Plan Review Details - Permit 13060023
Plan Review Stops For Permit 13060023
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-08-17 Cont ID  
Sent By JWITMER Date 2013-08-17 Time 08:00 Rev Time 0.00
Received By jwitmer Date 2013-08-17 Time 07:02 Sent To  
Notes
2013-08-17 07:21:24BUILDING PROVISO:
  
 SHEET A.1.721 DETAIL (E) H. C. FITTING ROOMS /
 (ACCESSBILE FITTING ROOMS)
 PROVIDE COMPLIANCE WITH 2010 FLORIDA ACCESSIBILITY
 CODE:
 903.4 BACK SUPPORT.
 THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE
 AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 INCHES
 (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A POINT 2
 INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE TO A
 POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM)
 MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED
 HORIZONTALLY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-07-03 Cont ID  
Sent By jwitmer Date 2013-07-03 Time 16:00 Rev Time 0.00
Received By jwitmer Date 2013-07-03 Time 14:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-09-12 Cont ID  
Sent By D HARVEY Date 2013-09-12 Time 14:28 Rev Time 0.00
Received By dharvey Date 2013-09-12 Time 13:14 Sent To  
Notes
2013-09-12 14:29:4313060023
 1751 PALM BEACH LAKES BLVD. #E103
 INTERIOR BUILD OUT FOR AMERICAN EAGLE OUTFITTERS
  
 PERMIT MAY BE ISSUED WITH THE FOLLOWING PROVISO:
  
 PROVIDE A DESIGNATED CLEAR WORKING SPACE AROUND THE
 ELECTRICAL SERVICE EQUIPMENT AND PANEL BOARDS. NEC
 215.5, 110.26
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-07-02 Cont ID  
Sent By dharvey Date 2013-07-02 Time 15:09 Rev Time 0.00
Received By dharvey Date 2013-07-02 Time 13:53 Sent To  
Notes
2013-07-02 15:11:3113060023
 1751 PALM BEACH LAKES BLVD. #E103
 INTERIOR BUILD OUT FOR AMERICAN EAGLE OUTFITTERS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
  
 SHEET E.0.200
  
 PROVIDE A DESIGNATED CLEAR WORKING SPACE AROUND THE
 ELECTRICAL SERVICE EQUIPMENT AND PANEL BOARDS. NEC
 215.5, 110.26
  
 SHEET E.0.300
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.22, 110.16, 110.22
  
  
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-08-13 Cont ID  
Sent By WJOLIN Date 2013-08-09 Time 14:41 Rev Time 0.00
Received By scaldero Date 2013-08-09 Time 14:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-06-15 Cont ID  
Sent By wjolin Date 2013-06-15 Time 14:02 Rev Time 0.00
Received By wjolin Date 2013-06-15 Time 12:53 Sent To  
Notes
2013-06-15 14:01:571751 PALM BEACH LAKES BOULEVARD - SUITE #103 (AMERICAN
 EAGLE OUTFITTERS)
 PERMIT #13060023
 MASTER #12100555
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-09-12 Cont ID  
Sent By dharvey Date 2013-09-12 Time 14:29 Rev Time 0.00
Received By dharvey Date 2013-07-30 Time 07:03 Sent To  
Notes
2013-08-29 15:50:09C28
  
