06-14 Cont ID  
Sent By ajones Date 2013-06-14 Time 14:20 Rev Time 0.00
Received By ajones Date 2013-06-14 Time 14:20 Sent To  
Notes
***NONE***