  
2013-07-31 07:03:51B38

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-10 Cont ID  
Sent By hmoser Date 2013-07-10 Time 14:28 Rev Time 0.00
Received By hmoser Date 2013-06-03 Time 09:38 Sent To  
Notes
2013-06-04 09:39:31C20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2013-07-03 Cont ID  
Sent By jwitmer Date 2013-07-03 Time 15:18 Rev Time 0.00
Received By jwitmer Date 2013-07-03 Time 15:18 Sent To  
Notes
2013-07-03 15:19:03NOT REQUIRED, USE CREDITS. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-09-07 Cont ID  
Sent By HMOSER Date 2013-09-07 Time 09:18 Rev Time 0.00
Received By hmoser Date 2013-09-07 Time 08:54 Sent To  
Notes
2013-09-07 09:11:41PASS PROVISO
 CURB TIEDOWN DETAIL WAS PROVIDED BY ENGINEER WITH SHELL
 CONTRACTOR.
 IF EQUIPMENT IS CHANGED AND EXISTING CURB CAN NOT BE
 USED
 PROVIDE A DETAIL FROM THE ENGINEER SHOWING CURB TIE
 DOWN TO ROOF
 OR CURB EXTENSION TIED TO CURB AND RTU TIED TO CURB,AT
 FINAL INSPECTION.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-07-10 Cont ID  
Sent By hmoser Date 2013-07-10 Time 14:28 Rev Time 0.00
Received By hmoser Date 2013-07-10 Time 11:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-06-06 Cont ID  
Sent By lwagner Date 2013-06-06 Time 10:59 Rev Time 0.00
Received By lwagner Date 2013-06-06 Time 09:04 Sent To  
Notes
2013-06-06 11:02:14FACILITIES WILL BE EXISTING

Review Stop POLICE POLICE
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2013-09-16 Time   Rev Time 0.00
Received By ktucker Date 2013-09-16 Time 11:01 Sent To  
Notes
2013-09-16 11:02:07CRIME PREVENTION THROUGH ENVIRONMENTAL DESIGN
 THE CITY OF WEST PALM BEACH HAS RECOGNIZED THAT
 TRADITIONAL CRIME PREVENTION STRATEGIES ARE NOT ENOUGH
 IN TODAY?S SOCIETY AND A NEW APPROACH IS NEEDED. THE
 NAME OF THIS APPROACH IS CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN (CPTED). CPTED ACKNOWLEDGES THAT
 THE MANNER IN WHICH PHYSICAL SPACE IS DESIGNED OR USED
 HAS A DIRECT BEARING ON CRIME AND SECURITY.
 THE PHYSICAL ENVIRONMENT HAS A DRAMATIC EFFECT ON OUR
 OWN BEHAVIOR AND THE WAY IN WHICH WE VIEW THE BEHAVIOR
 OF OTHERS. CPTED IS A CONCEPT SUPPORTED BY A SERIES OF
 OVERLAPPING PRINCIPLES BASED ON THE RELATIONSHIP OF THE
 BUILT ENVIRONMENT TO THE PRESENCE OR ABSENCE OF
 UNDESIRABLE BEHAVIOR. THE CPTED CONCEPT IS: ?THE PROPER
 DESIGN AND EFFECTIVE USE OF THE BUILT ENVIRONMENT CAN
 LEAD TO A REDUCTION IN THE INCIDENCE AND FEAR OF CRIME
 AND IMPROVEMENT IN THE QUALITY OF LIFE BY INCORPORATING
 ACCESS CONTROL, NATURAL SURVEILLANCE AND TERRITORIAL
 DEFENSIVE TACTICS.?
 CPTED THEORY IS BASED UPON THE CONTENTION THAT
 PLANNERS, DESIGNERS, ARCHITECTS, LANDSCAPERS AND LAW
 ENFORCEMENT CAN COOPERATIVELY CREATE A ?SAFE? CLIMATE
 WITHIN A BUILT ENVIRONMENT ? RIGHT FROM THE BEGINNING.
 SAFETY STRIKES AT THE VERY CORE OF WHAT IS GENERALLY
 REFERRED TO IN A COMMUNITY AS ?QUALITY OF LIFE.? A SAFE
 ENVIRONMENT IS ONE THAT REGULAR USERS PERCEIVE AS SAFE
 AND NON-USERS (CRIMINALS) PERCEIVE AS HIGHLY RISKY TO
 FREQUENT AND IN WHICH TO COMMIT CRIMES.
 THE WEST PALM BEACH POLICE DEPARTMENT HAS OUTLINED
 GUIDELINES WE WOULD LIKE TO SEE FOLLOWED. IN ADDITION
 TO THE GUIDELINES, WE ENCOURAGE YOU TO PLEASE ADOPT
 THESE MINIMUM STANDARDS:
  
 (1) A FULLY FUNCTIONING AND OPERATIONAL CCTV SYSTEM
 CAPABLE OF RECORDING AND RETRIEVING ON SITE, AN
 IDENTIFIABLE IMAGE TO ASSIST IN OFFENDER IDENTIFICATION
 AND APPREHENSION. MONITORS FOR THE SYSTEM SHOULD BE
 PLACED IN A MANAGER?S OFFICE OR BACK ROOM, WITH A
 MONITOR IN PUBLIC VIEW FROM THE SALES FLOOR.
 (2) CAMERA COVERAGE SHOULD BE AT SENSITIVE LOCATIONS:
 (A) DOORS THAT LEADS TO THE BACK OF HOUSE (B) HALLWAYS
 THAT LEAD TO REAR EXITS (C) SALES FLOOR (D) REGISTERS
 (LOW FOR FACIAL RECOGNITION) (E) FRONT ENTRY.
 (3) DOOR THAT LEADS TO THE BACK OF HOUSE AND EXITING
 REAR DOORS SHOULD BE ALARMED WITH A SENSOR AND VIEW
 FINDER.
 (4) SILENT PANIC ALARM UNDER EACH REGISTER, ONE IN THE
 BACK OF HOUSE WORK AREA
 (5) A SECURED DROP SAFE OR CASH MANAGEMENT DEVICE FOR
 RESTRICTED ACCESS TO MONEY/CASH RECEIPTS AT THE
 REGISTER AND A SECURED DROP SAFE OR CASH MANAGEMENT
 DEVICE IN THE STORAGE AREA.
 (6) CASH OUT AREA SHOULD BE IN THE FRONT OF THE STORE,
 CLOSE TO THE ENTRANCE.
 (7) SECURE THE REGISTERS TO THE COUNTER.
 (8) INSTALL ANTI-THEFT DEVICES INCLUDING SECURITY
 TOWERS AT ENTRANCES.
 (9) USE CONVEX MIRRORS IN CORNERS AND ANTI-THEFT TAGS
 ON MERCHANDISE.
 (10) HEIGHT MARKERS AT THE ENTRANCE AND EXIT.
 (11) EMPLOYEE ACCESS CONTROL ON ALL DOORS THAT LEAD
 INTO THE BACK.
 (12) WHERE WINDOW(S) ARE PRESENT, A CLEAR AND
 UNOBSTRUCTED VIEW FROM OUTSIDE THE STORE AND IN A
 NORMAL LINE OF SIGHT OF THE CASH REGISTER AND SALES
 TRANSACTION AREA
 (13) IF INSTALLING SWING GATE AT REGISTERS THEY SHOULD
 HAVE SIMPLE ACCESS CONTROL.
 (14) ALL SHOWCASES SHOULD HAVE LOCKS AND IN THE
 EXPENSIVE SHOWCASES, CONSIDER AN ALARM.
 (15) INTERIOR SHELVING AND DISPLAYS SHOULD BE NO HIGHER
 THAN FIVE FEET, EVEN LESS IN FRONT OF WINDOWS.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2013-08-22 Cont ID  
Sent By ESCHNEID Date 2013-08-22 Time 11:34 Rev Time 0.50
Received By eschneid Date 2013-08-22 Time 11:34 Sent To  
Notes
2013-08-22 11:34:38EXTERIOR SIGNAGE AND THE AWNINGS REQUIRE SEPARATE
 PERMITS.
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-06-25 Cont ID  
Sent By eschneid Date 2013-06-25 Time 09:05 Rev Time 0.50
Received By eschneid Date 2013-06-10 Time 15:26 Sent To  
Notes
2013-06-25 09:06:14EXTERIOR SIGNAGE AND THE AWNINGS REQUIRE SEPARATE
 PERMITS.
  
  